Die oben beschriebenen Produkte sind konform mit folgenden harmonisierten Normen:
The products described above are in conformity with the following harmonized standards:
Les produits décrits ci-dessus sont conformes aux normes harmonisées suivantes:
Sicherheit / safety / sécurité:
IEC/CEI 61010-1:2001 Sicherheitsbestimmungen für elektrische Mess-, Steuer-, Regel-
IEC/CEI 61010-2-010:2003 Sicherheitsbestimmungen für elektrische Meß-, Steuer-, Regel-
EMV / EMC / CEM:
IEC/CEI 61326:1997 + A1:1998 +
A2:2000
CE - DECLARATION DE CONFORMITE
BINDER GmbH
Im Mittleren Ösch 5, D-78532 Tuttlingen
Wärme-/Trockenschränke mit Programmregelung und forcierter
Umluft
Heating/drying ovens with program control and forced convection
Etuves universelles à régulation programmable et circulation d’air
forcée
und Laborgeräte – Teil 1: Allgemeine Anforderungen
Safety requirements for electrical equipment for measurement,
control, and laboratory use – Part 1: General requirements
Règles de sécurité pour appareils électriques de mesurage, de
régulation et de laboratoire – Partie 1 : Prescriptions générales
und Laborgeräte – Teil 2-010: Besondere Anforderungen an
Laborgeräte für das Erhitzen von Stoffen
Safety requirements for electrical equipment for measurement,
control, and laboratory use – Part 2-010: Particular requirements
for laboratory equipment for the heating of materials
Règles de sécurité pour appareils électriques de mesurage, de
régulation et de laboratoire. Partie 2-010 : Prescriptions
particulières pour appareils de laboratoire utilisés pour
l’échauffement des matières
Elektrische Betriebsmittel für Leittechnik und Laboreinsatz – EMVAnforderungen
Electrical equipment for measurement, control and laboratory use
– EMC requirements
Matériels électriques de mesure, de commande et de laboratoire
– Prescriptions relatives à la CEM
1 / 2
FP 01/2006 page 2/52
Die oben beschriebenen Produkte sind konform mit folgenden EG-Richtlinien:
The products described above are in conformity with the following EC guidelines:
Les produits décrits ci-dessus sont conformes aux directives CE suivantes:
Richtlinie 73/23/EWG des Rates vom 19. Februar 1973 zur
Angleichung der Rechtsvorschriften der Mitgliedstaaten betreffend
elektrische Betriebsmittel zur Verwendung innerhalb bestimmter
Spannungsgrenzen
Council Directive of 19 February 1973 on the harmonization of the
laws of Member States relating to electrical equipment designed
for use within certain voltage limits (73/23/EEC)
Directive 73/23/CEE du Conseil, du 19 février 1973, concernant le
rapprochement des législations des États membres relatives au
matériel électrique destiné à être employé dans certaines limites
de tension
EMV-Richtlinie
89/336/EWG, Änderung 93/68/EWG
EMC Directive
89/336/EEC, amended 93/68/EEC
Directive CEM
89/336/CEE, modifiée 93/68/CEE
Richtlinie 89/336/EWG des Rates vom 3. Mai 1989 zur
Angleichung der Rechtsvorschriften der Mitgliedstaaten über die
elektromagnetische Verträglichkeit
Council Directive 89/336/EEC of 3 May 1989 on the
approximation of the laws of the Member States relating to
electromagnetic compatibility
Directive 89/336/CEE du Conseil du 3 mai 1989 concernant le
rapprochement des législations des États membres relatives à la
compatibilité électromagnétique
Die oben beschriebenen Produkte tragen entsprechend die Kennzeichnung CE.
The products described above, corresponding to this, bear the CE-mark
Les produits décrits ci-dessus, en correspondance, portent l’indication CE.
D-78532 Tuttlingen, 10.01.2006
BINDER GmbH
P. M. Binder Dr.-Ing. V. Kek
Geschäftsführender Gesellschafter Leiter F & E
Managing Director Head of R & D
Directeur général Chef de service R&D
1.2 Structure of the safety instructions......................................................................................................6
1.3 Localization / position of safety labels at the unit................................................................................8
1.4 Type plate ...........................................................................................................................................9
1.5 General safety instructions on installing and operating the heating/drying oven FP........................10
1.6 Intended use .....................................................................................................................................11
3. UNIT DESCRIPTION ............................................................................................ 13
3.1 Unit overview.....................................................................................................................................14
3.2 Control panel.....................................................................................................................................15
6.1 Air change .........................................................................................................................................18
6.2 Settings at the RD3 program controller ............................................................................................19
6.3 General indications ...........................................................................................................................20
7. FIXED VALUE ENTRY MODE .............................................................................21
8. PROGRAM EDITOR............................................................................................. 22
8.1 Selecting between set-point ramp and set-point step.......................................................................22
8.2 Set-point entry for program operation...............................................................................................24
8.3 Program table template.....................................................................................................................28
8.4 Deleting a program section ...............................................................................................................29
9. PROGRAM START LEVEL.................................................................................. 30
10. USER LEVEL .......................................................................................................32
11. BEHAVIOR AT FAILURES ..................................................................................36
11.1 Behavior after power failure ..............................................................................................................36
15.3 Disposal of the unit............................................................................................................................44
For the proper operation of the heating/drying oven FP, it is necessary to read this operating manual
completely and carefully and to observe the given instructions.
