Bosch 520-HN-N, 520-HN-L User Instructions

520 HN
Flow Modulated with Hydro-generated Ignition Suitable for heating potable water only - Not approved for space heating purposes (Intended for variable flow applications with steady cold water inlet temperatures)
520-HN-N 520-HN-L
6 720 644 942 (2010/09) US
Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier. In the Commonwealth of Massachusetts this product must be installed by a licensed plumber or gas fitter.
Upon completion of the installation, these instructions should be handed to the user of the appliance for future reference.
What to do if you smell gas
• Close gas valve. Open windows.
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the fire department.
• Installation and service must be performed by a qualified installer, service agency or the gas supplier.
6 720 644 942
2
Index
Index
1 Warning 2
2 Appliance details 3
2.1 520 HN specifications (Technical data) 3
2.2 Unpacking the 520 HN heater 4
2.3 General rules to follow for safe operation 4
2.4 Dimensions and installation clearances 5
3 Installation instructions 6
3.1 Introduction 6
3.2 Proper location for installing your heater 6
3.3 Venting 6
3.4 Combustion air requirements 9
3.5 Mounting Heater 9
3.6 Gas piping & connections 11
3.7 Measuring gas pressure 13
3.8 Water connections 13
3.9 Recirculation application 14
4 Operation instructions 14
4.1 For your safety, read before operating your water heater 14
4.2 Lighting instructions 15
4.3 To turn off appliance 15
4.4 Adjusting the water temperature 15
4.5 Power adjustment knob 16
4.6 Draining the appliance 16
5 Maintenance and service 17
5.1 Maintenance intervals 17
5.2 Water valve 17
5.3 Pilot 17
5.4 Main burners 18
5.5 Vent assembly 18
5.6 Mineral scale build-up 18
6 Troubleshooting 19
6.1 Introduction 19
6.2 No spark at pilot with water flow 19
6.3 Spark appears when hot water is turned on, but pilot and burners will not ignite 19
6.4 Pilot lights, but burners will not come on. 20
6.5 Main burners go out during hot water use 20
6.6 Hot water temperature fluctuates at tap 21
6.7 Water is too hot 21
6.8 Water is not hot enough 22
6.9 Low hot water pressure 22
6.10 Noise when heater is running 22
6.11 Burners do not burn cleanly, yellow flames when operating 22
7 Protecting the environment 23
8 Interior components and diagram parts list 24
8.1 Interior components 24
8.2 Components diagram 25
8.3 Parts list 26
9 Fifteen Year Limited Warranty 27
1 Warning
Fig. 1
Warning: The heater must be isolated from the gas supply piping system during any pressure testing of that system at test pressures equal to or more than 0.5 psig.
Caution: Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
HOT
BURN
D A N G E R
Watertemperatureover125°Fcan causesevereburnsinstantlyor deathfromscalds.
Children,disabledandelderlyare athighestriskofbeingscalded.
Seeinstructionmanualbefore settingtemperatureatwater heater.
Feelwaterbeforebathingor showering.
6720608643-16.1AL
6 720 644 942
Appliance details
3
2 Appliance details
2.1 520 HN specifications (Technical data)
Approved in US/Canada
Capacity
520 HN: 4.36 GPM
Minimum input
520 HN: 30,735 Btu/hr
Maximum input
520 HN: 117 000 Btu/hr
Min. Output
520 HN: 23 906 Btu/hr
Maximum output
520 HN: 91 525 Btu/hr
Efficiency in %
Efficiency 80%
Gas Requirement
Gas connection - ¾” NPT
Inlet gas pressure under maximum operation:*
• Propane: 10.5” - 14” water column
• Natural Gas: 5.7” - 14” water column.
* To measure Gas Pressure, see Measuring Gas Pressure, chapter 3.7.
Venting
• Natural Draft
• Vent diameter - 5" or 6"
• Minimum height (feet) - 6’ with no elbows
• Vertical termination through roof or into chimney.
• Sidewall termination only with AQ4 power vent kit.
