Bosch DS240, DS241 User Manual

Installation Instructions
DS240 and DS241
Long Range Beam Smoke Detectors
1.0 Description
The DS240 and DS241 are long range projected beam type smoke detectors which consist of a separate transmitter and receiver. Internal pointability provides coverage flexibility without the need for brackets. Automatic Signal Synchronization and Range Adjustment reduce installation costs. Selectable sensitivity and alarm response time provide installation flexibility.
2.0 Specifications
Operating Volt age: DS240: 18.0 VDC to 32.0 VDC DS241: 10.2 VDC to 15.0 VDC
• Standby Current: DS240: Receiver: 45 mA @ 24.0 VDC
Transmitter: 20 mA @ 24.0 VDC
DS241: Receiver: 50 mA @ 12.0 VDC
Transmitter: 20 mA @ 12.0 VDC
Receiver Alarm
Current: DS240: 60 mA @ 24.0 VDC
DS241: 75 mA @ 12.0 VDC
Range (distance
between transmitter and receiver): 30 ft to 350 ft (9 m to 107 m)
Spacing (distance
between systems): Allow no more than 60 ft (18 m) between
systems. Sixty foot spacing is confirmed by Underwriters Laboratories, Inc. testing.
Pointability: Internally pointable optics for ±90° horizontal, and ±10° vertical adjustment.
• Sensitivity: Field selectable for 20, 30, 40, 50, 60, or 70 percent beam obscuration.
• Alarm Contacts: Normally Open contacts rated 1 A, 60 VDC maximum for DC resistive loads. Do not use with capacitive or inductive loads.
• Trouble Contact s: Normally Closed contacts rated 1 A, 60 VDC maximum for DC resistive loads. Do not use with capacitive or inductive loads.
Aux. Alarm
Contacts: Form "C" (NO, C, NC) contacts rated 1 A,
60 VDC maximum for DC resistive loads. Do not use with capacitive or inductive loads.
• Tamper: Receiver: Access door tamper switch in
series with trouble contacts.
Transmitter: Upon cover’s removal, cover
tamper switch interrupts transmission.
• System Signaling: Conventional 4-wire system. Not for use with systems that incorporate an alarm verification feature.
• Signal Delay: Fire : Selectable 30 sec or 5 sec Trouble: 20 ± 2 sec
Temperature: The storage and operating temperature range is -22°F to +130°F (-30°C to +54°C).
For UL Listed installations, the range is +32°F to +130°F (0°C to +54°C).
Mounting: The units are designed to be mounted to 4 in. (10 cm) square or octagonal electrical boxes (not supplied).
Listings and Approvals: UL S3019
ULC CS692 MSFM Permit #1943 NY City MEA Acceptance #MEA274-93-E CSFM #7260-1062:106 F M Job #OX2A9.AY
Standard Accessories: DIS2000 Remote Test/Indicator Plate and
Test Cable
Options: DIS240 Remote Indicator Plate, TK240
Field Test Kit, AL240 Alignment Light, and TC2000 Test Cord.
3.0 Principle of Operation
Each DS240 or DS241 beam smoke detector has a separate transmitter and receiver. The transmitter transmits an invisible infrared beam of a specific frequency and intensity. The receiver detects, then measures the beam’s intensity (see
Figure 1 - Infrared Transmission
As the beam is obscured by smoke, the receiver senses a decrease in the signal strength and measures that decrease. The receiver compares the signal level with two preset thresholds: an alarm threshold which is set using the sensitivity switch and a trouble threshold which is preset at approximately 10%. If the signal falls below the alarm threshold for the programmed alarm period, the receiver signals an alarm (see
Figure 2 - Beam Obscuration
If the signal falls below the trouble threshold for more than 20 sec, such as might happen if the beam is blocked by a foreign object, the receiver signals a trouble condition (see
Figure 3 - Beam Blockage
The receiver automatically compensates for the gradual loss of signal due to dust/dirt build-up on the cover. After 50 percent of the signal is lost, the receiver will indicate a trouble. When the dust/dirt build-up is cleaned or the blockage is removed, the detector automatically goes back to its normal operation level.