1. Safety
This operating manual is part of the scope of delivery. Always keep it at hand.
To avoid injuries and damage observe the safety instructions of the operating manual.
WARNING
Failure to observe the safety instructions.
Serious injuries and unit damage.
Observe the safety instructions in this operating manual.
Carefully read the complete operating instructions of the heating/drying oven FP.
1.1 Legal considerations
This operating manual contains information necessary for the intended use, correct installation, start-up
and operation, and for the maintenance of the unit.
Understanding and observing the instructions in this operating manual are prerequisites for hazard-free
use and safety during operation and maintenance.
This operating manual cannot cover all conceivable applications. If you would like additional information,
or if special problems arise that you feel are not sufficiently addressed in this manual, please ask your
dealer or contact us directly.
Furthermore, we note that the contents of this operating manual are not part of an earlier or existing
agreement, promise, or legal relationship, nor do they modify such a relationship. All obligations on the
part of BINDER derive from the respective purchase contract, which also contains the entire and
exclusively valid statement of warranty administration. The statements in this manual neither augment nor
restrict the contractual warranty provisions.
1.2 Structure of the safety instructions
In this operating manual, the following harmonized denominations and symbols indicate dangerous
situations in accordance with ISO 3864-2 and ANSI Z535.4.
Signal word panel
Depending on seriousness and probability of the consequences, dangers are identified with a signal
word, the corresponding safety color, and if appropriate, the safety alert symbol.
DANGER
Indicates an imminently hazardous situation that, if not avoided, will result in death or serious
(irreversible) injury.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious
(irreversible) injury.
FP 01/2006 page 6/52
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in moderate or minor
(reversible) injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in damage of the product
and/or its functions or of a property in its ambiance.
Safety alert symbol
Use of the safety alert symbol indicates risk of injury.
Observe all measures that are marked with the safety alert symbol in order to avoid death or
injury.
Pictograms
Warning signs
Electrical hazard.
Hot surface
Tipover hazard
Mandatory action signs
Mandatory regulation
Read operating instructions
Pull the power plug
Explosive substances
Inhalation hazard
Pollution Hazard
Lift with several persons
Lift with mechanical assistance
Environment protection
Prohibition signs
Do NOT touch
FP 01/2006 page 7/52
Do NOT spray with water
Information to be observed in order to ensure optimum function of the product.
Word message panel structure
Type / cause of hazard.
Possible consequences.
∅ Instruction how to avoid the hazard: prohibition
Instruction how to avoid the hazard: mandatory action
Observe the other notes and information not specially emphasized in the same way, in order to avoid
disturbances which could result in direct or indirect injuries or property damage.
1.3 Localization / position of safety labels at the unit
Following labels are located on the unit:
Pictograms (Warning signs) Service label
Hot surface
Figure 1: Position of labels at the unit
Keep safety labels complete and legible.
FP 01/2006 page 8/52
A
1.4 Type plate
Figure 2: Position of type plate
Nenntemperatur 300°C 1,60 kW
572°F 230 V 1 N ~
Schutzart IP 20 7,0 A
Temp. Schutz DIN 12880 50/60 Hz
Klasse 2.0
rtikel-Nr. 9020-0227 US PATS 4585923 / 5222612 / 5309981
Figure 3: Type plate (example of FP 115 regular unit)
Indications of the type plate Information
Nenntemperatur 300°C
Nominal temperature
572°F
Schutzart IP 20 IP type of protection 20 acc. to EN 60529
Temp. Schutz DIN 12880 Temperature safety device acc. to standard DIN 12880
Klasse 2.0 Temperature safety device, class 2
Artikel-Nr. 9020-0227 Art. No. 9020-0227
Projekt-Nr. --- (Special application acc. to project no.)
1,60 kW Nominal power 1.60 kW
230 V 1 N ~
Nominal voltage 230 V ± 10%, single-phase unit 7,0 A Nominal current 7.0 Amp
50/60 Hz Mains frequency 50/60 Hz
FP 115 Model FP 115
# 00-00000 Serial No. 00-00000
FP 01/2006 page 9/52
1.5 General safety instructions on installing and operating the heating/drying
oven FP
With regard to operating the heating/drying oven FP and to the installation location, please observe the
regulations BGR 120 of the German professional association of the chemical industry (formerly ZH 1/119
laboratory guidelines of the employers’ liability insurance association) (for Germany).
