Fire Alarm Systems | D290 Four‑wire Detector Base (24 VDC)
D290 Four‑wire Detector Base (24 VDC)
www.boschsecurity.com
u 24 VDC, four‑wire circuit compatibility
u Dual Form C relays
u Low profile construction
Use the D290 Detector Base where the specifications
call for a 24 VDC, four‑wire photoelectric smoke
detector. When using the detector base, a single pair
of wires is run for the initiating circuit and another pair
is run for the power. The power circuit connects to the
power supply of the control panel or an auxiliary UL
Listed power supply. A D275 Power Supervision
Module must be installed after the last detector base
on each power circuit to properly supervise the circuit
voltage.
Certifications and approvals
Region Certification
USA UL UROX: Smoke - Automatic Fire Detectors
(ANSI\UL 268)
CSFM see our website
NYC-
284-91-E, Vol. II
MEA
Installation/configuration notes
Compatible Products
The following products are compatible with the D290
Four‑wire Detector Base:
u Easy to install and service
u Molded in UL Listed white ABS plastic
Category Product ID Product Description
Control
Compatible with all UL Listed four‑wire control panels.
Panels
Detector
Heads
D254 Fixed‑temperature(+135°F [+57°C])
heat detector
D255 Fixed‑temperature (+190°F [+88°C])
heat detector
D256A Rate‑of‑Rise and fixed‑temperature
(+135°F [+57°C]) heat detector
D257A Rate-of-Rise and fixed-temperature
(+190°F [+88°C]) heat detector
D282A Photoelectric smoke detector head
D283A Photoelectric smoke detector head with
fixed‑temperature (135°F [57°C]) heat
sensor
Modules D275 Power supervision module
Mounting
The detector base mounts on standard four‑inch
octagonal or four‑inch square electrical back boxes.
2 | D290 Four‑wire Detector Base (24 VDC)
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Bosch Security Systems B.V.
P.O. Box 80002
5617 BA Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security
Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd.
201 Building, No. 333 Fuquan Road
North IBP
Changning District, Shanghai
200335 China
Phone +86 21 22181111
Fax: +86 21 22182398
www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division
Via Anhanguera, Km 98
CEP 13065-900
Campinas, Sao Paulo, Brazil
Phone: +55 19 2103 2860
Fax: +55 19 2103 2862
latam.boschsecurity@bosch.com
www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice
2707256715 | en, V2, 07. Aug 2014
Notice
Mounting boxes installed in plenums, pressurized
stairwells, or other air spaces must follow all
applicable codes and the requirements of the
authority having jurisdiction (AHJ).
Wiring
For detailed wiring requirements, see the D250A-D290
Series installation instructions.
Parts included
Quant. Component
1 D290 detector base
1 Hardware pack
1 Literature pack
Technical specifications
Electrical
Current (alarm): 43 mA
Current (standby): 0.035 mA to 0.055 mA; depends on
detector head
Voltage (operating): 17.7 VDC to 30 VDC
Environmental
Temperature
+32°F to +100°F (0°C to +38°C)
(operating):
Mechanical
Color: Bone white
Dimensions (diameter x
5.9 in. x 1 in. (15.1 cm x 2.5 cm)
D):
Outputs
Alarm: Two Form C relays with contacts rated for
2 A at 30 VDC, 1 A at 125 VAC for resistive
loads
Ordering information
D290 Four‑wire Detector Base (24 VDC)
24 VDC, four wire circuit compatibility
Order number D290