Water
• Hot water connection - ½” NPT
• Cold water connection - ½” NPT
• Water valve material: Fiberglass reinforced polymide
(PA)
• Minimum water flow to activate heater: 0.5 gallon/
minute (1.9 l/m)
• Minimum recommended water pressure: 30 PSI
(2.07 bar)
• Connections:
– Bottom of heater
• Temperature rises:
1)
– 45F rise @ 4.1 gpm – 50F rise @ 3.7 gpm – 55F rise @ 3.4 gpm – 65F rise @ 2.8 gpm – 77F rise @ 2.4 gpm – 90F rise @ 2.0 gpm
Dimensions
• Depth (in): 8.66” (220 mm)
• Width (in): 16.73” (425 mm)
• Height (in): 25.75” (655 mm)
• Weight: 35 pounds (16 kg).
Gas types
Natural Gas LP Gas
Safety devices
• Flame failure device (ionization flame rod)
• Pressure relief valve (Available as accessory)
• Overheat prevention (temperature limiter).
Water protection
IP X4.
Accessories (Bosch part #)
• Freeze prevention kit (7709003775)
2)
• Pressure relief valve (FWL-2).
1) Depending on gas pressure and altitude.
2) The freeze prevention kit is designed to provide protec­tion for the water heater down to approximately 5°F for short term conditions only. It will not protect the appli­ance in areas where the temperature is routinely expected to be below freezing.
- The freeze prevention kit will not protect plumbing out­side the appliance from freezing. Precautions should be taken.
6 720 644 942
4
Appliance details
2.2 Unpacking the 520 HN heater
Before installing the unit, be certain you have the correct heater for your type of Gas - Propane or Natural Gas. Identification labels are found on the
shipping box, and on the rating plate which is located on the right side panel of the cover.
B Installer must fill out checklist on back cover to
provide details in case service or warranty cov­erage is required.
Fig. 2 Rating plate
A Serial number B Type of gas
The box includes:
• Hot and cold water connection fittings
• Mounting screws
• Product registration card
• Installation manual
• Incandescent particle tray.
Do not lose this manual, there is a charge for a replacement.
Please complete and return the enclosed product registration card.
The 520 HN is not approved or designed for:
• Manufactured (mobile) homes, RV's or boats
• Heating or other recirculating/pumping applications*
• Solar/preheat backup or high temperature booster use
• Installation in bathroom, bedroom or other occupied rooms normally kept closed.
* This includes domestic hot water circulator pump loop systems that may be installed in home hot water system prior to installing this unit. An approved recirculation design can be found in chapter 3.9.
2.3 General rules to follow for safe operation
1. You must follow these instructions when you install
your heater. In the United States: The installation must conform with local codes or, in the absence of local codes, the National Fuel Gas Code ANSI Z223.1/ NFPA 54. In Canada: The Installation must conform with CGA B149.(1,2) INSTALLATION CODES and /or local installation codes.
2. Carefully plan where to install the heater. Proper
clearances must be followed.
3. The appliance must be isolated from the gas supply
piping system by closing its individual manual gas shutoff valve (not supplied with heater) during any pressure testing in excess of ½ Psig (3.5 kPa). The appliance and its gas connection must be leak tested before placing the appliance in operation.
4. Keep water heater area clear and free from
combustibles and flammable liquids. Do not locate the heater over any material which might burn.
5. Correct gas pressure is critical for the optimum
operation of this heater. Gas piping must be sized to provide the required pressure at the maximum output of the heater, while all the other gas appliances are in operation. Check with your local gas supplier, and see chapter 3.6 and 3.7 to verify proper gas line sizing.
6. Should overheating occur or the gas supply fail to
shut off, turn off the gas supply at the manual gas shut off valve, on the gas line. Note: manual gas shutoff valve is not supplied with the heater.
7. Do not use this appliance if any part has been
underwater. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been underwater.
i
BOSCH is constantly improving its products, therefore specifications are subject to change without prior notice.
