Bosch F.01U.512.627 Datasheet

Bosch F.01U.512.627 Datasheet

Communications Systems | LBB 1992/00 Plena Voice Alarm Router

LBB 1992/00 Plena Voice Alarm Router

Six-zone router with single or dual channel operationSix EMG input contacts

Six business input contacts

Six volume override output contacts

Supervision within the Plena Voice Alarm SystemEN 54 16 and EN 60849 compliant

The Plena Voice Alarm Router is an expansion unit that can add six zones as well as 12 input and eight output contacts to the Voice Alarm System. It can use the built-in amplifier on the LBB 1990/00 Voice Alarm Controller, and provides inputs and outputs for one or two amplifiers in a multi-amplifier one or two-channel system.

It provides dual channel operation for calls and BGM simultaneously to a maximum of six different zones, using two Plena amplifiers. Additionally, single channel operation is possible with only one Plena amplifier.

Multiple routers can also share one amplifier, including the internal amplifier on the controller unit. It is possible to use any number of amplifiers from one up to the number of routers used. The controller supports A/B wiring.

Functions

The LBB 1992/00 has a set of relays for zone-switching the power amplifier output(s) to different loudspeaker groups. Each zone can be switched between:

The call channel (call-station selection, all-call microphone, or emergency activation)

The BGM channel (front panel selection)

Off

Volume override relay contacts are provided for each zone separately for overriding local loudspeaker volume controls. This ensures that priority messages go through with a given volume, even though the local volume controls may be set to a low volume level for background music, for example. Both three-wire and four-wire override schemes are supported. A call or a triggered input will activate these contacts for the appropriate zones, together with an additional voltage-free contact (callactive) for control purposes.

An overload protected 24 VDC output provides power for driving external relays, making an external power supply unnecessary. The master output channel, or one of the input channels, can be selected to be monitored with headphone connector and LED meter.

Controls and indicators Front

Meter (LED's for -20, -6, 0 dB and Power ON)

Eight system fault LEDs

12 loudspeaker line fault LEDs

Six EMG call-zone selection buttons

12 EMG call-zone status LEDs

Six BMG zone selector buttons

Six BMG zone status LEDs

Back

2 x DIP switch

Unit ID rotary control

Mains voltage selector

www.boschsecurity.com

2 | LBB 1992/00 Plena Voice Alarm Router

Power switch

Mains socket

Interconnections

Back

12 loudspeaker outputs

Two external amp inputs

Call output

Six volume override outputs

12 trigger inputs

RS-232 connector

Two system interlinks

Two external amp outputs (XLR/balanced)

Power amp fault output

24 VDC power output

24 VDC power input

Two extra trigger outputs

Earth connection screw

Certifications and Approvals

Region

Certification

Europe

CE

TUV certificate IEC60849

 

 

Declaration of Conformity

 

 

 

Poland

CNBOP

 

Safety

 

acc. to EN 60065

Immunity

 

acc. to EN 55103-2

Emission

 

acc. to EN 55103-1

Emergency

 

acc. to EN 54 16 / EN 60849

Installation/Configuration Notes

LBB 1992/00 rear view

Parts Included

Quantity Component

1LBB 1992/00 Plena Voice Alarm Router

1Power cord

1Set of 19” mounting brackets

1Plena CD

1Installation and User Instructions

1XLR cable

1Ethernet cable

Technical Specifications

Electrical

Mains power supply

Voltage

230/115 VAC, ±10%, 50/60 Hz

Inrush current

1.5 A @ 230 VAC / 3 A @ 115 VAC

Max power consumption

50 VA

Idle / max load* current

0.2 A / 0.3 A

Battery power supply

 

Voltage

24 VDC, +15% / -15%

Current max

1.8 A

Typical / max load* current

0.51 A / 1.5 A

Trigger Inputs

12 x (6 EMG, 6 business)

Connectors

MC1,5 / 14-ST-3,5

Activation

Programmable

Supervision

On EMG inputs, programmable

Supervision method

Series / parallel resistor

100 V input

 

Connector

MSTB 2,5 /16-ST

Amp 1

100 V / 70 V / 0 V

Amp 2

100 V / 0 V

Power handling capacity

1000 W

Loudspeaker outputs

12 x (2 x 6 zones)

Connectors

MSTB 2,5 /16-ST, floating

100 V output

700 W rated per zone

Volume override types

3-wire, 4-wire (24 V), 4-wire failsafe

Output Contacts

 

Connector

MC 1,5/14-ST-3,5

Rating

250 V, 7A, voltage free

General purpose relays (2x)

NO / COM

* Maximum load means maximum load on 24 VDC, and indicator test.