Bosch D282A-DH Specsheet

Fire Alarm Systems | D282A‑DH Replacement Duct Smoke Detector Head (24 VDC)
D282A‑DH Replacement Duct Smoke Detector Head (24 VDC)
www.boschsecurity.com
u 24 VDC replacement detector head for D300A and
D300A‑HV Conventional Duct Detector Housings
The D282A‑DH Replacement Duct Smoke Detector Head detects the large smoke particles which typically result from wood, paper, and fabric combustion. It is a conventional 24 VDC photoelectric smoke detector head for use with the D300A and D300A‑HV conventional duct detector housing units. It uses an infrared (IR) LED light source and a silicon photo diode to measure light reflected from particulates in a detection chamber. After two consecutive measurements exceeding the threshold level, the unit signals an alarm condition. The detection chamber, designed for reliable smoke entry characteristics, is protected by a micro-fine insect screen to minimize nuisance alarms. The sensitivity stability and high signal‑to‑noise ratio of this detector permits its use in a wide range of environmental conditions. The detector head has a moisture‑proof reed switch that reacts to an external magnet for testing. The magnet test simulates a 4% to 6% smoke obscuration, which places the detector in an alarm condition. This test is especially useful in environmentally unstable or clean areas. There are built‑in LEDs that flash to indicate the unit is powered. The LEDs latch on steady in an alarm condition.
u Flashing LED power on indicator
Certifications and approvals
Region Certification
USA UL UROX: Smoke - Automatic Fire Detectors
CSFM see our website
Hong Kong HKFSD J-005/C/026
(UL268 and A)
Installation/configuration notes
Compatible Products
The following products are compatible with the D282A‑DH Replacement Duct Smoke Detector Head:
Category Product ID Product Description
Control Panels D7022 Two‑zone FACP
D7024 Conventional FACPs
D7024‑EXPConventional FACPs for export
Detector Housings
D300A‑HV High‑voltage duct smoke detector
D300A Duct smoke detector with housing
with housing
2 | D282A‑DH Replacement Duct Smoke Detector Head (24 VDC)
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc. 130 Perinton Parkway Fairport, New York, 14450, USA Phone: +1 800 289 0096 Fax: +1 585 223 9180 security.sales@us.bosch.com www.boschsecurity.us
Bosch Security Systems B.V. P.O. Box 80002 5617 BA Eindhoven, The Netherlands Phone: + 31 40 2577 284 Fax: +31 40 2577 330 emea.securitysystems@bosch.com www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security Systems 11 Bishan Street 21 Singapore 573943 Phone: +65 6571 2808 Fax: +65 6571 2699 apr.securitysystems@bosch.com www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd. 201 Building, No. 333 Fuquan Road North IBP Changning District, Shanghai 200335 China Phone +86 21 22181111 Fax: +86 21 22182398 www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division Via Anhanguera, Km 98 CEP 13065-900 Campinas, Sao Paulo, Brazil Phone: +55 19 2103 2860 Fax: +55 19 2103 2862 latam.boschsecurity@bosch.com www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice 2702251147 | en, V2, 04. Aug 2014
Installation
The D282A‑DH installs quickly and easily into the D300A and D300A‑HV. Remove the four screws that hold the housing unit's cover in place, twist the existing detector head counter‑clockwise to remove it, insert the replacement head, turn it clockwise, replace the housing unit's cover and tighten the screws.
Parts included
Quant. Component
1 D282A‑DH repalcement detector head
1 Literature pack
Technical specifications
Environmental Considerations
Relative Humidity: 10% to 85% non‑condensing
Temperature (operating): +32°F to +120°F (0°C to +49°C)
Mechanical Properties
Color: Bone white
Dimensions (diameter): 4 in. (10.2 cm)
Power Requirements
Current
Alarm: Depends on housing; refer to the D300A or D300A‑HV
specifications
Standby: 0.045 mA
Surge: 0.16 mA
Voltage
Operating: 15.0 VDC to 33.0 VDC
Ordering information
D282A‑DH Replacement Duct Smoke Detector Head (24 VDC)
Detects the large smoke particles which typically result from wood, paper, and fabric combustion
Order number D282A-DH
Loading...