Bosch D263, D263TH Specsheet

Fire Alarm Systems | D263 Photoelectric Smoke and Smoke and Heat Detectors
D263 Photoelectric Smoke and Smoke and Heat Detectors
www.boschsecurity.com
u 12 V or 24 V input
u Designed for commercial or residential use
The D263 family includes the following detector models:
Model Description
D263 Two-wire
D263TH Two-wire with 135°F (57°C) heat sensor
D263THS* Two-wire with 135°F (57°C) heat sensor and
sounder
* Sounders produce 85 dB at 10 ft (3 m). Each of these detector models is UL Listed and works with commercial fire protective signaling and household fire warning systems. Each model detects smoke particles produced during wood, paper, and fabric combustion.
System overview
These detector models use an infrared (IR) LED light source and a silicon photodiode to measure light in a chamber. A fine screen covers the chamber to deter insects and to reduce dust accumulation and nuisance alarms.
u Light-emitting diodes (LEDs) indicate the status of
the chamber, power, and alarm
u Removable terminal block to simplify wiring
connections
During a fire, smoke particles reflect light onto the photodiode. When the photodiode measurements exceed the alarm threshold, the detector signals an alarm condition. After the alarm condition clears, interrupt power at the control panel to reset the detector. Use a D132B Reversing Relay Module to activate the sounder (85 dB at 10 ft [3 m]). When using a D132B, the LED does not latch on alarm.
Functions
Chamber Calibration Tests
Check the sensitivity and calibration of any of these detectors using a visual check, a magnet test, or a voltage measurement test. Visual check: When the detector’s calibration is within the factory­listed range, the red alarm LED flashes once every
3.5 sec. If the detector’s calibration is out of range for more than 24 h, the red alarm LED flashes once a second. Magnet test:
2 | D263 Photoelectric Smoke and Smoke and Heat Detectors
Hold a magnet horizontally against the detector for about 10 sec and observe the LED.
• If the detector is within the factory-listed calibration range, it goes into alarm and the Alarm LED latches on.
• If the detector is too sensitive, the LED rapidly flashes six times (once every half second) and the detector signals an alarm.
• If the detector is not sensitive enough, the LED slowly flashes four times, once every 2 seconds, and the detector signals an alarm.
• If the detector does not operate, it does not signal an alarm.
Voltage measurement test: Use a D1005 Test Cable and a digital voltmeter to measure the voltage and compare the results with the factory-listed sensitivity range.
Certifications and approvals
Region Certification
USA UL UROX: Smoke - Automatic Fire Detectors
CSFM see our website
NYC­MEA
MSFM
Hong Kong HKFSD D263\TH\THS
(UL268 and A), UROX7: Smoke - Auto­matic Fire Detectors Certified for Cana­da (cULus),
274-93-E, Vol. VII
Installation/configuration notes
Use smoke detectors for detection circuits that protect people. Use heat detectors for circuits that protect property.
Compatible Products
The following products are compatible with the D263 Series detectors:
Category Product ID Product Description
Control Panels
Modules D132B Reversing relay module
Bosch Security Systems makes no claim written, oral, or implied that the D263 Series detectors work with any two-wire control panels except those specified in the Control Panel Compatibility chart in Technical Service Note (P/N: 31866).
Mounting
The detector has a mounting plate that attaches on a standard four-inch back box. For commercial and industrial installations in accordance with NFPA 72, space each detector 30 ft (9.2 m) apart.
Wiring
The terminal block accepts up to 12 AWG (ISO 4 mm2) wire. You can remove the terminal block from the detector for easier wiring. The terminal block snaps in and out of the detector.
Parts included
QuantityComponent
1 Detector
1 Lit pack – Installation Manual, Technical Service Note on
installation
Technical specifications
Environmental Considerations
Radio Frequency Interference (RFI) Immunity:
Relative Humidity: Up to 93%, non-condensing
Temperature (operating): +32°F to +120°F (0°C to +40°C)
No alarm on critical frequencies in the range of 26 MHz to 950 MHz.
Mechanical Properties
Dimensions (Diameter x H): 5 in. x 2 in. (12.7 cm x 5.1 cm)
Material: High impact, fire retardant ABS
plastic
Relay Contacts
Auxiliary Form C:
1 A, 120 VAC/30 VDC at 1 A, 30 W maximum
Power Requirements
Current Draw (alarm): Determined by control panel
Current Draw (standby): 0.080 mA at 12 V, 0.1 mA maximum
Current Draw (start-up): 0.12 mA
Current Draw (trouble): 0.1 mA maximum
Power-up Time: 22 sec maximum
RMS Ripple (maximum): 25% of DC input
Voltage (stand-by): 8.5 VDC to 33 VDC
Ordering information
D263 Two‑Wire Smoke Detector
Two‑wire photoelectric smoke detector.
Order number D263
D263TH Two‑Wire Smoke/Heat Detector
Two‑wire photoelectric smoke detector with a 135°F (57°C) heat sensor.
Order number D263TH