6 720 644 942
Appliance details
5
2.4 Dimensions and installation clearances
Fig. 3 Dimensions in Inches and (mm)
4 Heat exchanger 5 Burner 10 Flow control knob 11 Water valve 20 Gas connection 23 Ignition unit 26 Power adjustment knob 34 LED indicator for burner status 35 On/Off switch 36 Front cover 37 Mounting holes 38 Exhaust pipe union 39 Draft diverter with flue gas sensor 40 Gas valve
Fig. 4 Minimum clearances
39
38
4
5
23
11
40
H
6720608036-01.2Av
8,66"(220)
E
F
G
4,92"(125)
D
2,50"
(63.5)
1,97"
(50)
3,82" (97)
A
B
37
10
26
35
34
20
36
C
Model 520 HN
TOP (A)
12 inches (306 mm)
FRONT (B)
4 inches (100 mm)
BACK
0 inches
SIDES
4 inches (100 mm)
BOTTOM (C)
12 inches (306 mm)
Dimensions inches (mm)
520 HN
A 16.73” (425)
B 25.75” (655)
C 13.15” (334)
D 5.11” (130)
E 21.25” (540)
F 2.55” (65)
G 1.18” (30)
H 3/4”
Table 1 Dimensions in inches (mm)
6 720 644 942
6
Installation instructions
3 Installation instructions
3.1 Introduction
Please follow these instructions. Failure to follow instructions may result in:
B Damage or injury. B Improper operation. B Loss of warranty.
If you are unable to perform the tasks required to install this heater properly, please contact a locally licensed plumber or gas technician. Please contact Bosch Water Heating with any questions.
3.2 Proper location for installing your heater
Carefully select the location of the water heater. For your safety and for proper heater operation, you must provide combustion air to the heater and a proper exhaust vent system. Follow the guidelines below:
B 1. Common installation practice is to determine the
venting system layout and penetration first, then work back to the heater.
B 2. Locate the heater where venting, gas and plumb-
ing connections are feasible and convenient.
B 3. The hot water lines should be kept short to save
energy. Centrally locating the water heater is best. It is always best to have hot water lines insulated.
3.3 Venting
B Minimum vent pipe diameter: 5 inches B Minimum vertical vent height: 6 feet, with no elbows B Establish 12 inch rise before any elbow
The heater must be vented to the outside following all local ordinances and specifications for installing a gas appliance vent or chimney. The heater must be located as close as practicable to a vertically rising chimney or vent that has a listed vent cap at its termination point. The venting system must be designed and constructed so as to develop a positive flow adequate to remove flue gasses to the outdoors. Consult the National Fuel Gas Code if the vent will have elbows or share venting with another natural draft appliance.
3.3.1 Horizontal venting
An AQ4 powervent, with a proof-of-draft safety interlock device, is required and is available for sidewall venting. Contact your dealer. In the Commonwealth of Massachusetts power vented applications must utilize proof-of-draft safety interlock device and comply with regulations established for all side wall horizontally vented gas fueled equipment.
3.3.2 Vertical venting
B A 5 inch diameter gas vent constructed of double
wall Type B gas vent is recommended. A 6 inch vent is required in elevations greater than 2000 feet, see Fig. 10. Under no circumstances must the vent pipe be reduced in size.
Warning: The water in this water heater is cold and always remains cold except for the times that hot water is being used. DO NOT INSTALL IN AN AREA WHERE IT COULD FREEZE. Drain the heater entirely if freezing temperatures are anticipated in area where heater is installed. See chapter
4.6 for draining instructions. To prevent any freeze damage, introduce short bursts of compressed air (20-40psi) through these connections to remove the residual water in the horizontal pipes and water valve.
Warning: Flammable materials, gasoline, pressurized containers, or any other items or articles that are potential fire hazards must NOT be placed on or adjacent to the heater. The appliance area must be kept free of all combustible materials, gasoline and other flammable vapors and liquids.
Warning: Place the heater in a location where water leaks will do NO DAMAGE to adjacent areas.
Danger: Do not reduce the vent pipe size. Do not put an elbow directly on top of heater. Failure to follow venting requirements may result in dangerous exhaust gases entering living space.
Warning: Do not combination vent with a power vented appliance.
Warning: Horizontally venting to a vertically constructed vent stack along an outside wall of a building is not permissible.
Warning: Horizontally venting to a sidewall vent terminator (without powervent) is not permissible.
6 720 644 942
Installation instructions
7
B An approved gas vent connector must be attached to
the top of the water heater and rise vertically at least 12" before entering into an approved gas vent connector elbow.
B The minimum vertical gas vent height allowed is 6
feet; horizontal vent connectors and elbows are not to be considered in the total gas vent height.
