Fire Alarm Systems | FAA‑325‑B6 6‑inch Analog Sensor Base
FAA‑325‑B6 6‑inch Analog Sensor Base
www.boschsecurity.com
u Modular design
u Robust six‑inch detector base
u Easy sensor removal for cleaning and servicing
The FAA‑325‑6 Analog Sensor Base is combined with
analog addressable sensors that use the advanced
digital communication protocol (DCP) to provide early
fire warning for life safety and property protection.
Functions
Modular Design
The sensor base is part of a two‑piece modular
designed detector assembly. The permanently
installed base provides in and out connection points
for the polling circuit.
Preservation of loop
The sensor base has a simple rugged design with
terminal screws for wiring. It preserves loop continuity
when sensors are removed.
Locking System
A simple tamper‑proof lock is enabled by removing a
small plastic tab on the back of the sensor. Once
locked, the sensor must be removed with a small
screw driver.
u Stable mounting of sensors
u Terminal screws for remote LED, Data In and Out
provided
Certifications and approvals
Region Certification
USA UL UROX: Smoke-automatic Fire Detectors
(ANSI/UL 268)
CSFM see our website
Installation/configuration notes
Compatibility
The following devices are compatible with the
FAA‑325‑6 Analog Sensor Base:
Category Product ID Product Description
Fire Panels FPA-1000-UL Compact Fire Panel
FPA-1000-V2 Analog Addressable Fire Panel
Detectors FAH‑325 Analog Heat Detector
FAI‑325 Analog Ionization Smoke Detector
FAP‑325 Analog Photoelectric Smoke
Detector
Mounting
For UL Listing requirements, space the detectors no
more than 30 ft (9.1 m) apart.
2 | FAA‑325‑B6 6‑inch Analog Sensor Base
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Bosch Security Systems B.V.
P.O. Box 80002
5617 BA Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security
Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd.
201 Building, No. 333 Fuquan Road
North IBP
Changning District, Shanghai
200335 China
Phone +86 21 22181111
Fax: +86 21 22182398
www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division
Via Anhanguera, Km 98
CEP 13065-900
Campinas, Sao Paulo, Brazil
Phone: +55 19 2103 2860
Fax: +55 19 2103 2862
latam.boschsecurity@bosch.com
www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice
2705950219 | en, V5, 06. Aug 2014
Wiring
Install the detector base in either a Class A or a
Class B analog polling circuit with the following
wirings depending on the distances:
Wiring Distance
18 AWG (ISO 0.75 mm2) 3900 ft (1188 m)
16 AWG (ISO 1.5 mm2) 6200 ft (1889 m)
14 AWG (ISO 2.5 mm2) 10000 ft (3048 m)
Parts included
Quant. Component
1 FAA‑325‑6 Analog Sensor Base
1 Hardware pack:
• Two mounting screws
1 Literature – Installation manual
Technical specifications
Electrical
Voltage: 24 VDC to 40.7 VDC
Environmental
Environment: Dry; Indoor use only
Relative Humidity: Up to 95%, non‑condensing
Temperature
(operating):
+14°F to +122°F (-10°C to +50°C)
For UL Certificated installations, +32°F to
+115°F (0°C to +47°C)
Temperature
-4°F to +140°F (-20°C to +60°C)
(storage)
Mechanical
Color: Ivory
Material: ABS Blend
Dimensions: 4 in. x 1.5 in. (10.2 cm x 3.8 cm)
Weight: 2.3 oz (65 g)
Ordering information
FAA‑325‑B6 6‑inch Analog Sensor Base
6‑inch (152.4 mm) base for FAH‑325, FAI‑325, and
FAP‑325 sensors. US sales only!
Order number FAA-325-B6