The BINDER GmbH is responsible for safety-related unit properties only if skilled electricians or qualified
personnel authorized by BINDER perform all maintenance and repair, and if components relating to
chamber safety are replaced in case of failure with original spare parts.
To operate the unit, use only original BINDER accessories or accessories of third-party suppliers
authorized by BINDER. The user is responsible for any risk when using unauthorized accessories.
CAUTION
Danger of overheating.
Damage of the unit.
∅ Do not install the unit in unventilated recesses.
Ensure sufficient ventilation for carrying-off the heat.
The heating/drying oven FP must NOT be operated in hazardous locations.
DANGER
Explosion hazard.
Danger of life.
∅ Do NOT operate the unit in potentially explosive areas.
∅ NO explosive dust or air-solvent mixture in the ambiance.
The heating/drying oven FP does not dispose of any measures of explosion protection.
DANGER
Explosion hazard.
Danger of life.
∅ Do NOT introduce any substance combustible or explosive at working temperature into
the heating/drying oven.
∅ NO explosive dust or air-solvent mixture in the inner chamber.
Any solvent contained in the charging material must not be explosive or inflammable. I.e., irrespective of
the solvent concentration in the steam room, NO explosive mixture with air will form. The temperature
inside the chamber must lie below the flash point or below the sublimation point of the charging material.
Keep informed about the physical and chemical properties of the charging material, as well as the
contained moisture constituent and its behavior under addition of heat energy.
Keep informed about any potential health risks caused by the charging material, the contained moisture
constituent or by reaction products which may arise during the temperature process. Take adequate
measures to exclude such risks prior to putting the heating/drying oven into operation.
FP 01/2006 page 10/52
DANGER
Electrical hazard.
Danger of life.
∅ The unit must NOT become wet during operation or maintenance.
The heating/drying ovens have been produced in accordance to the VDE regulations and were routinely
tested in accordance to VDE 0411.
CAUTION
The inner chamber, the outgoing air pipe, the door window (option) and the access
ports will become hot during operation.
Danger of burning.
∅ Do NOT touch the inner surfaces, the outgoing air pipe, the door window, the access
ports, and the charging material during operation.
1.6 Intended use
Heating/drying ovens FP are suitable for drying and heat treatment of solid or pulverized charging
material, as well as bulk material, using the supply of heat. The ovens are suitable for harmless charging
material. A mixture of any component of the charging material with air must NOT be explosive. The
operating temperature must lie below the flash point or below the sublimation point of the charging
material.
Other applications are not approved.
Do NOT use the unit for drying purpose, especially if greater quantities of steam leading to condensation
will be set free.
Due to the special demands of the Medical Device Directive (MDD), these ovens are not
qualified for sterilization of medical devices as defined by the directive 93/42/EWG.
Respecting the instructions in this operating manual and conducting regular maintenance
work (chap. 14.1) is part of the intended use.
FP 01/2006 page 11/52
2. Warranty
BINDER products are manufactured with great care and checked carefully prior to delivery (VDE-piece
checked).
1. Should your BINDER product have a material defect or manufacturing fault, we shall repair it – as long
as it is a new BINDER product – free of charge if the defect or fault occurs within 12 months after
delivery. This period will be extended to 24 months, starting from delivery, provided that all
maintenance and potential repair work within the first 12 months is carried out by us or authorized
service stations.
2. Should you discover a defect or fault in your BINDER product within the aforementioned period,
please inform the company from which you purchased the BINDER product or BINDER directly.
3. All above-mentioned periods or deadlines shall begin with the delivery of a new BINDER product to
the end buyer. Producing the invoice or delivery note shall bring evidence of deadline keeping.
4. In case a BINDER product has a defect or fault, we shall either replace the defective product with a
new one or repair the defective product at our discretion (so called supplementary performance –
“Nacherfüllung”). All parts replaced in the course of such repair shall become our property. Deadlines
mentioned under above number 1 shall not be prolonged by repair work or substitution. In case
supplementary performance should fail, usual warranty rights according to German Law (withdrawal
from contract or price reduction) shall apply, provided the defect or fault occurs within the first 12
months. Should the 24 month-period be relevant and supplementary performance fail, you shall only
be entitled to a price reduction.
