Bosch D293E Specsheet

Fire Alarm Systems | D293 Four‑wire Detector Bases
D293 Four‑wire Detector Bases
www.boschsecurity.com
u Variety of interchangeable smoke and heat detector
heads
u Detector's head removes easily by twisting
pre‑wiring the system
The D293 Series includes the D293A Four‑wire Detector Base with Auxiliary Form C Relay, the D293E Four‑wire Power Supervision Detector Base, and the D293S Four‑wire Detector Base with Sounder. Use these bases with smoke and heat detector heads to provide early fire warning for life safety and property protection systems. This base is compatible with a number of control panels and with the following Bosch Security Systems, Inc.'s' detector heads:
• D285 Photoelectric Smoke Detector Head
• D285TH Photoelectric Smoke Detector with Heat Sensor Head
• D286 Ionization Smoke Detector Head
• D603 Fixed‑temperature (135°F [57°C]) and Rate‑of‑Rise Heat Detector
• D604 Fixed‑temperature (135°F [57°C]) Heat Detector
• D605 Fixed‑temperature (190°F [88°C]) Heat Detector
u Externally‑powered sounder (85 dB at 10 ft [3 m])
Certifications and approvals
Region Certification
USA UL UROX: Smoke - Automatic Fire Detectors
(ANSI/UL 268), UROX7: Smoke - Auto­matic Fire Detectors Certified for Cana­da (cULus),
CSFM see our website
NYC-
274-93-E, Vol. VII
MEA
MSFM permit #2186
Installation/configuration notes
Compatible Products
The following products are compatible with the D293 Four‑wire Detector Bases:
Category Product ID Product Description
Control Panels Compatible with all UL Listed four‑wire control
panels.
Detector
D285 Photoelectric smoke detector head
Heads
D285TH Photoelectric smoke detector head
with heat sensor
2 | D293 Four‑wire Detector Bases
D286 Ionization smoke detector head
D603 Fixed‑temperature (135°F [57°C])
D604 Fixed‑temperature (135°F [57°C])
D605 Fixed‑temperature (190°F [88°C])
Modules D275 End‑of‑line (EOL) supervision
Remote Annunciators
DRA-5 Remote annunciator
and Rate‑of‑Rise heat detector head
heat detector head
heat detector head
module
Mounting Considerations
Depending on local regulations, the bases can be surface mounted using anchors, mollies, or wing nuts. The bases can be directly mounted on single‑gang switch boxes or mounted on four‑inch octagonal electrical boxes using the supplied adaptor plate.
Notice
Ensure the volume of any electrical box used accommodates the number and size of conductors as specified by the National Electrical Code (NEC) or any local regulations having jurisdiction.
Electrical (D293E)
Current (alarm): 12 VDC: 82 mA;
Current (standby): 24 mA at 12 VDC and 24 VDC
Voltage (standby): 10 VDC to 30 VDC
24 VDC: 86 mA; 30 VDC: 100 mA maximum
Electrical (D293S)
Alarm Current (base):
Alarm Current(sounder):
Voltage (base): 10 VDC to 30 VDC
Voltage (sounder): 12 VDC nominal, 10 VDC to 16 VDC;
12 VDC: 48 mA; 24 VDC: 51 mA; 30 VDC: 70 mA maximum
12 VDC: 15 mA; 24 VDC: 24 mA; 30 VDC: 25 mA maximum
24 VDC nominal, 18 VDC to 30 VDC
Environmental
Temperature (operating):
+32°F to +100°F (0°C to +38°C)
Mechanical
EOL Supervision
Use one D293E Base for the last detector on the loop or one D275 module per detector loop. Use the EOL resistor(s) specified by the control panel manufacturer.
Parts included
Quant. Component
1 D293A, D293E, or D293S Four‑wire Detector Base
1 Adaptor plate (P/N: 18851)
1 Hardware pack
1 Literature pack
Technical specifications
Electrical (D293A)
Current (alarm): 12 VDC: 58 mA;
24 VDC: 62 mA; 30 VDC: 75 mA maximum
Current (standby): 0.12 mA maximum
Voltage (standby): 10 VDC to 30 VDC
Dimensions (diameter):
6.375 in. (16.2 cm)
Outputs (D293A)
Alarm: One normally-open (NO) relay
Auxiliary: One set of Form C contacts rated for 62.5 VA,
0.5 A at 125 VAC and 30 W, 1.0 A at 30 VDC for resistive loads
Outputs (D293E)
Alarm: One normally‑open (NO) relay
Auxiliary: One set of normally‑open (NO) contacts rated
EOL: One EOL relay rated for 10 W, 0.5 A at 100 VDC
for 62.5 VA, 0.5 A at 125 VAC and 30 W, 1.0 A at 30 VDC for resistive loads
for resistive loads
Outputs (D293S)
Auxiliary: One set of normally‑open (NO) contacts rated
Sounder Powered by external source
for 10 W, 0.5 A at 60 VDC for resistive loads
Ordering information
D293A Four‑wire Detector Base with Auxiliary Relay (Form C)
Four‑wire detector base with an auxiliary Form C relay.
Order number D293A
Loading...