Bosch D285, D285TH Installation Instructions Manual

D285/D285TH
Installation Instructions
EN
Photoelectric Smoke Detectors
D285/D285TH | Installation Instructions |
1.0 Overview
The D285 Series Photoelectric Smoke Detectors (D285, D285TH) comply with Part 15 of the Federal Communications Commission (FCC) Rules. Operation is subject to the following two conditions:
1. These detectors might not cause harmful interference.
2. These detectors must accept any interference received, including interference that might cause undesirable operation.
Changes or modifications not expressly approved by Bosch can void the user’s authority to operate the D285 Series Smoke Detectors.
1.0 Overview
The D285 Series are UL Listed, open-area, photoelectric, smoke detectors designed for use with commercial fire protective signaling systems and household fire warning systems (refer to the National Fire Alarm Code [NFPA 72]). These detectors are available in two-wire and four-wire models, and have an optional +135°F (+57°C) fixed-temperature heat sensor.
For commercial and industrial installations, space the detectors 30 ft (9.2 m) apart as recommended by NFPA 72.
When properly installed using the D280/D290 Series Detector Bases, tamper protection is provided by in/out wiring of the positive power line. This causes the control to initiate a trouble signal when a detector is removed from its base. The master control supervises the two-wire systems. Four-wire system supervision is provided by an end-of-line (EOL) power supervision device such as a D275 or a D293E Power Supervision Base and an EOL resistor (as specified by the control manufacturer).
Refer to Table 1 for product descriptions.
Table 1: Product Description
D285 D285TH
D285DH
D287 D292 D293A D293E
D293S D275 TP280
Detector only (requires base) Detector with integral +135°F (+57°C) heat
sensor (requires base) Detector only, for D340 Series Duct Smoke
Detectors Base only, two-wire Base only, four-wire Base only, four-wire, Form “C” auxiliary relay Base only for power supervision, four-wire,
EOL relay, Normally Open auxiliary relay Base only, four-wire, with sounder EOL supervision module for four-wire systems Trim Plate 6 in. (16.2 cm) diameter
The letter “A” is the UL compatibility identifier for the D285 Series. Refer to the Two-Wire Smoke Detector Compatibility Technical Service Note (P/N: 31866) to determine the UL compatibility identifier used with the D287 Base.
Table 2: Specifications
Operating Temperature
Power Requirements
Standby Voltage:
Maximum RMS Ripple:
Start-up Current:
Standby Current:
Note: The D293E equals 24 mA at 12 VDC and 24 VDC.
Alarm Current
Two-wire:
Four-wire:
Power-up Time:
Compatible Control Panels
Two-wire:
Four-wire:
+32° to 100°F (0°C to +38°C ) 0 to 95% relative humidity (non-condensing)
Two-wire: 8.5 VDC to 33 VDC Four-wire: 10 VDC to 30 VDC
25% of DC input
120 µA maximum
80 µA at 12 VDC 90 µA at 24 VDC 100 µA at 33 VDC
Dependent on the control panel that limits the alarm current to 100 mA maximum.
D292: 48 mA at 24 VDC and 51 mA at 24 VDC (70 mA maximum at 30 VDC)
D293E: 80 mA at 12 VDC and 24 VDC (100 mA maximum at 30 VDC)
D293S: Base 48 mA at 12 VDC, sounder 15 mA at 12 VDC, 25 mA at 24 VDC
22 sec maximum
Refer to the
Compatibility Technical Service Note
(P/N: 31866).
Note: Bosch makes no claim (written, oral, or implied) the D285 Series Smoke Detectors work with any two-wire control panels except those specified in the
Two-Wire Smoke Detector Compatibility Technical Service Note
Compatible with all UL Listed four-wire control panels. Refer to the manufacturer's installation instructions for proper EOL resistor selection.
Two-Wire Smoke Detector
(P/N: 31866).
Bosch | 6/04 | 32029E2
D285/D285TH | Installation Instructions | 2.0 Mounting
2.0 Mounting
1. Before mounting, remove the dust cover from the detector. The dust cover can be replaced during construction periods, but it must be removed once the alarm system is enabled.
The tamper screw is located in the recess on the top of the dust cover.
2. Mount the base according to its instructions.
3. Mount the detector to the base by turning it clockwise until it clicks into place. When it is secure, the alignment line aligns with the tamper screw hole (refer to Figure 1).
Figure 1: Mounting the Base
1
1 - Alignment arrow 2 - Base contacts (three sets)
The D285 Series Smoke Detectors are keyed. Do not force a detector onto its bases.
2
3.0 Installation Testing
1. Check the wiring from the control panel to the last head on each run for proper polarity and continuity.
a. Ensure each run terminates with an EOL
resistor as specified by the control panel manufacturer.
b. Ensure the four-wire runs terminate with EOL
modules or D293E Bases.
2. Apply power to the system, checking for alarms and troubles.
a. Note which detectors are in alarm (if any) and
then shut down the system.
b. Remove these detectors from their bases and
recheck the bases for proper wiring. If the problems persist, replace the affected detectors or swap them with known good units. This determines if the problem is caused by the detector or the base.
c. If a system alarm with no detector alarms is
present, remove all detectors and check the wiring at each base. Pay close attention to the wiring of each EOL resistor and EOL module.
3. When the system is free of alarms, check each detector to ensure the red LED indicator is flashing approximately every 3 sec. This verifies the detector is receiving power and operating properly.
4. Test each detector to ensure it will cause a control panel alarm. This is the only way to ensure proper operation. Alarm the detectors by doing one of the following:
a. Place a magnet horizontally against the
detector’s side (centered over the “T” marked on the head) to activate an internal reed switch, or
b. Use a UL Listed aerosol smoke detector
tester such as the Home Safeguard Industries’ 25S to simulate an alarm. Follow the instructions with the aerosol smoke detector tester.
When a detector alarms, the red LED indicator activates and latches into the ON position. Clear the alarm before proceeding to the next detector.
5. Check the overall loading of the alarm loop by measuring the voltage across each EOL resistor. This voltage should equal or exceed the minimum specified by the control panel manufacturer.
3Bosch | 6/04 | 32029E
Loading...
+ 5 hidden pages