A trouble will be indicated at the receiver if the beam strength is increased by more than 20% for greater than 20 sec. Causes include improper initial alignment or the removal of a partial beam blockage at the time of alignment. Preform a fine-tune alignment (see
7.3 Fine Tune Alignment
on page 6).
Figure 1
Figure 2
).
Figure 3
).
).
Section
Downloaded from: http://www.guardianalarms.net
4.0 Installation Considerations
eriW
htgneL
eziSeriW
GWA41
)mm8.1(
GWA61
)mm5.1(
GWA81
)mm2.1(
)m251(tf005
)m403(tf0001 )m267(tf0052
)m4251(tf0005
sriap02
sriap01 sriap4 sriap2
sriap31 sriap6 sriap3 riap1
sriap8 sriap4 sriap2 riap1
4.2 Avoid sources of bright light
The proper location and spacing of detectors is critical in a properly installed and operating fire alarm system. For best results, it is recommended that the detectors be located and spaced in accordance with the National Fire Protection Association (NFPA) Standard 72 "The National Fire Code.” This standard is available at a nominal cost from The National Fire Protection Association, Batterymarch Park, Quincy, MA, 02269.
In all installations, good engineering judgement should prevail. The following are some general considerations:
• Do not use mirrors. The detectors should be installed with a clear line-of-sight between the transmitter and receiver.
• The beam path should be clear of moving objects.
• Set the sensitivity based on the distance between the transmitter and receiver. See
Section 7.2 Sensitivity Adjustment
on page 5.
• The detectors may be mounted directly to the ceiling or to side walls. Do not mount the units where the beam path may run parallel within 4 in. (10.2 cm) of a corner.
• For a sloped or peaked ceiling, the beam path should be located within 3 ft (1 m) of the ceiling’s peak.
• Stratification of air may hinder smoke from reaching detectors mounted close to the ceiling. Stratification occurs when smoke, rising because it is warmer than the surrounding air, reaches a level where it is the same temperature as the surrounding air and will not rise to the ceiling. If stratification is considered a possibility, extra beams should be installed where stratification is expected.
Sunlight and light from extremely bright sources such as the exposed bulbs of high pressure sodium, mercury vapor, and metal halide lights can cause stray signals. The receiver should not be pointed toward any of these sources.
Sunlight: Avoid pointing the receiver directly at the rising or setting sun. If you are installing the unit where sunlight can’t be avoided, mount the receiver slightly higher than the transmitter and aimed down toward the transmitter. This should reduce this problem by causing the receiver to look below the horizon.
Bright Lights: Don’t mount the receiver where it is looking at exposed bulbs of high pressure sodium, mercury vapor, and metal halide lights. The illustration below shows where these exposed lights should be avoided.
Keep bright lights out of this area
Receiver
4.5 ft. (1.4 m)
225 ft. (68.6 m)
350 ft. (106.8 m)
14.5 ft. (4.4 m)
Bare fluorescent lights may also pose a problem especially in long hallways where a series of lights run perpendicular to the beam. Incandescent lights are not a problem as long as they are not directly in the beam path.
4.3 Use the correct wire gauge and length
Beam smoke detectors are often used to protect very large areas. This means that the wire runs used to power the detectors and signal alarm conditions can be very long. The voltage available at the end of very long wire runs may not be sufficient to power the detector, especially when the system is running on battery backup. It is very important that the correct wire gauge is used for these installations.
• Avoid areas subject to normal smoke concentrations such as kitchens and garages.
• Do not install units where normal ambient temperatures are below -22°F (-30°C) or above +130°F (+54°C).
The following are some specific installation considerations:
4.1 Avoid Sources of Heat and Air Movement
The detectors should be located where the beam path will not pass near heating and cooling outlets.
• Don’t mount where hot or cold air can blow directly into the beam path.
• Heating, ventilating, and air conditioning systems can cause smoke to be blown away from the beam path.
