Bosch D290 Specsheet

Fire Alarm Systems | D290 Four‑wire Detector Base (24 VDC)
D290 Four‑wire Detector Base (24 VDC)
www.boschsecurity.com
u 24 VDC, four‑wire circuit compatibility
u Dual Form C relays
u Low profile construction
Use the D290 Detector Base where the specifications call for a 24 VDC, four‑wire photoelectric smoke detector. When using the detector base, a single pair of wires is run for the initiating circuit and another pair is run for the power. The power circuit connects to the power supply of the control panel or an auxiliary UL Listed power supply. A D275 Power Supervision Module must be installed after the last detector base on each power circuit to properly supervise the circuit voltage.
Certifications and approvals
Region Certification
USA UL UROX: Smoke - Automatic Fire Detectors
(ANSI\UL 268)
CSFM see our website
NYC-
284-91-E, Vol. II
MEA
Installation/configuration notes
Compatible Products
The following products are compatible with the D290 Four‑wire Detector Base:
u Molded in UL Listed white ABS plastic
Category Product ID Product Description
Control
Compatible with all UL Listed four‑wire control panels.
Panels
Detector Heads
D254 Fixed‑temperature(+135°F [+57°C])
heat detector
D255 Fixed‑temperature (+190°F [+88°C])
heat detector
D256A Rate‑of‑Rise and fixed‑temperature
(+135°F [+57°C]) heat detector
D257A Rate-of-Rise and fixed-temperature
(+190°F [+88°C]) heat detector
D282A Photoelectric smoke detector head
D283A Photoelectric smoke detector head with
fixed‑temperature (135°F [57°C]) heat sensor
Modules D275 Power supervision module
Mounting
The detector base mounts on standard four‑inch octagonal or four‑inch square electrical back boxes.
2 | D290 Four‑wire Detector Base (24 VDC)
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
Bosch Security Systems B.V. P.O. Box 80002 5617 BA Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6571 2808 Fax: +65 6571 2699 apr.securitysystems@bosch.com www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd. 201 Building, No. 333 Fuquan Road North IBP Changning District, Shanghai 200335 China Phone +86 21 22181111 Fax: +86 21 22182398 www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division Via Anhanguera, Km 98 CEP 13065-900 Campinas, Sao Paulo, Brazil Phone: +55 19 2103 2860 Fax: +55 19 2103 2862 latam.boschsecurity@bosch.com www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice 2707256715 | en, V2, 07. Aug 2014
Notice
Mounting boxes installed in plenums, pressurized stairwells, or other air spaces must follow all applicable codes and the requirements of the authority having jurisdiction (AHJ).
Wiring
For detailed wiring requirements, see the D250A-D290 Series installation instructions.
Parts included
Quant. Component
1 D290 detector base
1 Hardware pack
1 Literature pack
Technical specifications
Electrical
Current (alarm): 43 mA
Current (standby): 0.035 mA to 0.055 mA; depends on
detector head
Voltage (operating): 17.7 VDC to 30 VDC
Environmental
Temperature
+32°F to +100°F (0°C to +38°C)
(operating):
Mechanical
Color: Bone white
Dimensions (diameter x
5.9 in. x 1 in. (15.1 cm x 2.5 cm)
D):
Outputs
Alarm: Two Form C relays with contacts rated for
2 A at 30 VDC, 1 A at 125 VAC for resistive loads
Ordering information
D290 Four‑wire Detector Base (24 VDC)
24 VDC, four wire circuit compatibility
Order number D290