Fire Alarm Systems | D132A Smoke Detector Reversing Relay Module
D132A Smoke Detector Reversing Relay
Module
www.boschsecurity.com
u Allows compatible control panels to sound all smoke
detectors within a loop during an alarm
The D132A Smoke Detector Reversing Relay Module
allows compatible control panels to sound all smoke
detectors connected to point 1 or zone 1 when a
single detector on the loop goes into alarm.
Functions
Reverse Trigger
The reverse trigger requires a low input (short to
ground) to activate. When activated, it reveses polarity
on the detector loop.
Sounding Detectors in a Loop
When an alarm occurs within a loop connected to
point 1 or zone 1, all detectors on that loop go into
alarm. To restore the devices, the sensors must be
reset.
Trouble Point
During normal operation the trouble point relay is
normally closed (NC). During a trouble condition, the
relay switches to normally open (NO).
u Mounts easily on any of the three-hole module
mounting locations in a compatible control panel
enclosure
Certifications and approvals
Region Certification
USA UL UTOU: Control Units and Accessories -
CSFM see our website
Household System Type (UL985)
Installation/configuration notes
Compatibility
Category Manufactu
Control
Panels
Detectors Bosch D263THS Two-wire PIR smoke
rer
Bosch B-series panels
Model Number*
1
G-series panels
D6412 and D4412 panels
detector with 135°F (57°C) heat sensor
and sounder
2
D273THCS Four-wire PIR smoke
detector with 135°F (57°C) heat
sensor, auxiliary relay, and sounder
2 | D132A Smoke Detector Reversing Relay Module
Category Manufactu
Model Number*
rer
D273THES Four-wire PIR smoke
detector with 135°F (57°C) heat
sensor, sounder, and EOL relay
D273THS Four-wire PIR smoke
detector with 135°F (57°C) heat sensor
and sounder
1
B-series = B5512, B4512 and B3512 panels
2
G-series = D9412GV4, D7412GV4, D7212GV4, D9412GV3,
D7412GV3, D7212GV3, D9412GV2, D7412GV2, D7212GV2
*For legacy products compatible with the D132A, see the D132A
Installation Instructions.
Mounting Considerations
The module has a 3‑hole pattern for easily mounting
inside the control panel’s enclosure. Mounting screws
are provided.
Wiring Considerations
The module’s terminal block accepts wire gauges from
22 AWG to 16 AWG (ISO 0.34 mm2 to 1.5 mm2). The
maximum detector circuit length is dependent on the
wire gauge and the number of detectors on the loop.
Parts included
a single smoke detector on the loop goes into alarm.
To restore the smoke detectors to normal, reset the
smoke detectors.
Order number D132A
Quantity Component
1 D132A module
1 Hardware pack containing 3 mounting screws
1 Installation Guide
Technical specifications
Electrical
Current (Alarm): 70 mA maximum
Current (Idle): 10 mA maximum
Voltage (Operating): 10.2 VDC to 13.9 VDC
Environmental
Environment Indoor, dry
Operating Temperature: +32°F to +120°F (0°C to +49°C)
Relative Humidity: 5% to 85% at +86°F (+30°C) non-
condensing
Mechanical
Dimensions: 3 in. x 3 in. (7.6 cm x 7. cm)
Ordering information
D132A Smoke Detector Reversing Relay Module
This module allows compatible control panels
(G Series, B series, D6412 and D4412) to sound all
smoke detectors connected to point 1 or zone 1 when