![](/html/ec/ec3c/ec3cf0a5d83b2a282c60b1a2d54cb2d7b8d747682832e41a708cdd8be1fd6b82/bg1.png)
Fire Alarm Systems | FAA-440 Analog Bases
FAA-440 Analog Bases
www.boschsecurity.com
u Modular design
u Easy detector removal for cleaning and servicing
u Stable mounting of detectors
The FAA‑440 Analog Bases come in two sizes (4 in.
[10 cm] and 6 in. [16 cm]) and two models (Standard
and ISO which has a built‑in isolator). They are used in
combination with FAP-440 and FAH-440 analog
addressable detectors to provide early fire warning for
life safety and property protection.
Functions
Indicator LED (Isolator Bases)
In the event of a short circuit, the isolator base LED
will show a steady yellow signaling a trouble condition.
Modular Design
The detector base is part of a two-piece modular
designed detector assembly. The permanently
installed base provides in and out terminals for the
polling circuit.
Preservation of loop
It contains a simple rugged design with terminal
screws for wiring and preserves loop continuity when
detectors are removed.
u Terminal screws for remote LED, Data In and Out
provided
u Some models include isolator circuitry which
prevents the entire SLC loop from being disabled
when a short circuit occurs
Locking System
A simple tamper‑proof locking system is provided
which can be enabled by removing a small plastic tab
on the back of the detector. Once locked, the detector
can only be removed by using a small screw driver.
Certifications and approvals
Region Certification
USA UL UROX Smoke-automatic Fire Detectors
(ANSI/UL 268)
CSFM see our website
Installation/configuration notes
Compatible Products
The following products are compatible with the
FAA‑440 Analog Bases:
Category Product ID Product Description
Fire Panels FPA‑1000
Analog Addressable Fire Panels
family
Fire Panel
Accessories
FPE‑1000‑SLC Signaling Line Circuit Plug‑in
Module
Detectors FAH‑440 Analog Heat Detector
![](/html/ec/ec3c/ec3cf0a5d83b2a282c60b1a2d54cb2d7b8d747682832e41a708cdd8be1fd6b82/bg2.png)
2 | FAA-440 Analog Bases
FAP‑440 Analog Photoelectric Detector
FAP‑440‑D Analog Dual Ray Photoelectric
Detector
FAP‑440‑DT Analog Dual Ray Multisensor
Detector Photo/Heat
FAP‑440‑DTC Analog Dual Ray Multicriteria
Detector Photo/Heat/CO
FAP-440-T Analog Multisensor Detector
Photo/Heat
FAP-440-TC Analog Multicriteria Detector
Photo/Heat/CO
Mounting Considerations
Detectors are typically mounted on the ceiling.
However, if detectors are mounted on a wall, they
must be at least 4 in. (10.2 cm), but no more than
12 in. (30.5 cm), below the ceiling. When other
devices containing magnets or producing magnetic
fields (for example, loudspeakers) are present in the
area, the base must be at least 1 ft (30 cm) from these
devices to prevent unwanted activation of the test
switch.
For UL Listing requirements, the spacing between smoke
detectors should be no more than 30 ft (9.14 m and the
spacing between heat detectors should be no more than
50 ft (15.24 m).
Wiring Considerations
The control panel communicates to the detectors via
the analog addressable loop (SLC), which allows the
use of standard non‑twisted, non‑shielded wiring.
The following wire gauges were tested and approved:
Technical specifications
Electrical (Isolator Bases)
Maximum current consumption at 77°F (25°C) and 39 V bus voltage
• Standby: 0.07 mA
• Alarm: 10 mA
Operating voltage (SLC
loop):
Internal resistance: < 50 Ω
Power up time: < 30 ms
Shut down time: < 50 ms
24 V DC to 41 V DC
Environmental
Protection category: IP 42
Relative Humidity: < 95% (non‑condensing)
Installation Temperature: +32°F to +100°F (0°C to +38°C)
Storage Temperatures:
• Without CO sensor -13°F to +176°F (-25°C to +80°C
• With CO sensor +14°F to +122°F (-10°C to +50°C)
Mechanical
Dimensions
• Detector: 4.4 in. x 2.0 in. (11.2 cm x 5.1 cm)
• Detector with 4inch base:
5.0 in. x 2.5 in. (12.7 cm x 6.4 cm)
Wire Gauge Maximum length
18 AWG (ISO 0.75 mm2) 4000 ft (1200 m)
16 AWG (ISO 1.5 mm2) 6225 ft (1900 m)
14 AWG (ISO 2.5 mm2) 7200 ft (2200 m)
12 AWG (ISO 4 mm2) 9850 ft (3000 m)
Remote Indicator
If a remote indicator is used in the circuit, it must be
no more than 10 ft (3 m) from the base.
Parts included
Quant. Component
1 FAA‑440‑B4 or -B6 Family Analog Base
1 Hardware pack
1 Literature – Installation manual
• Two 2‑inch mounting screws (stainless steel raised
head [Phillips and slot] with N8-32UNC thread)
• Detector with 6inch base:
Housing Material: CYCOLOY/ABS
7.0 in. x 2.5 in. (17.8 cm x 6.4 cm)
Trademarks
All hardware and software product names used in this
document are likely to be registered trademarks and
must be treated accordingly.