Bosch c-Si M 60-225-16, c-Si M 60-240-16, c-Si M 60-230-16, c-Si M 60-235-16 Installation And Safety Manual

Page 1
Solar Energy
Installation and Safety Manual of the Bosch Solar Modules c-Si M 60-225-16, c-Si M 60-230-16, c-Si M 60-235-16, c-Si M 60-240-16
Read Me
Thank you for buying our Bosch Solar photo­voltaic (PV) modules. This manual describes the installation and maintenance instructions for the modules intended for use in North America.
Before installing, wiring and using a module, it is important to thoroughly read this manual and understand the instructions. Installers must understand the basic principles of electricity and electrical apparatuses as well as article 690 of the National Electrical Code. Special atten­tion must be given to the safety instructions.
Disclaimer of Liability
Since the use of this Safety and Installation Manual and the conditions or methods of instal­lation, operation, use and maintenance of the module are beyond the control of Bosch Solar, Bosch Solar does not assume responsibility and expressively disclaims liability for loss, damage injury or expense arising out of or in any con­nected with such installation operation, use or maintenance of the module.
Bosch Solar assumes no responsibility for in­fringement of patents or other rights of third parties which may result from use of the mod­ule. No license is granted by implication or oth­erwise under any patent or patent rights. The information in this Manual is based on Bosch Solar‘s knowledge and experience and is be­lieved to be reliable; but such information in­cluding product specifications (without limita­tions) and suggestions do not constitute a war­ranty, expressed or implied. Bosch Solar re­serves the right to make changes to the prod­uct, specification or the Manual without prior notice.
1. Important Safeguards/Warnings
Read this section carefully before installing, using, repairing or performing maintenance on the PV modules or the PV power system.
WARNING
Lethal voltages and/or shock hazard may
be present in modules and arrays during sunlight hours, even at low light level. This hazard increases when multiple modules are connected together to pro­vide higher system voltage or current levels. Dangerous voltages may also be present at night from connections to batteries and feedback from inverters or other parts of the system.
Bosch Solar modules should only be installed by qualified installers with adequate solar in­stallation experience. You must comply with the standards and regulations applicable to PV in­stallations, such as National Electrical Code (NEC) and other building codes, the grid opera­tor’s technical connection requirements, and trade association rules concerning accident prevention. Failure to comply can lead to sig­nificant personal injury and equipment damage.
Lethal voltages and/or a shock hazard may be present in modules and arrays during sunlight hours, even at low light level. This hazard in­creases when multiple modules are connected together to provide higher system voltage or current levels. Dangerous voltages may also be present at night from connections to batteries and feedback from inverters or other parts of the system.
2. Underwriters Laboratories Information
(U.S. and Canada Only)
Bosch Solar c-Si M 60-225-16, c-Si M 60-230-16, c-Si M 60-235-16 and c-Si M 60-240-16 are UL 1703 listed. This UL standard covers flat-plate photovoltaic modules and panels intended for installation on or integral with buildings or to be freestanding (not attached to buildings), in accordance with the National Electrical Code (NFPA 70), appropriate Building Codes, and any other applicable Local Codes in the US.
UL Listed Bosch Solar c-Si modules are rated class C and intended to be installed on “Class A” fire rated roofs, residential or commercial, per local codes in US.
1/9
photovoltaikforum.com
Page 2
Solar Energy
For “Class C” modules, the assembly is to be mounted over a fire resistant roof covering rated for the application.
Under normal conditions, a photovoltaic module is likely to experience conditions that produce more current and/or voltage than reported at standard test conditions. Therefore, the values of Isc and Voc marked on this module must be sized according to section 690-8 of the National Electrical Code for all component voltage rat­ings, conductor ampacities, fuse sizes, and size of controls connected to PV output.
Use only UL Listed grounding lugs suitable for outdoor use: Burndy P/N CL-50-DB or ILSCO P/N GBL-4DB in conjunction with an 8-32 stainless steel fastener and star washer. USE conductor cable of minimum 10 AWG and minimum 90°C temperature rating, which is also sunlight resistant rated, for modules and interconnect wiring that is exposed to weather as per NEC.
National Electrical Code (NEC)
The National Electrical Code (NEC) covers the installation of photovoltaic systems and must be adhered to when systems are designed and installed. Article 690, Solar Photovoltaic Sys­tems, of the NEC applies to solar photovoltaic electrical energy systems including the array circuit(s), power conditioning unit(s) and con­troller(s) for such systems.
