The DS484Q and DS486Q are photoelectric quad beam detectors that use four pulsed infrared beams to activate
an alarm relay upon detection of an intruder. Both models contain a transmitter that emits an invisible infrared
beam, and a receiver. If the beam is broken, the receiver signals an alarm. Multiple channel operation provides
increased system flexibility by allowing multiple devices to be used near each other without cross-talk or other
interference.
1.2 Components
Figure 1: DS484Q/DS486Q Components
12
5
6
4
7
8
9
1 - Chassis
2 - Base
3 - Cover
4 - Mounting holes
5 - Vertical adjustment screw (upper)
6 - Terminal block (transmitter has five terminals,
receiver has nine terminals)
7 - Wire entrance
8 - Vertical adjustment screw (lower)
1 - POWER LED
2 - Beam power control
3 - DIP switches
Figure 3: DS486Q Receiver Operation Panel
3
4
5
6
1
2
ALIGNMENT IS COMPLETED
75
50
SWITCH
OFF ↔ ON
ITEM
No
OFF ON
1Group
AB
23SEE CHART
BELOW
4AND/OR
AND OR
5BYPASS
OFF ON
SOUND
6
OFF ON
CHECK
SW2 - 3 : CHANNEL
M
1
2
OFF
SW2
OFF
ON
OFF
SW3
ON
OFF
WHEN ‘ ‘ IS OFF
200
150
100
INTERRUPTION
TIME (msec)
3
ON
ON
ALIGNMENT
CHECK
TERMINAL S
ALARM
300
400
500
EDC LEVEL
1 - INTERRUPTION TIME switch
2 - Alignment check terminals
3 - ALARM LED
4 - Level meter
5 - Environmental discrimination circuit (EDC) LED
6 - DIP switches
1.3 Features
1.3.1 100 Times Sensitivity Allowance
Stable operation is maintained even if 99% of beam energy is cut by environmental disturbances such as rain, fog,
or frost.
1.3.2 Beam Power Control
Use this feature to select the appropriate beam intensity for the detection range. Controlling beam intensity
minimizes the risk of reflection off nearby walls and cross detection with other detectors.
1.3.3 Beam Interruption Time Control
Use this feature to change the beam interruption time to best fit the application.
1.3.4 Using Multiple Transmitter-and-Receiver Sets
Up to four transmitter-and-receiver sets can be stacked.
1.3.5 Selectable Beams
The beams in the DS484Q and DS486Q are configurable into eight different combinations (two groups by four
channels). These combinations can eliminate false alarms that can occur from cross-talk when multiple beams are
stacked, or when the transmitter and receiver are separated by a long distance.
The diameter of the transmitted beam increases with increased distance between the transmitter and
receiver. At distances that approach the maximum range, the beam might reach two or more
receivers. Refer to Section 2.1.2 Beam Spread on page 5 for additional information.
Bosch Security Systems, Inc. | 7/05 | 4998138530F 3
The photoelectric intrusion detection system in the
DS484Q and DS486Q provides alarm relay activation
for different considerations. Use the DIP Switches to
Table 1: EDC BYPASS Switch States
Detector Status BYPASS Switch
select the required protection:
AND gate – All four beams must be blocked
simultaneously to cause an alarm. This setting results in
fewer false alarms caused by birds and other small
animals.
Poor
Environmental
Condition*
OR gate – Either the upper or lower pairs of beams
must be blocked. This setting can detect an intruder
crawling on the ground.
1.3.7 Environmental Discrimination Circuit (EDC)
The Environmental Discrimination Circuit (EDC)
sends a signal when maintaining stable operation
becomes difficult due to environmental disturbances.
The EDC detects the gradual loss of signal along the
beam’s path because of dirt built up on the cover, or
because of rain, fog, or snow. If the signal decreases by
95% over at least 4-seconds, the EDC activates the
EDC LED (refer to Figure 3 on page 3) and relay. This
indicates that something is partially blocking a beam,
or that the covers need cleaning.
