Bosch D340P Installation Manual

Installation Guide
EN
Duct Smoke Detector Housing
D340 | Installation Guide | 1.0 Overview
Trademarks
The National Fire Alarm Code® is a registered trademark of the National Fire Protection Association.
®
Life Safety Code
is a registered trademark of the
National Fire Protection Association.
1.0 Overview
The D340 Air Duct Smoke Detector Housing is designed to mount to the ducts of heating, ventilation, and air-conditioning (HVAC) systems to monitor the presence of smoke in the conditioned air.
Use the D340 with the D285DH Photoelectric Smoke Detector (provided separately). The detector is combined with an efficient housing design to sample the air passing through a duct and detect potentially hazardous conditions. When it detects smoke, the detector sends an alarm signal to the control panel. The control panel initiates the necessary action to shut off fans and blowers or to switch to other air handling systems.
The D340 operates on a two-wire loop, and requires a smoke detector head.
Test the system by placing an external magnet on the housing or switching the keyswitch from a Remote Test station. Reset control requires a 24 V supply from the control panel or an external power supply.
You can reset the detector by shutting down zone power. If your system has a D344-RT Remote Test Kit, you can reset the system using the keyswitch.
Install the D340 according to:
NFPA 90A: Standard for the Installation of Air
Conditioning and Ventilating Systems
®
NFPA 72: National Fire Alarm Code
NFPA 101: Life Safety
Code®
IBC: International Building Code
IFC: International Fire Code
Any applicable local and state codes
Local authority having jurisdiction (AHJ)
2.0 D340 Options
Table 1: D340 Options
Options Description
D285DH Photoelectric smoke detector head D344-1.5 1.5 ft (0.5 m) sample tube D344-3 3 ft (1 m) sample tube D344-5 5 ft (1.5 m) sample tube D344-RT Remote Test Kit (D307) D344-RL Remote LED Indicator Kit (D306) D344-TF Tube filters for sample and exhaust tubes
(20 per package) SMK-TM Test magnet DRA-5 Remote alarm indicator D275 End-of-line (EOL) module
3.0 Assembly
The D340 includes:
One housing, power card, and cover assembly
Two #10-24 x 1 in. machine screws for mounting
Two #10-24 jack nuts
One exhaust tube
Two tube clamps with four screws
Two foam gaskets
Two air filters
One drilling template
One cover gasket
The D340P also includes a smoke detector head and
1.5 ft (0.5 m) tube.
2 Bosch Security Systems, Inc. | 7/09 | F01U071685-06
.
4.0 Sample Tubes
The sample tubes must extend across the width of the duct. The three sizes of sample tubes are:
D344-1.5 (1.5 ft [0.46 m])
D344-3 (3 ft [0.91 m])
D344-5 (5 ft [1.52 m])
Sample tubes include an end plug that must be installed in the narrow end of the tube (Figure 1).
Figure 1: D344-1.5 Sample Tube
1
1 - Set screw 2 - End plug
You can combine or cut sample tubes to make different lengths. A sample tube can be a maximum length of 10 ft (3 m) or a minimum length of 1 ft (0.3 m). For example, you can join a 3 ft (1 m) and a 5 ft (1.5 m) to make an 8 ft (2.4 m) sample tube.
To combine sample tubes:
1. Remove the roll pin and set screw from one of the
sample tubes.
2. Remove the end plug from the other sample tube.
3. Push the flared end over the sample tube you want
to lengthen.
4. Align the holes, insert the set screw, and reinstall
the end plug. For example, if you want a 7 ft (2 m) sample tube, combine a 3 ft (1 m) sample tube and a 5 ft (1.5 m) sample tube. Then cut 1 ft (0.3 m) from the narrow end to get the necessary length.
Sample tubes must have at least 12 sample holes within the duct. Do not cut sample tube to less than 12 sample holes.
2
D340 | Installation Guide | 4.0 Sample Tubes
Figure 2: Support Hole Position
1
1 - 1 in. to 2 in. (2.5 cm to 5 cm)
5. Seal the gap between duct and sample tube. You can remove up to 6 in. (15 cm) from the D344-1.5 for 1 ft (0.3 m) duct installations.
When using the D344-1.5 in installations where the duct width is between 12 in. (31 cm) and 18 in. (46 cm), cover some of the sample holes. The D344-1.5 has 19 sample holes, but only 12 are required for normal installations. Depending on the length, you might have to cover some of the holes with duct tape. Use even spacing when covering the sample holes to allow an even sample across the width of the duct. Refer to Figure 3.
