1 | Overview
The D130 Auxiliary Relay Module is an accessory for use with
Bosch Security Systems, Inc. control panels. (For additional
information, refer to your control panel documentation.)
This module has a 12 V/24 V relay with two sets of nonlatching Form C contacts. The D130 allows the system to
switch larger amounts of current or different voltages that
are beyond the control panel’s auxiliary power rating, or the
rating of modules such as the D8129 Octo-relay Module or
the B308 Octo-output Module.
Use the D130 with a D125B Dual Class B Initiating Module and a 24 VDC power supply to interrupt power to 24 V
smoke detectors with the Sensor Reset function at a keypad.
Armt
NO COM NEGNC
NO
COMNC12 V
24 V
E1
CUT FOR 24 V COIL
Figure 1.1: D130
The D130 uses a 12 V or 24 V power source to power its coil.
The relay can be energized by switching the 12/24 V or the
NEG side of the relay coil. When the contacts are in the inactive
state, the normally closed (NC) terminal has continuity with the
common (COM) terminal. In the active state, the normally open
(NO) terminal has continuity with the COM terminal. A red LED
indicates the coil of the relay is energized.
Auxiliary
Relay Module overview
2 | Mount the module
Mount the module into the enclosure’s 3-hole mounting
pattern using the supplied mounting screws and mounting
bracket. Refer to Figure 2.1.
Mounting the module:
1. Using the two supplied #4 screws, attach the D130 to
the supplied three-hole mounting bracket.
2. Align the mounting bracket and module.
3. Using the three supplied #8 screws, secure the mounting
bracket and module through either side of the control
panel enclosure.
2
1
3
4
E1
CU R 24 V C
Arm t
2
Figure 2.1: Mounting the D130
F01I011616
>ABS/PC<
6
5
Callout ― Description
1 ― Module
2 ― #4 screw
3 ― Mounting bracket
4 ― Control panel enclosure wall
5 ― Mounting locations
6 ― #8 screw holes for mounting to enclosure inside wall
3 | Wire the module
Wire the module to the control panel and other devices using
the fi gures in this section.
NOTICE!
For system supervision, do not use looped wire
under the terminals. Break the wire run to provide
supervision of the connections.
NOTICE!
Run all non-power limited wiring at least 0.25 in
(0.64 cm) from power limited wiring.
3.1 | Wire for switched auxiliary power devices
7
POS+NEG
-
2
NO COM NC NEG
1
12 V NC COM NO
24 V
1
E1
6
Figure 3.1: Wiring a D130 with 12 VDC or 24 VDC power
supply for switched auxiliary power devices
Callout ― Description
1 ― Power limited, supervised
2 ― D130 module
3 ― Control panel
4 ― 12 VDC* switched AUX power terminal
5 ― COM terminal (of the control panel)
6 ― Jumper E1 not cut*
7 ― External 12 VDC or 24 VDC power supply**
8 ― Device requiring 12 VDC or 24 VDC switched auxiliary
power
* If power output is 24 VDC, cut Jumper E1.
** When using ground fault detect, do not reference the
external power supply negative terminal to earth ground.
8
POS+NEG
3
-
4
5
3.2 | Wire with a D125B Dual Class B
Inititating Module
NOTICE!
To supervise the loops, install an end-of-line (EOL)
resistor beyond the last detector of each protective
loop. If you are replacing a D125 or D125A module
with the D125B, you can use the 1.5 k
installed with the original system. If you are installing
a D125B in a new system, or in an existing system
and adding additional devices, use the 1.8 k
resistor (P/N: 15-03130-006) supplied with the
module.
Ω resistor
Ω
NOTICE!
Refer to the D125B Installation Instructions (P/N:
F01U036340) for more information.
5
TB1/J1
1
ZONE
SWITCH
4
POS+NEG
-
9
2
NO COM NC NEG
E1
6
R8
3
4 5
2
ZONE
PANEL
A
COMMON
B
7
8
12 V NC COM NO
24 V
RV1
RV4
LOOP
1
1
RV3
8
7
6
B+
A-
B-
LOOP
LOOP
LOOP
RV2
9
10
A+
EARTH
GND
3
10
11
Figure 3.2: Wiring a D130 with 12 VDC or 24 VDC power
supply and a D125B
Callout ― Description
1 ― Power limited, supervised
2 ― D130 module
3 ― Control panel
4 ― External UL Listed 12 VDC or 24 VDC regulated power
supply*
5 ― D125B Dual Class A Initiating Module
6 ― Jumper E1 not cut**
7 ― To on-board point or expansion module***
8 ― Connect only to one common at the control panel
9 ― To additional D125B Dual Class A Initiating Module
10 ― 12 VDC** switched Aux power terminal
11 ― COM Terminal
* When using ground fault detect, do not reference the
external power supply negative terminal to earth ground.
