Signalling Devices
AVENAR all-in-one 4000
Fire alarm planning guide –
Focus on EN 54-23
Introduction DIN EN 54-23
Since the introduction of DIN EN 54-23 for optical
signalling devices for fire alarm systems in all
European Union Member States on January
1st 2014 only authorized optical and opticalacoustical signalling devices are permitted. In
Germany this standard is valid since 2017,
based on the revised planning and design
standard, because the EN 54-23 standard is
a product and testing standard and not an
application standard.
The purpose of this brochure is to give a basic
knowledge regarding the planning of signalling
devices, with the example of AVENAR all-in-one
4000.
The standard DIN EN 54-23 assists planners
in planning and designing optical and opticalacoustical signalling devices (the acoustic part
is treated according to DIN EN54-3) in a building.
The standard defines how and in which quantity
signalling devices are needed in a technical
building planning.
The purpose of optical signalling devices is to alert persons in a
building or who are near to a building in case of fire, so that they
can protect themselves or be evacuated in time.
The following table shows the installation categories of
DINEN 54-23 described with letters C (ceiling mounting),
W (wall mounting) and O (open, for individual mounting).
These three categories are explained in the following chapters.
Furthermore, in the table below, you can find the main
requirements for DIN EN 54-23.
EN54-23
Categories Main requirements
C ceiling mounting
c-x-y
W wall mounting w-x-y
O individual mounting
defined by
manufacturer
Flash color:
red or white
Type:
A and B
Flash frequency:
0.5 to 2 Hz
Luminous intensity:
1cd at 70% of all measurements
and not over 500 cd
Product overview
AVENAR all-in-one 4000
(Unit-) base
Alarming part
(including battery)
Alarming Part
EN54-23: optical signalling, flasher ring
with 12 LEDs
EN54-3: acoustical part, 32 preprogrammed
tones with up to 97 db(A)
For easy (pre-) mounting and cabling
Detector base
Option for detector removal protection
Fits with detector or cover
Cover part
With detection, combination with
AVENAR detector 4000 series
Without detection, cover in red or
white color
Product type CTN Material color Flash color
Ceiling type FNX-425U-WFWH White White
Ceiling type FNX-425U-RFWH White Red
Wall type FNX-425U-WFRD Red White
Wall type FNX-425U-RFRD Red Red
Accessory battery pack FNX-425U-BAT N/A N/A
Accessory cover FNX-425U-COVRD Red N/A
Accessory cover FNX-425U-COVWH White N/A
Available tools for for AVENAR all-in-one 4000
Safety Systems Designer Remote Services