Figure 3: D344-1.5 Sample Tube
1
1 - Place tape over these sample holes
Sample tubes over 3 ft (1 m) must be supported at the end opposite the duct detector. The support hole should be 1 in. to 2 in. (2.5 cm to 5 cm) below the entry hole to allow for possible moisture drainage (Figure 2).
Bosch Security Systems, Inc. | 7/09 | F01U071685-06 3
D340 | Installation Guide | 5.0 Mounting
5.0 Mounting
5.1 Preparing the Duct
You must verify the duct air flow and velocity. The D340 is designed for use in air handling systems with air velocities between 300 ft/min and 4000 ft/min (1.5 m/sec to 20.3 m/sec). Check the HVAC engineering specifications to ensure the air velocity in the duct falls within these parameters. If necessary, use a velocity meter to check the air velocity in the duct.
5.1 Determining the Mounting Location
To obtain a representative air sample, avoid stratification and dead air space. These conditions can be caused by return duct openings, sharp turns, connections, or long, uninterrupted runs. For this reason, place the D340 in the range of six to ten times the width of the duct from any uninterrupted run. Refer to Figure 4 and Figure 5.
Figure 4: Typical D340 Placement – Example A
5.2 Positioning the D340
The D340 can be mounted in any direction of 90° increments without regard to the air flow direction (Figure 6).
Figure 6: D340 Positions
1
2 2
1 1
2
2
1
1
3
2
1 - Bend or other obstruction 2 - Six to ten times the width of the duct 3 - Width of duct
Figure 5: Typical D340 Placement – Example B
1
3
2
1 - Return air inlet 2 - Six to ten times the width of the duct 3 - Width of duct
1 1
2 2
3
1 - Air flow 2 - Correct mounting position 3 - Incorrect mounting position
1
3
1
4 Bosch Security Systems, Inc. | 7/09 | F01U071685-06
.
1. Locate the D340 mounting template (Figure 7) and
remove it from its backing.
Figure 7: D340 Mounting Template
5
2
1
DUCT SMOKE DETECTOR
MOUNTING TEMPLATE
REMOVEABLE AFTER DRILLIN G
6
D340 | Installation Guide | 5.0 Mounting
This attaches the jack nuts to the duct. You might have to hold the jack nuts with a installer wrench or a pair of pliers while tightening the screws to stop the jack nut from spinning in the hole. Remove the screws for later use.
7. Place the two foam gaskets over the sample and
exhaust ports on the back of the D340 (Figure 10).
Figure 10: Gasket Placement
3
4
4
1 - 16 in. (41 cm) 2 - 6.5 in. (16.5 cm) 3 - Two 1-3/4-in. (45-mm) diameter holes for the
sample tubes
4 - Two 3/8-in. (9.5-mm) diameter holes for
mounting to the duct 5 - 1.5 in. (38.1 mm) 6 - 8.0 in. (20.5 cm)
2. Place the template over the desired location on the
duct (Figure 8).
Figure 8: D340 Template Placement
16.070 in. (40.8 cm)
6.480 in. (16.5 cm)
(2) 1-3/4 in. (44.5 mm) DIA. HOLES FOR SAMPLING TUBES
(2) 3/8 in. (9.5 mm ) DIA. HOLES FOR DUCT MOUN TING
DUCT SMOKE DETECTOR
MOUNTING TEMPLATE
REMOVEABLE AFTER DRILL ING
1
1 - Foam gasket (2)
8. Mount the D340 to the jack nuts using the
supplied 10-24 x 1-in. machine screws (Figure 11). Remember that overtightening the screws can cause excessive bowing of duct.
Figure 11: Mounting the D340 to the Jack Nuts
3. Drill out the required holes and remove any
remaining debris.
4. Remove the template.
5. Place a #10-24 jack nut (Figure 9) in each of the
1 - Two 10-24 x 1-in. machine screws
9. Locate the wiring knockout holes (Figure 12).
1
3/8 in. (9.5 mm) holes.
Figure 9: Jack Nuts
6. Insert the #10-24 x 1 in. machine screws into the
jack nuts and firmly tighten.
Bosch Security Systems, Inc. | 7/09 | F01U071685-06 5
Loading...
+ 9 hidden pages