Bosch AVENAR User Manual

Signalling Devices
AVENAR all-in-one 4000
Fire alarm planning guide – Focus on EN 54-23
Introduction DIN EN 54-23
Since the introduction of DIN EN 54-23 for optical signalling devices for fire alarm systems in all European Union Member States on January 1st 2014 only authorized optical and optical­acoustical signalling devices are permitted. In Germany this standard is valid since 2017, based on the revised planning and design standard, because the EN 54-23 standard is a product and testing standard and not an application standard.
The purpose of this brochure is to give a basic knowledge regarding the planning of signalling devices, with the example of AVENAR all-in-one
4000.
The standard DIN EN 54-23 assists planners in planning and designing optical and optical­acoustical signalling devices (the acoustic part is treated according to DIN EN54-3) in a building. The standard defines how and in which quantity signalling devices are needed in a technical building planning.
The purpose of optical signalling devices is to alert persons in a building or who are near to a building in case of fire, so that they can protect themselves or be evacuated in time.
The following table shows the installation categories of DINEN 54-23 described with letters C (ceiling mounting), W (wall mounting) and O (open, for individual mounting). These three categories are explained in the following chapters. Furthermore, in the table below, you can find the main requirements for DIN EN 54-23.
EN54-23
Categories Main requirements
C ceiling mounting
c-x-y
W wall mounting w-x-y
O individual mounting
defined by manufacturer
Flash color:
red or white
Type:
A and B
Flash frequency:
0.5 to 2 Hz
Luminous intensity:
1cd at 70% of all measurements and not over 500 cd
Product overview AVENAR all-in-one 4000
(Unit-) base
Alarming part
(including battery)
Alarming Part
EN54-23: optical signalling, flasher ring with 12 LEDs EN54-3: acoustical part, 32 preprogrammed tones with up to 97 db(A)
For easy (pre-) mounting and cabling
Detector base
Option for detector removal protection
Fits with detector or cover
Cover part
With detection, combination with AVENAR detector 4000 series Without detection, cover in red or white color
Product type CTN Material color Flash color
Ceiling type FNX-425U-WFWH White White
Ceiling type FNX-425U-RFWH White Red
Wall type FNX-425U-WFRD Red White
Wall type FNX-425U-RFRD Red Red
Accessory battery pack FNX-425U-BAT N/A N/A
Accessory cover FNX-425U-COVRD Red N/A
Accessory cover FNX-425U-COVWH White N/A
Available tools for for AVENAR all-in-one 4000
Safety Systems Designer Remote Services