Block RKD15/2x12 Catalog Page

Safety isolating transformer
RKD 15/2x12
Advantages
Minimum size at high power
Low weight
Dual input voltage for series or parallel connection
Outstanding temperature behaviour thanks to low magnetic leakage field
Very low noise field
Applications
As a mains transformer for adjustment of the voltage and simple electrical isolation.
As an isolating transformer for the safe electrical isolation of the input and output sides. The transformer may be used to set up protective separation as a protective measure in accordance with VDE 0100.
As a safety isolating transformer for the safe electrical isolation of the input and output sides. The transformer is suitable for creating SELV and PELV circuits because of the limit on the output voltage.
Sample application
Picture shows RKD 60 2x12
Standards 2 Z
Safety isolating transformer to: VDE 0570 Part 2-6, DIN EN 61558-2-6, EN 61558-2-6, IEC 61558-2-6, UL 5085-1/-2, CSA 22.2 No.66
Approvals W Z
UL 5085-1/-2, CSA 22.2 No.66
Safety isolating transformer
+
-
30
RKD 15/2x12
Type RKD 15/2x12
Input
Rated input voltage Rated frequency
Output
Rated output voltage Rated Power No-load voltage (app. x factor) No-load loss (typ.) Efficiency
Standards
Classification
Approvals
Approvals
Environment
Ambient temperature max.
Safety and protection
Type Insulation class Protection index Safety class (prepared) Short circuit strength Test voltage
Order numbers
Order Number
2 x 115 Vac 50 - 60 Hz
2 x 12 Vac 15 VA
1.35
0.30 W
73.0 %
Safety isolating transformer
cURus
40 °C
Open type VDE=B, UL=class 105 IP 00 II non-short-circuit proof 4000 Vac, 50 Hz
RKD 15/2x12
Type RKD 15/2x12
Terminal and mounting
Fixing method Terminals
Measures and weights
Major diameter Ø Outside diameter in the area of the wire lead Ø Height without mounting Weight
Mounting kit, M4 bolt Connecting leads, 200 mm
58 mm 60 mm 27 mm
0.29 kg
Subject to change.