DS7465i
Installation Instructions
Input/Output Module EN
DS7465i | Installation Instructions | 1.0 Introduction EN | 2
1.0 Introduction
The DS7465i Input/Output Module operates with
compatible multiplex systems. It has a Form “C” relay
(the output zone) that is programmed to activate from
several different system events. The DS7465i can
also monitor normally open (NO) or normally closed
(NC) contacts and report their status as a multiplex
address to the control system. Up to 60 DS7465i
Modules can be used on the DS7400Xi. Use up to 20
DS7465i Modules per bus on compatible fire alarm
control panels (FACPs). When installing the DS7465i
with a D8125MUX, refer to the D8125MUX Operation
and Installation Guide (P/N: F01U034973) and the
D9412GV2/D7412GV2 Approved Applications
Compliance Guide (P/N: F01U003639).
2.0 Installation
These installation instructions assume the control
panel is installed and in proper working condition.
Perform the following procedure to install the
DS7465i:
You must program the control panel and set
the DS7465i address switches before the
Figure 1: Removing the Cover
DS7465i can operate.
1. Program the DS7465i and the control panel
as described in the control panel’s reference
guide.
Disconnect power to the control panel
before running wires and connecting the
DS7465i.
2. To remove the cover of the DS7465i, place
your thumb directly above the lip of the
DS7465i and press in and up. Refer to
.
1
Figure
3. To remove the DS7465i circuit board from the
base, press the circuit board retainer tab and
pull the circuit board up and out of the base.
Refer to
Figure 2.
Figure 2: Removing the Circuit Board
2
1
5
G 1 - +
3
O
1 2 3 4 5 6 7 8
N
4
1 - Circuit board
retainer tab
2 - Tamper switch
3 - Address switches
When used in a fire system, NFPA 72
prohibits this product from sharing a
communications bus with non-fire devices.
Hold the circuit board by its edges to avoid
damaging it.
4. Insert the wiring through the wire entrance of
the base.
5. Mount the base using the supplied screws.
Surface-mount the DS7465i near the devices
it controls or monitors.
6. Return the DS7465i circuit board to the base.
After any programming or hardware
change, do a functional test of the system
as required by local codes.
4 - Terminal strips
5 - Wire entrance
3.0 Wiring
Table 1: DS7465i Terminal Descriptions
Terminal Description
NO Normally open relay contact
C Common relay contact
NC Normally closed relay contact
G Input zone ground
1 Input
- Multiplex bus negative
+ Multiplex bus positive
Bosch Security Systems, Inc. | 10/09 | F01U070743-03
DS7465i | Installation Instructions | 3.0 Wiring EN | 3
The input zone is power limited and
supervised. The output relay must only
be used on power-limited circuits.
Fire applications require NO contacts on
the input zone.
Connect wiring to the DS7465i as shown in Figure 3
through
Figure 5.
The input loop is designed to monitor NO
or NC dry contacts. It is supervised using
a 47 kΩ end-of-line (EOL) resistor. If
using the input loop as a fire alarm input,
order the Multiplex Resistor Kit (P/N:
28010).
Figure 4: DS7436 Multiplex Expansion Module
Wiring
DS7465i
DS7436
6
1
2
1 2
4
3
5
1 - Power
2 - Bus
3 - Use either Bus A or Bus B, or both. Refer to the
control panel’s reference guide.
Do not loop wire around the terminals.
The relay contacts are rated 1A @ 30
4 - To DS7436 B+/B- terminals
Ω
5 - EOL 47 k
(P/N 26069)
6 - Programmable Form “C” dry contacts rated at
1A @ 30 VDC
VDC for resistive loads. Do not use with
inductive or capacitive loads.
Figure 3: DS7430 Multiplex Expansion Module
Wiring
DS7465i
Figure 5: D8125MUX Multiplex Expansion
For UL Listed fire installations, use NO
contacts and order the Multiplex Resistor
Kit (P/N: 28010).
Module Wiring
DS7430
DS7465i
1
5
2
9
+- +- + - +-
1
5432
3
4
1 - Power
2 - Bus
3 - To DS7430 Mux Bus Terminals
Ω
4 - EOL 47 k
5 - Form “C” dry contacts rated at 1A @ 30 VDC
Bosch Security Systems, Inc. | 10/09 | F01U070743-03
(P/N 26069)
For UL Listed fire installations, use NO
contacts and order the Multiplex Resistor
Kit (P/N: 28010).
7
6
8
1 - D8125 Multiplex Module
2 - Power A
3 - MUX Bus A
4 - Power B
5 - MUX Bus B
6 - Use either Bus A or Bus B. Refer to the control
panel’s reference guide
7 - To MUX Expansion Module MUX Bus +/- terminals
8 - EOL 47 k
9 - Form “C” dry contacts rated at 1A @ 30 VDC
Ω
(P/N 26069)