Isolating transformer
RKD 1600/2x115
Advantages
Minimum size at high power
Low weight
Dual input voltage for series or parallel connection
Minimal no-load losses
Outstanding temperature behaviour thanks to low magnetic leakage field
Very low noise field
Applications
As a mains transformer for adjustment of the voltage and simple electrical
isolation.
As an isolating transformer for the safe electrical isolation of the input and
output sides. The transformer may be used to set up protective separation as a
protective measure in accordance with VDE 0100.
As a safety isolating transformer for the safe electrical isolation of the input
and output sides. The transformer is suitable for creating SELV and PELV
circuits because of the limit on the output voltage.
Sample application
Picture shows RKD 60 2x12
Standards " Z
Isolating transformer
to: VDE 0570 Part2-4, DIN EN 61558-2-4, EN 61558-2-4, IEC 61558-2-4, UL
5085-1/-2, CSA 22.2 No.66
Approvals W Z
UL 5085-1/-2, CSA 22.2 No.66
Isolating transformer
RKD 1600/2x115
Type RKD 1600/2x115
Input
Rated input voltage
Rated frequency
Output
Rated output voltage
Rated Power
No-load voltage (app. x factor)
No-load loss (typ.)
Efficiency
Standards
Classification
Approvals
Approvals
Environment
Ambient temperature max.
Safety and protection
Type
Insulation class
Protection index
Safety class (prepared)
Short circuit strength
Test voltage
Order numbers
Order Number
2 x 115 Vac
50 - 60 Hz
2 x 115 Vac
1600 VA
1.02
9.60 W
97.0 %
Isolating transformer
cURus
40 °C
Open type
VDE=B, UL=class 105
IP 00
II
non-short-circuit proof
4000 Vac, 50 Hz
RKD 1600/2x115
Type RKD 1600/2x115
Terminal and mounting
Fixing method
Terminals
Measures and weights
Major diameter Ø
Outside diameter in the area of the wire lead Ø
Height without mounting
Weight
Remaining hole casting,
with integrated mounting holes
Connecting leads, 200 mm
202 mm
205 mm
105 mm
12.70 kg
Subject to change.