All wiring shall be in accordance with the NEC, and grounding method of the frame of arrays shall comply with the NEC, article 250.
USL/CNL
All USL/CNL installations shall be in accordance with CSA C22.1, Safety Standard for Electrical Installations, Canadian Electrical Code, Part 1.
2/9
photovoltaikforum.com
Page 3
Solar Energy
3. Bosch Solar Module Electrical Characteristics
Model
Open Circuit Voltage at STC, (V dc)
Rated Voltage at STC, (V dc)
Maxi­mum Sys­tem Volta­ge, (V dc)
Rated Current at STC, (A dc)
Short Circuit Current at STC, (A dc)
Rated Maximum Power at STC, (Watts)
Maximum Series Fuse, (A)
c-Si M 60-225-16
36.0 28.3
600
7.95 8.7 225 15
c-Si M 60-230-16
36.35 28.75
600
8.0 8.75 230 15
c-Si M 60-235-16
36.5 29.35
600
8.0 8.75 235 15
c-Si M 60-240-16
36.7 29.65
600
8.1 8.8 240 15
Module bypass diode type, voltage rating, current rating, and configuration of the diode
Diode Ratings Module series Total #
of Dio-
des
Diodes # in par-
allel for each
string
Diode Manufac-
turer
Diode
Type
(A) (PIV)
c-Si M 60-225-16
3 1 Tyco SL1010 11 40
c-Si M 60-230-16
3 1 Tyco SL1010 11 40
c-Si M 60-235-16
3 1 Tyco SL1010 11 40
c-Si M 60-240-16
3 1 Tyco SL1010 11 40
NOTE: DO NOT attempt to open the diode housing or junction box located on the back side of any Bosch Solar module. There are no user serviceable parts inside.
4. SAFETY INSTRUCTIONS
Handling Safety
DO NOT drop, allow objects to fall on,
or stand or step on modules.
DO NOT install during high winds.
Never leave a module unsupported or
unsecured. If a module falls, the glass could break. A module with broken glass cannot be repaired and must not be used.
DO NOT disassemble the module, or
remove any part installed by Bosch So­lar. Use modules for their intended use
only and follow all manufacturers’ in­structions.
DO NOT attempt to remove snow or ice
from the module.
DO NOT direct artificially concentrated
sunlight on the module.
Installation Safety
DO NOT attempt to install or service
any portion of the PV system unless you understand the electrical operation and are fully qualified to do so.
3/9
photovoltaikforum.com
Page 4
Solar Energy
DO NOT drill holes in the frame or glass
of the module. Doing so will void the warranty.
Have a fire extinguisher, and first aid kit
when performing field work on all ener­gized equipment where the system open circuit voltage is 30 volts or greater.
Since sparks may be produced, do not
install module where flammable gases or vapours are present
DO NOT attempt to open the diode
housing or junction box located on the back side of any Bosch Solar module. There are no user serviceable parts in­side.
DO NOT work on modules when mod-
ules are wet. If a wet module is cracked or broken the full system voltage may be present.
Fire Safety
1. Refer to your local authority for guide-
lines and requirements of building or structural fire safety.
2. It may be necessary to use components
such as earth ground fault circuit breakers, fuses and circuit breakers
3. Do not use modules near equipment or
locations where flammable gasses can be generated or can collect.
Electrical Safety
Rated electrical characteristics are
within ±10 percent of the indicated val­ues of Isc, Voc, Pmax under Standard Test Conditions. (Irradiance of 100 W/cm, Am 1.5 spectrum and a cell temperature of 25°C (77°F).
Under normal conditions, a photo-
voltaic module may experience condi­tions that produce more current and/or voltage than reported at Standard Test Conditions. Accordingly, the values of ISC and VOC marked on UL Listed modules should be multiplied by a fac­tor of 1.25 when determining compo­nent voltage ratings, conductor capaci­ties, fuse sizes and size of controls
connected to the module output. Refer to Sec. 690-8 of the National Electric Code for an additional multiplying fac­tor of 125 percent (80 percent of rat­ing) which may be applicable.
DO NOT wear jewellery when working
on the modules.
A two-person team is to be used while
performing field work on all energized equipment where the system open cir­cuit voltage is 30 volts or greater.
Wear electrical insulating gloves rated
at 1000 volts and suitable eye protec­tion when working on systems where the system open circuit voltage is 30 volts or greater.