- Smoke must accumulate in the beam path to be detected.
• Heaters mounted close to the beam path can cause the beam to become distorted.
You can test for beam distortion by monitoring the signal voltage. After setup, the signal voltage of the detector should read 4 VDC. Monitor the voltage and turn on all heating and cooling devices in the area. The signal voltage should not fluctuate more than 0.20 VDC. If it does, the detector should be moved to avoid these disturbances.
Use the following chart to determine the proper wire size, wire length and the number of transmitter and receiver pairs that can be used.
Page 2 P/N: 22066P © 2004 Bosch DS240/DS241 Installation Instructions
4.4 Provide a stable mounting surface
4.6 Consider the expected Fire load
Beam smoke detectors depend on the measurement of the projected beam to sense smoke. Therefore, shifts in the alignment of the beam due to movement of the transmitter/receiver can cause trouble or alarm conditions.
• Always select a stable mounting surface.
• Never mount the unit to a suspended support such as a pipe or length of wood supported at only one end.
This type of mounting can create a “pendulum effect” which greatly multiplies even very small movements at one end of the support. For example, a 2 in. (5.1 cm) movement translates into a beam misalignment of over 20 ft at 350 ft (6 m at 107 m).
Mounting surfaces should be supported at opposite corners to reduce the pendulum effect.
• Always select surfaces not subject to building movement.
The automatic compensation circuits of the DS240 and DS241 will eliminate most problems created by normal building expansions and contractions. In some unusual circumstances, the walls and
support structure may be subject to more significant movement due to the operation of heavy equipment, such as cranes, anchored to the top of the walls.
When designing a fire alarm system, consider the expected fire load within the application.
For instance, fires caused by the ignition of flammable petroleum­based liquids usually result in a rapid buildup of heavy smoke. When these types of fires are probable, use sensitivity settings 0 or 1 which provide a response time of 5 sec.
5.0 Mounting
NOTE: This product is not designed for use in outdoor applications.
Install a 4 in. (10 cm) square or octagonal electrical box (not supplied) to a rigid surface that will not be subject to movement or vibrations.
NOTE: If not mounting to an electrical box, be sure the surface will
not be subject to movement or vibrations. For example: do not mount directly to a suspended ceiling without extra support.
• Remove the receiver's access door (1 screw), then remove the cover (4 screws). See
Figure 4
.
COVER MOUNTING
SCREWS (4)
When in doubt about mounting surface stability, measure the signal voltage of the detector. This voltage should be 4.0 VDC. Misalignment of the beam can cause this voltage to increase or decrease. The detector will indicate a trouble condition when the voltage increases to more than 4.8 VDC, or when it decreases to less than 2.0 VDC over a long period of time or to 0.4 VDC greater than 20 sec. For more information on reading this voltage, see
Voltage Calibration
on page 6).
Section 8.3 Reference
If movement of the mounting surface is suspected, relocate the detector to a surface that does not move or add supports to the mounting surface to prohibit movement.
DO NOT over-tighten the mounting screws. When the detector is mounted to an electrical mounting box
[4 in. (10 cm) square or octagonal], the mounting plate may bow as a result of the mounting box screw tabs being below flush with the top edges of the mounting box. Over-tightening the mounting screws bows the mounting plate inward at the bottom, causing the optics to aim low.
Irregularities in the flatness of the mounting box edge surfaces or screw tabs will worsen this condition. Using only mounting boxes with flat, regular surfaces and properly formed screw tabs, and tightening the mounting screws to secure the mounting plate to 2 in./lb torque will minimize any misalignment caused by bowing of the mounting plate.
4.5 Consider the effects of stratification in cold environments
In very cold environments such as unheated warehouses, smoke may cool very quickly and is less likely to rise to the ceiling. Consider additional units at lower mounting heights to help compensate for this situation.
ACCESS DOOR
Figure 4 - Access Door and Cover
• Remove the receiver’s backplate by removing the single mounting screw from the top of the circuit board carrier plate then separating the two plates (see
EXPOSE BACKPLATE
REMOVE TO
DO NOT
REMOVE
Figure 5
).
