Bosch D298M, D298S Specsheet

Fire Alarm Systems | D298 Four‑wire Addressable Detector Bases (24 VDC)
D298 Four‑wire Addressable Detector Bases (24 VDC)
www.boschsecurity.com
u Low‑profile modular design
u Addressable application
The D298M Master Detector Base and the D298S Detector Base are used with smoke and heat detector heads to provide early warning fire detection for life safety and property protection systems. The D298M and D298S are 24 VDC bases for use in systems controlled by either:
• a D7412G (or newer) or D9412G (or newer) control panel with a D8125 POPEX Module and 24 VDC auxiliary power supply, or
• a D9124 Fire Alarm Control Panel (FACP)
The D298M provides individual addresses on the FACP data expansion circuit and accepts the D285/D285TH Photoelectric Smoke Detector Heads, the D286 Ionization Smoke Detector Head, or the D603, D604, and D605 Heat Detector Heads. It connects to the D263 Photoelectric Smoke Detector or the D263TH Photoelectric Smoke Detector with fixed‑temperature (135°F [57°C]) heat sensor. It also acts as the master in a slave circuit consisting of up to 19 D287 or D288 Two-wire Detector Bases with D285/D285TH Photoelectric Smoke Detector Heads, D286 Ionization Smoke Detector Heads, or D603, D604, or D605 Heat Detector Heads. The D298M needs a 3 kΩ end‑of‑line resistor (P/N: F01U008725) to complete the circuit and provide supervision.
u Easy head removal for cleaning and servicing
The D298S has a built‑in POPIT to provide individual addresses on the FACP data expansion circuit and accepts the D285 Series Photoelectric Smoke Detector Heads and the D603, D604, and D605 Heat Detector Heads. When used with the D285 Series detector heads, the D298S indicates Chamber Check trouble to the control panel through the POPIT bus. The Chamber Check trouble indication appears on the keypads as a fire trouble. These detector bases use the PAM‑4 Relay Module to provide two Form C dry contact auxiliary outputs. Removing a detector head from an active polling circuit sends a trouble signal to the control panel, but does not interrupt the polling circuit.
Certifications and approvals
Region Certification
USA UL UROX: Smoke - Automatic Fire Detectors
CSFM see our website
NYC­MEA
(ANSI/UL 268)
12-92-E, Vol. X
2 | D298 Four‑wire Addressable Detector Bases (24 VDC)
Installation/configuration notes
Compatible Products
The following products are compatible with both the D298M Master Detector Base and the D298S Detector Base:
Category Product ID Product Description
Control G Series
Panels D9124 Addressable FACP
Detector D285 Photoelectric smoke detector head
Heads D285TH Photoelectric smoke detector head with
D286 Ionization smoke detector head
D603 Rate‑of‑Rise heat detector
D604 Fixed‑temperature (+135°F [+57°C])
D605 Fixed‑temperature (+190°F [+88°C])
1
Includes the D7412G (and newer) and D9412G (and
1
Addressable Control Panels
fixed‑temperature (+135°F [+57°C]) heat sensor
heat detector
heat detector
newer) control panels The following products are also compatible with the D298M Master Detector Base:
Category Product ID Product Description
Detector D287 Two‑wire detector base
Bases D288 Two‑wire detector base
Detectors D263 Photoelectric smoke detector head
D263TH Photoelectric smoke detector head with
fixed‑temperature (+135°F [+57°C]) heat sensor
Mounting
These bases mount on a single‑gang switch box or on standard three‑inch and four‑inch square or octagonal back boxes. An adapter plate is packaged with the base.
Wiring
The D298M and D298S bases accept any solid wire from 12 AWG to 24 AWG (ISO 4 mm2 to 0.2 mm2). The minimum wire size depends on the number of bases used and the distance from the FACP to the farthest base. For specific wiring requirements, see the D278S/
D298S Installation Instructions or the D298M Installation Instructions.
Parts included
D298M Master Detector Base
Quant. Component
1 D298M detector base
1 EOL resistor (P/N: F01U008725)
1 Adapter plate (P/N: 18851)
1 Hardware pack
1 Literature pack
D298S Detector Base
Quant. Component
1 D298S detector base
1 Adapter plate (P/N: 18851)
1 Hardware pack
1 Literature pack
Technical specifications
Electrical (Auxiliary Supply)
Current (alarm)
D298S: 18 mA maximum
D298S with PAM-4 Relay: 30 mA
D298M1: 36 mA maximum
D298M1 with PAM-4 Relay: 49 mA
Current (standby)
D298S: 2 mA
D298S with PAM-4 Relay: 8.5 mA
D298M1: 13 mA
D298M1 with PAM-4 Relay: 29 mA
Voltage (operating): 18.9 VDC to 28.0 VDC
1
The current ratings are based on D298M with 19 detectors.
Environmental
Temperature (operating): +32°F to +100°F (0°C to +38°C)
Mechanical
Color: Bone white
Dimensions (diameter x D): 6.375 in. x 0.9 in.
(16.2 cm x 2.3 cm)
Ordering information
D298M Master Detector Base
Provides individual addresses on the FACP data expansion circuit and accepts the D285/D285TH Photoelectric Smoke Detector Heads, the D286 Ionization Smoke Detector Head, or the D603, D604, and D605 Heat Detector Heads.
Order number D298M
D298S Detector Base
Used as a stand-alone addressable base
Order number D298S