Bosch D323A Specfications

Fire Alarm Systems | D323A Analog Photoelectric Smoke Detector Head
The D323A Analog Photoelectric Smoke Detector Head is (FACPs).
The D323A detects dense smoke typically given off by plastic, foam, paper, wood, and other materials that tend to smolder. It can detect fast‑flaming fires. It uses an LED and photodiode to measure particulate levels in its detection chamber. These measurements are transmitted in digital form to the control panel. The system allows for adjusting sensitivity levels by the detector over a range of 0.05% to
4.0% obscuration. Sensitivity levels for specific detectors can be modified on a daily schedule.
The D323A has two LEDs that flash every time the device is polled, and latch on red when the device goes into alarm. The unique detection chamber design prevents external light from affecting the photodiode.
Functions
Control Panel Connection
The D323A has an eight‑bit microprocessor and communicates with the control panel (both power and data) over a two‑wire polling circuit. Each polling circuit can support up to 126 analog devices. The circuit can be configured as either a Class A or a Class B polling circuit. Removing the D323A head from the base for service initiates a trouble signal but does not interrupt the polling circuit.
Contamination Testing FACP Polling: The D8024 and D10024A FACPs are UL
Listed to monitor the contamination level of the D323A. The FACP monitors the test condition (level of contamination) of the detector as part of its normal polling activity. This electrical test determines if the device is within its UL Listed calibration range. The control panel automatically compensates for contamination of the detector and indicates when the device requires cleaning.
Manual: The detector can also be tested using the Bosch Security Systems' D1000 Smoke Test Box, a UL Listed calibrated testing device. Depending on the amount of particulates, the rate of change, and the established standard, the control panel can initiate an alarm or trouble condition.
Certifications and Approvals
Region Certification
USA UL UROX: Smoke - Automatic Fire Detectors
(UL268)
CSFM 7272-1615: 156
NYC-MEA 26-02-E, Vol. III
Hong Kong HKFSD
D323A Analog Photoelectric Smoke Detector Head
Addressable analog photoelectric smoke detector head that mounts on D321A or D336A Analog Detector Base
Advanced digital communications protocol
Digital data communications and power provided over two-wire circuit
Easy head removal for cleaning and servicing
Dual Polling Status and Latching Alarm LEDs on head for easy viewing
EEPROM addressing in detector head
UL Listed for commercial fire applications
www.boschsecurity.com
2 | D323A Analog Photoelectric Smoke Detector Head
USA NFPA Complies with National Fire Protection
Association NFPA 72
Installation/Configuration Notes
Compatible Products
The following products are compatible with the D323A Analog Smoke Detector Head:
Category Product ID Product Description
Control Panels D8024 Analog FACP
D10024A Analog FACP
Detector Bases D321A Analog detector base
D336A Analog detector base
Modules D9067 Polling circuit module
Programming Products
D5070 Analog device programmer
Modular Construction
The D323A is part of a two‑piece modular design photoelectric smoke detector assembly. Attach the D323A to a D321A Analog Detector Base (6 in. [15 cm]) or a D336A Analog Detector Base (4 in. [10 cm]) by inserting the detector head into a groove on the base and turning the head clockwise.
The base’s security locking tab prevents any unauthorized head removal from the base.
Mounting
Smoke detectors are typically mounted on the ceiling. However, if smoke detectors are mounted on a wall, they must be at least 4 in. (10 cm), but no more than 12 in. (30.5 cm), below the ceiling.
For UL Listing requirements, the spacing between detectors should be no more than 30 ft (9 m).
Programming
The D323A’s address is set by programming an EEPROM microchip located in the detector head. The D5070 Analog Device Programmer is required for address setting.
Parts Included
Quant. Component
1 Detector head
1 Dust cover
Technical Specifications
Environmental Considerations
Relative Humidity: 95% maximum, non‑condensing at +104°F
(+40°C)
Temperature (Operating): +32°F to +120°F (0°C to +49°C)
Mechanical Properties
Color: Ivory
Dimensions (diameter x D): 4 in. x 1.5 in. (10 cm x 3.8 cm)
Material: Acrylonitrile‑chlorinated polyethy-
lene‑styrene terpolymer (ACS) plastic
Weight: 3.2 oz (91 g)
Power Requirements
Current (Alarm): 8 mA
Current (Polling): 0.022 mA ± 20%
Current (Standby): 0.39 mA
Voltage (Operating): 24 VDC nominal;
17 VDC to 41 VDC range
Ordering Information
D323A Analog Photoelectric Smoke Detector Head
An addressable device used in the analog poll­ing circuit of the Bosch Security Systems' D8024 and D10024A Fire Alarm Control Pan­els
D323A
Americas:
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V. P.O. Box 80002 5600 JB Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6258 5511 Fax: +65 6571 2698 apr.securitysystems@bosch.com www.boschsecurity.com
Represented by
© Bosch Security Systems Inc. 2010 | Data subject to change without notice T1119598347 | Cur: en-US, V5, 4 Jul 2010
Loading...