B All gas vent sections must be secured to each other
with sheet metal screws and be properly supported.
Horizontal runs:
Any gas vent section that is greater than 45 degrees from the vertical is considered horizontal. Horizontal sections must slope upwards at least ¼ inch for every foot of its horizontal length and be properly supported. Keep the horizontal section short and avoid too many elbows. The maximum horizontal run allowed is half of the total vertical vent height; horizontal vent connectors and elbows are not to be considered in the total gas vent height.
Vent termination:
The gas vent constructed of double wall Type B gas vent must terminate above the roof surface with a listed vent cap at a height that's in accordance with Fig. 7 and table 2, provided they are at least 8 feet (2.4 m) from a vertical wall or similar obstruction. All other gas vents that are not able to terminate within the minimum specified height allowed must terminate not less than 2 feet (0.6 m) above the highest point where it passes through the roof and at least 2 feet (0.6 m) higher than any vertical wall or similar obstruction within 10 feet (3.1 m).
Fig. 5 Flat roof
Fig. 6 Vent Adaptor for High Altitude Installations
Freeze prevention
In cold climates, components of a tankless water heater can freeze and burst from negative draft. A leading cause of negative draft is combustion appliances in the building not being supplied with sufficient combustion air. A wood stove or furnace can pull its combustion air from the water heater‘s vent pipe, allowing the cold incoming air to freeze the cold water in the heat exchanger. Supplying more combustion air for all com­bustion appliances is the solution. A HVAC specialist should be consulted to design solutions for providing more combustion air.
In cold climates where backdraft is a problem, the freeze prevention kit accessory (7709003775) should be installed.
LISTED VENT CAP
MINIMUM 6 FEET (1.8M)
LISTED GAS VENT
ESTABLISH A ONE
FOOT RISE BEFORE
ANY ELBOWS
5” X 6” ADAPTOR
USED AT HIGH
ALTITUDE
6 720 644 942
8
Installation instructions
Masonry chimney
Masonry chimneys shall be built and installed in accordance with NFPS 211 or local codes. A minimum 5" diameter gas vent pipe (metal double wall Type B), or an approved clay flue liner or a listed chimney lining system must be used when venting into a naturally drafting, internal masonry chimney. 6 inch is required in elevations greater than 2000 feet, see Fig. 6. Local codes may require the use of both gas vent and an approved lining system when venting into a masonry chimney. The Commonwealth of Massachusetts requires the use of a listed liner. Lining systems include approved clay flue lining, a listed chimney lining system or other approved material that will resist corrosion, erosion, softening, or cracking from exhaust flue gases at temperatures up to 1800 degrees F. The lining system must be listed for use with naturally drafting, draft hood equipped gas appliances. Follow local codes and refer to NFGC 54 and NFPA 58.
Existing interior masonry chimney
The metal gas vent pipe should be permanently mounted inside the masonry chimney. Double wall Type B gas vent is recommended. The masonry chimney may have to be tile or metal lined before the insertion of the gas vent pipe; check local codes for clarification. The lining material must be listed for use only with naturally drafting, draft hood equipped gas appliances. Follow manufacturer's instructions for installation of listed lining material. You may not vent any other fuel burning appliances into any free space remaining in the chimney. The minimum vertical gas vent length within the masonry chimney must be no less than 5 ft (1.5 m); the vent terminator must extend at least 3 feet (0.9 m) above where the chimney meets the roofline and at least 2 feet (0.6 m) higher than any vertical wall or similar obstruction within 10 feet (3.1 m). The top of the gas vent must have an approved vent terminator. See Fig. 8.