** If power output is 24 VDC, cut Jumper E1.
*** A D8128D OctoPOPIT Module or a B208 Octo-input
Module can be used.
3.3 |
Wire with a D125B
Dual Class B Inititating Module
and a D8129 Octo-relay Module
4 | Certifi cations
NOTICE!
Refer to the D125B Installation Instructions (P/N: F01U036340) for more information.
After any programming or hardware change, perform a functional test of the system as required by local codes.
5
POS+NEG
-
10
3
NO COM NC NEG
12 V NC COM NO
24 V
E1
11
6
TB1/J1
SWITCH
4
ZONEX OUT 1
ZONEX OUT 2
Aux Power +
COM
1
ZONE
RV1
RV4
LOOP
1
2
RV3
6
7
8
B-
A-
B+
LOOP
LOOP
LOOP
NC
RV2
10
9
EARTH
A+
GND
DATA
AUX
GND
COMMNCNO
COMM
2
1
7
NO
COMMNCNO
COMMNCNO
COMMNCNO
COMMNCNO
COMMNCNO
COMMNCNO
8
7
6
5
4
3
R8
2
4 5
3
PANEL
ZONE
B
COMMON
A
8
9
1
1
2
Figure 3.2: Wiring a D130 with 12 VDC or 24 VDC power supply and the D125B and an expansion module
Callout ― Description
1 ― Power limited
2 ― Supervised
3 ― D130 module
4 ― Control panel* (ZONEX 2 available on D9412GV4/D9412GV3/D9412GV2/D9412G/D9412/D9112/D9112B1 only)
5 ― External UL Listed 12 VDC or 24 VDC regulated power supply**
6 ― D125B Dual Class A Initiating Module
7 ― D8129 Octo-relay Module*
8 ― To on-board point or expansion module***
9 ― Connect only to one common at the control panel
10 ― To an additional D125B Powered Loop Interface Module
11 ― Jumper E1 not cut****
* When using an SDI2 control panel, use a B308 Octo-output Module and SDI2 wiring instead of the D8129 and ZONEX wiring.
** When using ground fault detect, do not reference the external power supply negative terminal to earth ground.
*** A D8128D OctoPOPIT Module or a B208 Octo-input Module can be used.
**** If power output is 24 VDC, cut Jumper E1.
Region Certifi cation
US UL APOU: Proprietary Alarm Units
(UL1076),
UOJZ: Control Units, System (UL864,
9th edition)
CSFM 7167-1615: 100
7165-1615:0242
7165-1615:0238
7165-1615:0119
7167-1615:0239
NYCMEA
12-92-E, Vol. II 12-92-E, Vol. II
12-92-E, Vol. 12 12-92-E, Vol. 12
12-92-E, Vol. 15 12-92-E, Vol. 15
FDNY-
6059
CoA
5 | Specifi cations
Dimensions 70 mm x 76 mm (2.75 in x 3.0 in)
Relay 5 A @ 30 VDC maximum
10 A @ 5 VDC minimum
Current Max 60 mA Standby
60 mA Alarm
Power input Nominal 12 VDC with jumper intact
Nominal 24 VDC with jumper cut
Power supplies UL1481 and UL864 Listed auxiliary
12 VDC or 24 VDC regulated, power
limited power supply for Fire Protective
Signaling Units and Commercial/
Residential Burglar Units
Fire or control
panel wiring
Compatible
control panels
Copyright
This document is the intellectual property of Bosch Security
Systems, Inc. and is protected by copyright. All rights reserved.
Trademarks
All hardware and software product names used in this document
are likely to be registered trademarks and must be treated
accordingly.
Bosch Security Systems, Inc. product manufacturing dates
Use the serial number located on the product label and refer to
the Bosch Security Systems, Inc. website at
http://www.boschsecurity.com/datecodes/.
Maximum distance - Wire size (maximum
resistance: 1
Ω
):
60 ft (18 m) - 22 AWG (0.65 mm)
160 ft (48 m) - 18 AWG (2 mm)
All Bosch Security Systems, Inc. control
panels and FACPs
Auxiliary Relay Module
D130