MOUNTING
SLOTS (4)
WIRING
ENTRANCE
Figure 5 - Removing the Backplate
• Bring wiring from the electrical box through the wire entrance.
NOTE: All wiring should be unpowered.
• Securely mount the backplate to the electrical box.
• Return the circuit carrier plate to the backplate. Secure it in place with the single mounting screw.
• Repeat this mounting procedure for the transmitter.
DS240/DS241 Installation Instructions © 2004 Bosch P/N: 22066P Page 3
6.0 WIRING
Only apply power after all connections have been made and inspected.
CAUTION
• Wire the transmitter and receiver terminals as follows (see
Figure 6
NOTE: Do not install on verified fire circuits.
NOTE: Do not coil excess wiring inside the units.
Transmitter Terminals 1 & 2: Input power terminals. See for the operating voltages of the DS240 and DS241.
).
Control Panel
Power Loop – Power Loop +
Receiver
Alarm Loop
Fire Alarm
AUX. RELAY ALARM
1234567
FIRE
ALARM
End of Line
12
+
Transmitter
Figure 6 - Wiring a Single Unit
Section 2.0 Specifications
TRBL
ALARM
resistor
VDC
–+
89
on page 1
• Slide the Remote Indicator Connector over the pins just to the right of the receiver’s terminal strip.
DS240/DS241 Receiver
Fire
Trouble
10 to 32
Alarm
Alarm
VDC
–+
Violet Black Red Yellow Green
Remote Indicator
98
Plate Connector
Fire Alarm
Control Panel
Alarm Loop
Power Loop – Power Loop +
7654
EOL
DIS2000
Voltage Monitor
Ground (–)
Red LED
Yellow LED
Green LED
Receiver Terminals 1, 2 & 3:
Figure 7 - Connecting the DIS2000 Remote Indicator Plate
Form "C" Auxiliary relay contacts. Terminals 1 & 2 will open on fire alarm; Terminals 2 & 3 will close (short) on fire alarm.
NOTE: If connecting a DIS240 Remote Test/Indicator Plate,
consult the
DIS240 Installation Instructions
(P/N: 24171).
Receiver Terminals 4 & 5: Normally Open Fire alarm contacts will close (short) on fire
7.0 SET-UP
alarm.
Before starting this section, confirm that all connections have been
Receiver Terminals 6 & 7:
made and are secure, then apply power to both units.
Normally Closed Trouble contacts will open for trouble alarm.
• Press the Aim Mode button (directly above the green LED) on the
Receiver Terminals 8 & 9: Input power terminals. See
Section 2.0 Specifications
on page 1
transmitter (see
Figure 8
up while its cover is off.
). This allows the transmitter to power
for the operating voltages of the DS240 and DS241.
NOTE: Resetting from a fire alarm requires power to the receiver to
AIM MODE
BUTTON
be interrupted for at least one second. If not provided by the fire panel, it can be accomplished by installing a switch in series with Terminal 9.
Remote Indicator Plate
The DIS2000 Remote Indicator Plate is shipped with the DS240/ DS241 as a standard accessory. Although the Remote Indicator Plate is not required, the manufacturer recommends its installation to provide a means of checking the condition of the detector from ground
GREEN
LED
level. If a DIS2000 or DIS240 Remote Indicator Plate will be used, install
the Remote Indicator Connector to the receiver now (see Figure 7).
Figure 8 - Cutout View of Transmitter Circuit Board Showing
Aim Mode Button Location
- Check the transmitter’s green LED. It should be flashing on
NOTE: The DIS240 remote indicator should be located no further
and off. than 100 ft (31 m) from the receiver and wired with 18 AWG (1.2 mm) or larger wire. The DIS2000 may be wired up to 500 ft (152 m) from the receiver.
Page 4 P/N: 22066P © 2004 Bosch DS240/DS241 Installation Instructions
Loading...
+ 8 hidden pages