The EDC feature was not evaluated by
Underwriters Laboratories (UL).
When either
optical module is
blocked for 3 or
more seconds.
Figure 4: Receiver DIP Switches
1
When both
optical modules
are blocked for 3
seconds.
2
1 - DIP switches 1through 4 and 6 in the OFF
position
2 - DIP Switch 5 (EDC BYPASS Switch) in the
ON position
To use the EDC Bypass Switch, set the receiver’s DIP
Switch 5 to ON or OFF (Figure 4). Refer to Table 1 for
information about the functions and detector status.
∗ Poor environmental condition refers to difficulty in maintaining
stable operation due to environmental disturbances like fog or
rain.
OFF
EDC LED lights
and EDC signal
is provided
through the
normally-closed
relay output at
the receiver.
The alarm is
generated by loss
of beam energy.
EDC LED turns
on and EDC
signal is provided
No alarm output
is generated.
After the
specified
interruption time,
the ALARM LED
turns ON and
alarm signal is
generated.
If beams are
blocked for more
than 3 seconds,
EDC LED turns
ON, and EDC
signal is
generated.
BYPASS Switch
ON
EDC LED turns
on and EDC
signal is provided
through the
normally-closed
relay output at
the receiver.
With the loss of
beam energy, the
ALARM LED
lights but alarm
signal is not
generated (alarm
relay is
automatically
shunted).
EDC LED turns
on and EDC
signal is
provided.
If another optical
module is
blocked, the
ALARM LED
turns ON, but no
alarm signal is
generated.
After the
specified
interruption time,
the ALARM LED
turns ON, and
alarm signal is
generated.
EDC LED does
not turn ON, and
EDC signal is not
provided.
Connect the EDC to a trouble circuit.
Check the system after the EDC relay
activates.
4 Bosch Security Systems, Inc. | 7/05 | 4998138530F
Read the following information before installing,
wiring, and performing regular maintenance on the
equipment.
Do not install the detector:
• near trees and plants where falling leaves can block
the beam
• where intense sources of light and sunlight can
reflect directly into the receiver optics
A beam of light shining at a ±3-degree
angle of each receiver can cause false
• on movable surfaces
• where subject to splashing water or sea spray
• beyond the maximum range of each model
• where strong electrical noise or radio frequency
interference occurs
• where strong vibration occurs
• in the presence of corrosive or explosive gas
Face upper and lower optical modules toward each
other on the transmitter and the receiver.
alarms.
• Do not install or wire detectors during a
thunderstorm.
• Do not supply power until all wiring is
completed.
• Maintain power between 10.5 VDC and
28 VDC at all times.
• Do not disassemble or modify the base.
2.1.1 Beam Strength over Distance
The beam strength is best if used within the maximum
range of the detectors. If used for shorter distances,
excess beam energy reaches the receiver resulting in
reflection off nearby walls and incorrect
communication with other detectors.
2.1.2 Beam Spread
The beam spread is +0.7°. Refer to Figure 5 and Table 2
to determine the installation conditions.
Table 2: Beam Spread Distances
Between
Transmitter and
Receiver
∗
Refer to Figure 5.
∗
m ft m ft m ft
20 66 0.5 1.7 0.8 2.6
40 131 1.0 3.3 1.3 4.3
60 197 1.5 4.9 1.8 5.9
80 263 2.0 6.6 2.2 7.2
100 328 2.5 8.2 2.7 8.9
120 394 3.0 9.8 3.2 10.5
140 459 3.5 11.5 3.7 12.1
160 525 4.0 13 4.2 13.7
180 591 4.5 14.8 4.7 15.4
200 656 6.0 16.4 5.2 17.1
Horizontal
Spread∗
Total Vertical
Spread∗
Figure 5: Beam Spread
1
4
2
3
1 - Beam spread
2 - Distance between transmitter and receiver
3 - Horizontal spread
4 - Total vertical spread
Bosch Security Systems, Inc. | 7/05 | 4998138530F 5