DO NOT touch terminals while the
module is exposed to light without wearing electrical insulating gloves.
DO NOT use modules in systems that
can exceed 600 volts open circuit under any combination of solar irradiation and ambient temperature.
DO NOT connect or disconnect a mod-
ule unless the array string is open- cir­cuited or all of the modules in the string are covered.
5. Mechanical Installation
NOTE: The maximum wind and snow loads on a module mounted in any position must not exceed a re­sultant surface load of 30lb/ft² over the module surface. Reference ASCE 7-95 for determining the proper wind and snow load calculations for each location. All installations should also be in accordance with local building codes and regula­tions. For proper structural design, it is recom­mended to retain the services of a structural engineer experienced with the installations of PV systems.
NOTE: It is the sole responsibility of the user and/or installer to verify that the module mounting sys­tem and mounting method are properly engi­neered and in accordance with local building codes and regulations.
4/9
photovoltaikforum.com
Page 5
Solar Energy
NOTE: Modules shall be mounted so that the junction box shall be in the uppermost position to mini­mize the ingress of water.
Clearance between Modules
A clearance of 6mm/.25” between modules is sufficient in most installations to accommodate thermal expansion. However, the appropriate clearance is dependent upon installation spe­cific factors including the module mounting system, temperature at the site and the maxi­mum operating temperature of the module. The maximum distance between modules should not exceed 12” based on using standard wiring.
Orientation, Tilt Angle & Shading
Photovoltaic modules generate maximum power when facing directly towards the sun. PV sys­tems can track the sun or remain in a fixed tilt position. Tracking systems will produce more energy but are more costly and require more maintenance. PV systems are predominantly set at a tilt. The further North from the equator, the more tilt. Since applications and needs are different, consult a PV system integrator or use a commercially available software program to determine the expected energy output. The following chart may serve as a rule of thumb.
Site Latitude Horizontal Tilt Angle
0-10 = 10 Degrees
11-20 = Latitude
21-30 = Latitude + 5~
31-40 = Latitude + 10~
41+ = Latitude + 15~
The following paragraphs list some other gen­eral rules of thumb:
It is not recommended to set the tilt angle be­low 10-15 degrees. Dirt tends to accumulate on modules installed at flatter angles and does not wash off as readily during rainfall. Dirt accumu­lation or any debris, even snowfall on the mod­ule will reduce its energy output.
Modules should be located in areas with an unobstructed view of the sun where they will receive maximum exposure of sunlight for the longest possible time during the day. Shadow­ing caused by buildings, trees, utility poles and other obstructions, significantly reduces the
module energy output.
In systems that are configured with multiple rows of modules, the rows must be spaced far enough apart to minimize the impact of shading on other rows. This distance is dependent on the latitude and tilt angle at which the system is installed. The closer to the equator, requires a lower tilt angle and therefore the shorter this distance. The further from the equator, higher tilt angle and therefore the greater this distance needs to be. If there are questions regarding the optimum configuration in which to arrange, mount or wire the modules, obtain assistance from your Bosch Solar dealer or distributor or retain the services of an engineer familiar with the proper design of PV systems.
Suggested Mounting Methods
The information in this section only suggests possible methods of securing the PV modules to a ‘module mounting system.’
It is the sole responsibility of the user and/or installer to verify that the module mounting system and mounting method is properly engi­neered and is in accordance with local building codes and regulations.
Bosch Solar PV modules can be arranged in either landscape or portrait position on flat or sloped roofs or surfaces and at flat or tilted angles.
The modules shall be mounted so that the junc­tion box shall be in the uppermost position to minimize the ingress of water.
NOTE: Always use caution when mounting a module on tilted angles or sloped roofs so the module does not slide out of position while attaching it to the module mounting system.
NOTE: The minimum standoff distance between Bosch Solar modules and the roof is 40mm.
CAUTION Never leave a module unsupported or unsecured. If a module falls, the glass could break. A module with broken glass cannot be repaired and must not be installed.
Bosch Solar requires one of the following meth­ods for mounting Bosch Solar PV Modules:
5/9
photovoltaikforum.com
Page 6
Solar Energy
A. The four provided mounting holes
on the bottom of the modules, us­ing ¼” bolts with washers and nuts. Bolt torque is 15-20 ft-lbs.