Fig. 7 Pitch roof
Fig. 8 Masonry chimney
APPROVED VENT CAP
LOWEST DISCHARGE OPENING
MINIMUM 6 FEET (1.8M)
X
12
ROOF
PITCH IS
X/12
LISTED GAS VENT
H (minimum) height
from roof to lowest discharge opening
ESTABLISH A ONE
FOOT RISE BEFORE
ANY ELBOWS
GAS VENT TERMINATIONS FOR LISTED VENT CAPS
Roof pitch H (minimum) feet meters
Flat to 6/12 1.0 0.30
6/12 to 7/12 1.25 0.38
Over 7/12 to 8/12 1.5 0.46
Over 8/12 to 9/12 2.0 0.61
Over 9/12 to 10/12 2.5 0.76
Over 10/12 to 11/12 3.25 0.99
Over 11/12 to 12/12 4.0 1.22
Over 12/12 to 14/12 5.0 1.52
Over 14/12 to 16/12 6.0 1.83
Over 16/12 to 18/12 7.0 2.13
Over 18/12 to 20/12 7.5 2.27
Over 20/12 to 21/12 8.0 2.44
Table 2
6720608032-14.1Av
GAS VENT
APPROVED VENT CAP
VENT CONNECTOR
Establish a one foot rise before any elbows
6 720 644 942
Installation instructions
9
3.4 Combustion air requirements
The Protankless water heater holds cold water in its copper heat exchanger and water valve when not in use. Because of this, any cold air that comes down through the unit's vent pipe is capable of freezing these components. This Installation Manual specifies the minimum vertical vent pipe and the amount of combustion air required for this unit. When all requirements are followed, the unit will operate properly and safely. However, there may still be a risk of freezing due to negative draft if all the combustion appliances in the structure are not being supplied with sufficient combustion air. A wood stove or furnace can pull it's combustion air from the Protankless vent pipe. This allows the cold infiltrating air to potentially freeze the cold water in the AquaStar heater. Damage from freezing is not covered under the manufacturer's warranty. Supplying more combustion air for all combustion appliances is the solution. Follow the instructions on venting and checking adequacy of combustion air. A HVAC specialist should be consulted to design solutions for providing more make-up air if necessary. Observe the following instructions concerning combustion air.
Appliances located in unconfined spaces: a) An unconfined space is one whose volume is greater
than 50 cubic feet per 1000 Btu per hour of the combined rating of all appliances installed in the space. That would be 5850 cubic feet for the Protankless 520 HN alone.
b) Installations in structures that have been tightly constructed (air infiltration rate of 0.40 ACH or less) must be provided with combustion air per the National Fuel Gas Code. Consult a HVAC specialist if your air infiltration rate is questionable.
Appliances located in confined spaces:
The confined space must be provided with two permanent openings, one commencing within 12 inches of the top and one commencing within 12 inches of the bottom of the enclosure. Each opening must have a minimum free area of one square inch per:
• 1000 Btu/hr if all air is taken from inside the building.
• 2000 Btu/hr if all air is taken from the outside by
horizontal ducts.
• 4000 Btu/hr if all air is taken from the outside by
direct openings or vertical ducts.
Or the confined space must be provided with one permanent opening or duct that is within 12 inches of the ceiling of the enclosure. This opening must have a minimum free area of one square inch per:
• 3000 Btu/hr if all air is taken from the outside by a
direct opening or vertical duct.
Louvers, grills and screens have a blocking effect. If the effective free area is not known, increase the sizes of
your openings by 400% if your louvers are wood and by 135% if your louvers are metal. Refer to the National Fuel Gas Code for complete information. In buildings of tight construction all air should be taken from outside.
3.5 Mounting Heater
The 520 HN is approved for installation on a combusti­ble wall provided the floor covering below the heater is noncombustible. For installations in an alcove or closet, maintain the minimum clearances to combustible and non-combustible materials listed in Fig. 4.
Remove cover and inspect.
B Remove the flow control and power adjustment
knobs.
B Unsrew the cover fixing screws, see Fig. 10. B Loosen the two Phillips head screws located on
bottom rear of cover. Remove cover by pulling it outward and then lifting upwards.
B Ensure that the flue terminal is clear. B After inspection, replace front cover and tighten
screws.
Install incandescent particle tray.
B Install incandenscent particle tray using screws
provided as shown in Fig. 9.
Fig. 9 Incandescent particle tray illustration
Warning: before starting installation:
B check that there are no loose parts
inside the appliance
B ensure that gas pipe, gas valve, and
burner have no damage and are properly fitted.
B Read chapter 2.2 to verify proper gas
type and to verify all parts are included in box.
i
Front cover must be removed in order to inspect components visually (see instructions below).
Incandescent particle tray
Screws
Loading...
+ 19 hidden pages