Installation Instructions
for the
DX3010 Octo-Output Expander
1.0 General Information
The DX3010 is an Octo-Output Expander that provides eight Form
“C” relay outputs for compatible control panels. It connects to the
control panel via the data bus. The outputs are fully programmable.
Each output operates individually from the other seven outputs for
complete flexibility. Refer to the control panel's manual for
programming instructions.
The DX3010 replaces the DS7488 and D9529 Modules.
2.0 Specifications
• Operating Volt age: 10 to 14 VDC
• Operating Current: 10 mA + 40 mA
for each energized relay
• Outputs: Dry Contacts rated 5.0 A
@ 28 VDC (maximum for
resistive loads)
• Sensor Loop Terminal W ire Size: #14 (1.8 mm) to #22
(0.8 mm) AWG
• Operating Temperature: +32°F to +122°F
(+0°C to +50°C)
• Relative Humidity: 5% to 85% @ +86°F
(+30°C) non-condensing
• Control Panel Compatibility: DS7240, DS7220, D6412,
D4412, DS7400Xi*
* The DS7400Xi has not been tested by Underwriters
Laboratories for compatability.
DX3010
Terminals
DX3010
Side Mounting Locations
Enclosure Wall
Mounting Hardware
(supplied with DX3010)
3.0 Mounting
Failure to follow the procedures in these instructions
can result in personal injury and/or damage to the
equipment.
The DX3010 contains static-sensitive components
and must be handled with care. Follow the anti-static
procedures when handling the modules.
Test according to NFPA 72 if used in fire applications.
Up to three DX3010 Modules can be installed in the control panel’s
enclosure. The DX3010 Module can be remotely mounted in a
D203 Enclosure (see Figures 1 and 2).
Figure 1: Control Panel Enclosure Side Wall Mounting
Install the module in
the D203 Enclosure.
Figure 2: Installing the DX3010 in a D203 Enclosure
4.0 Wiring
Refer to Table 1 for the data bus wiring length requirements.
Remove all power to the system (AC and standby
battery) before making or breaking any
connections. Failure to do so might result in
personal injury and/or damage to the equipment.
4.1 Data Bus Connections
Connect the DX3010 to the control panel data and auxiliary power
sources as shown in Figure 3.
DX3010
Y
Yellow (Data)
G
Green (Data)
B
R
Black (-)
Red (+)
To control panel
Output Activated State
NC NOC
Output De-activated State
NC NOC
NC NOC
8
Figure 3: Control Panel Connections
If the DX3010 is to be installed far from the control
panel, the control panel cannot be used to power
the DX3010. An external power supply must be
used. See Figure 4 for external power supply
connections.
Control Panel
to DX3010
Control Panel
to DX3010
External Power Supply
to DX3010
Power
Source
Control
Panel
External
Power
Supply
#22 AWG
(0.8 mm)
40 ft.
(12.2 m)
1000 ft
(305 m)
40 ft.
(12.2 m)
#18 AWG
(0.8 mm)
80 ft.
(24.4 m)
2000 ft.
(610 m)
80 ft.
(24.4 m)
Table 1: W ire Lengths
Wire length may be restricted by panel limitations. See the control
panel’s Installation Instructions for more information.
5.0 Setting the DX3010's Address
Use Table 2 to configure the DX3010’s address. Consult the control
panel’s Installation Manual to determine the appropriate address
for each DX3010 you connect.
Each time you change the address DIP switches,
you need to cycle the power to the DX3010 (turn
the power off and then on) for the address change
to take effect.
See Figure 5 for DIP Switch orientation.
If using an external 12 VDC power supply, wire as shown in
Figure 4.
When using any external power supply, the negative
(-) output must not be tied to earth ground. A ground
fault condition will be reported if negative (-) is
grounded.
DX3010
Y
Yellow (Data)
G
Green (Data)
B
R
Black (-)
Red (+)
To control panel
(+) (-)
External 12 VDC
Power Supply
Module Address 150
OPEN
123456
Figure 5: DIP Switch Orientation
Example:
=
=
= Switch OPEN (Up)
= Switch CLOSED (Down)
NC NOC
8
Figure 4: External Power Supply Connections
Page 2 © 2008 Bosch Security Systems, Inc. DX3010 Installation Instructions