B. Uni-Rac type “unistrut” or C-
channel rails, using Uni-Rac clamp mount clips part numbers N:320201 (end clamps) or N:320199 (mid clamps) secured with ¼” – 14 bolts. Bolt torque is 12-15ft-lbs.
Refer to Figure 2, Details A, B, and C for three examples of different methods using various hardware for attaching the PV module to the module mounting system.
NOTE: Under no circumstances may the short frame edges be used for anchoring the module.
Use only the 4 recommended mounting holes (See Figure 1)
Mounting holes (4X)
Grounding holes (4X)
Figure 1: Mechanical Layout
6/9
photovoltaikforum.com
Page 7
Solar Energy
Figure 2: Examples of Attaching Modules
7/9
photovoltaikforum.com
Page 8
Solar Energy
6. Electrical Installation
Module To Module Interconnection
Bosch Solar modules have been designed to be easily interconnected. Each module comes with one positive (+) wire with a plug on one end and one negative (-) wire with a receptacle on one end. Both wires are connected inside of the junction box (diode housing). Modules are interconnected by inserting the plug from one module into the receptacle of the next module in the array string. Secure the mated connector pair to the inside flange of the module frame to protect it from damage.
Building Source Circuit and Configuring
Modules
PV arrays are comprised of source circuits. A source circuit is a series of modules connected together to reach the desired power. The num­ber of modules in a source circuit can vary de­pending on the module voltage and desired system voltage, provided the max system volt­age does not exceed that allowed by NEC Sec­tion 690-7 (600 volts).
When calculating the system operational volt­ages use the module V
p. However, for NEC
compliance, the maximum system voltage is calculated using Voc.
When determining component voltage ratings, conductor ampacities, fuse sizes, and size of controls connected to PV output, use the values of Isc and Voc marked on the module or found in this instruction manual.
NOTE: Under normal conditions, a photovoltaic module is likely to experience conditions that produce more current and/or voltage than reported at standard test conditions. Accordingly, the val­ues of Isc and Voc marked on this module must be multiplied by a factor of 1.25 when determin­ing component voltage ratings, conductor am­pacities, fuse sizes, and size of controls con­nected to PV output.
Refer to Section 690-8 of the National Electrical Code for an additional multiplying factor of 125 percent (80 percent derating) which may be applicable.
CAUTION DO NOT connect or disconnect a Bosch Solar module unless the array string is open-circuited or all of the modules in the string are covered. The connectors are not designed to make or break the full system current.
CAUTION Be aware that the artificially concentration sunlight shall not be directed on the modules or panels.
Module Grounding
The module frame must be properly grounded. The installer shall ground the frame using the grounding method described in NEC Article 250.
All USL/CNL installations shall be in accordance with CSA C22.1, Safety Standard for Electrical Installations, Canadian Electrical Code, Part 1.
The grounding wire must be properly fastened to the module using a ground bonding lug. Use only UL Listed grounding lugs suitable for out­door use: Burndy P/N CL-50-DB or ILSCO P/N GBL-4DB in conjunction with an 8-32 stainless steel fastener and star washer. An uncoated copper lug is not acceptable for attachment to the aluminium frame.
Four grounding holes are provided on the inside of the module frame located in the middle of each of the four frame flanges. See Figure 3 for location of module grounding holes. See Figure 4 for installation of lug.
Note: The star washers are required for making a reliable electrical earth connection with the anodized aluminium frame as well as to prevent loosening of the screw over time.
To attach grounding lugs, use #8-32 (4mm) bolts and nuts, star washers, and lock washers that are provided for use with module ground points. The ground lug shall be installed from the bottom side of the frame using the paint cutting star washers, lock washer and bolt. Torque hex bolt to 50-70 in-lbs. This ground hardware can accommodate a 14AWG through 4AWG bare (stranded or solid) wire.
8/9
photovoltaikforum.com
Page 9
Solar Energy
Grounding wire
Figure 3: Grounding Hole Locations
Figure 4: Installation of the grounding lug
Use only UL Listed grounding lugs suitable for outdoor use: Burndy P/N CL-50-DB or ILSCO P/NGBL-4DBin conjunction with an 8-32 stainless steel fastener and star washer. Attach this lug to the module frame with a nut, bolt and star washer as shown in Figure 4.
Grounding Holes (4X)
Contact Information:
www.bosch-solarenergy.com solarenergy@us.bosch.com
9/9
photovoltaikforum.com
Loading...