Fire Alarm Systems | D113 Battery Lead Supervision Module
D113 Battery Lead Supervision Module
www.boschsecurity.com
u Works with 12 V nominal systems
u Meets NFPA 72 requirements for battery lead
supervision for fire alarm control panels (FACPs)
This module provides supervision of the battery lead
connection in a system controlled by a Bosch Security
Systems, Inc. 12 VDC control panel. This module may
be used with other panels when referenced in the
panel’s installation/operation instructions. The module
meets NFPA 72 requirements for battery lead
supervision for fire alarm control panels (FACPs).
Functions
Trouble and Supervisory Conditions
When the D113 detects a disconnected battery lead, it
creates a shorted condition on the supervising zone or
point. The panel should be programmed according to
the appropriate programming guide to generate a
trouble response to a shorted condition on the loop.
The D113 is reset by reconnecting the battery lead and
clearing the trouble condition at the FACP.
Certifications and approvals
Region Certification
USA UL AMCX: Central Station Alarm Units (AN-
SI/UL 1610 and ANSI/UL 1635), AOTX:
Local Alarm Units (ANSI/UL 609 and ANSI/UL 464), APOU: Proprietary Alarm
Units (ANSI/UL 1076), NBSX: Household Burglar Alarm System Units
(ANSI/UL 1023), UOXX: Control Unit Ac-
Region Certification
cessories, System (ANSI/UL 864), and
UTOU: Control Units and Accessories,
Household System Type (ANSI/UL 985)
CSFM see our website
NYC-
12-92-E,_Vol. XII
MEA
NYC-
12-92-E, Vol. XV
MEA
Installation/configuration notes
Compatible products
The following products are compatible with the D113
module:
Category Product
Batteries D126 Standby Battery (12 V, 7 Ah)
D1218 Battery (12 V, 18 Ah)
Control
G series panels
1
panels
2 | D113 Battery Lead Supervision Module
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Bosch Security Systems B.V.
P.O. Box 80002
5617 BA Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security
Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd.
201 Building, No. 333 Fuquan Road
North IBP
Changning District, Shanghai
200335 China
Phone +86 21 22181111
Fax: +86 21 22182398
www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division
Via Anhanguera, Km 98
CEP 13065-900
Campinas, Sao Paulo, Brazil
Phone: +55 19 2103 2860
Fax: +55 19 2103 2862
latam.boschsecurity@bosch.com
www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice
2695042827 | en, V3, 23. Jul 2014
Category Product
1
G-series = D9412GV4, D7412GV4, D7212GV42, D9412GV3,
D7412GV3, D7212GV32, D9412GV2, D7412GV2, D7212GV22,
D9412G, D7412G, D7212G
2
These products are legacy products and have been investigated for
2
compatibility only to UL864 8th edition.
Parts included
Quantity Component
1 D113 module
1 Snap track
1 Hardware pack (3 screws and module connection
wires)
1 Literature pack (Installation Manual)
Technical specifications
Electrical
Voltage (input range) 10.2 V min to 13.9 V max
Voltage (battery) 12 V nominal
Current draw
1
For battery calc, use 45 mA for alarm and 45 mA for standby
1
45 mA
Ordering information
D113 Battery Lead Supervision Module
Supervises wiring connections for two 12 V batteries
connected to the same set of charging terminals.
Order number D113