5. Should the defect occur within 12 months after delivery, we shall take over all costs necessary for the
repair of the defect, especially transportation, travel and labor costs, in so far as there is no cost
increase due to the product being brought to another location than the place of delivery. However, we
shall decide whether the defect will be repaired at the location where the BINDER product is operating
or whether the BINDER product has to be sent to us. In case the 24 month-period should be relevant,
please send the defective BINDER product at your expense to BINDER or the company from which
you purchased the BINDER product. We shall repair the BINDER product at your premises only if
transportation costs are excessively high. The customer shall be liable for any risk of sudden
destruction or deterioration.
6. Should you have to send back a BINDER product, the BINDER product will have to be supplied in its
original packaging or any similar suitable packaging.
7. All warranty claims as laid down in this document basically become invalid:
• if the defect or fault is caused by repair or intervention by non-authorized persons. With
authorized persons, we mean only Binder service engineers and service engineers of our service
partners.
•the same applies if you have attached non-suitable parts or accessories to the BINDER products,
which are not original BINDER spare parts, and if those parts or accessories have caused the
defect or fault.
•parts that become used due to natural wear and tear, e.g. door seals, lamps, lights (enumeration
not exhaustive)
• defects caused by external intervention like e.g. fall or blow
• defects arising from non-compliance with operating instructions, improper use, abnormal ambient
conditions, overload or absence of care/maintenance
• in the case of devices that were converted or redesigned by non-authorized third parties
• in case of minor deviations from the set quality that are irrelevant to the value and usability of the
device
8. All rights or claims beyond the ones described above, especially concerning the right of compensation
for potential damages which might be caused by BINDER products shall be excluded provided that
such exclusion is not prohibited by governing law.
FP 01/2006 page 12/52
9. Should you send a BINDER product to us for repair or any other reasons, we shall only accept the
BINDER product upon presentation of a so-called authorization number that has previously been
issued to you. We shall issue the authorization number after receiving your complaint in writing or via
telephone prior to your sending (back) the BINDER product to us. The authorization number will be
issued following the receipt of the information mentioned below:
• BINDER product type and serial number
• Date of purchase
• Name and address of the dealer from which you bought the BINDER product
• Exact description of defect or fault
• Your full address; if possible contact person and availability of that person
• Exact location of the BINDER product
• Contamination clearance certificate via fax in advance!
The authorization number needs to be applied to the packaging in such a way that it can be easily
recognized or be recorded clearly in the delivery documents. For security reasons we cannot accept
your delivery if it does not carry an authorization number!
IMPORTANT NOTICE:
Any warranty repair maintenance or service work may only be carried out by persons or companies being
properly authorized by us. If you do not know an authorized service station, please contact us and we will
name you our service partner closest to you. Otherwise, we will carry out the necessary work ourselves.
Date: November 2003
3. Unit description
BINDER heating/drying ovens with forced convection FP are equipped with the electronic program
controller RD3 with digital display. This allows programming of temperature cycles and an individual fan
speed setting for each program section.
The APT.line
precision, thanks to the direct and distributed air circulation into the interior.
The air turbine supports exact attainment and maintenance of the desired temperature accuracy. The fan
speed is digitally adjustable from 0 % to 100%.
All unit functions are easy and comfortable to use thanks to their clear arrangement. Major features are
easy cleaning of all unit parts and avoidance of undesired contamination.
The inner chamber, the pre-heating chamber and the inside of the doors are all made of stainless steal
(material no. 1.4301 in Germany). The housing is RAL 7035powder-coated. All corners and edges are
completely coated.
The heating/drying oven FP is regularly equipped with a serial interface RS 422 for computer
communication, e.g. via the communication software APT-COM
13.1). For further options, see chap. 16.5.
®
preheating chamber system guarantees high level of spatial and time-based temperature
®
3 DataControlSystem (option, chap.
The model FP 720 is equipped with
four castors.Bothfrontcastorscan belocked by brakes.
The units can be operated in a temperature range of 5°C above ambient temperature up to +300°C.
FP 01/2006 page 13/52
3.1 Unit overview
Figure 4: Heating/drying oven FP (example: model FP 53)
(1) Main switch on/Off
(2) Safety device class 2 or class 3.1 (option)
(3) Program controller RD3
(4) Lever for ventilation slide
(5) Door handle
FP 01/2006 page 14/52
3.2 Control panel
(3) (2) (1)
Figure 5: Control panel of standard unit
(1) Main on/off switch
(2) Safety device class 2
(3) Program controller RD3
4. Scope of delivery, transportation, storage, and installation
4.1 Unpacking, and checking equipment and scope of delivery
After having unpacked, please check the unit and its optional accessories, if any, based on the delivery
note for completeness and for transportation damage. If transportation damage has occurred,
immediately inform the carrier.
Please remove any transportation protection devices and adhesives in / on the unit and at the doors and
take out the operating manuals and accessory equipment.
CAUTION
Sliding or tilting of the unit.
Damage of the unit.
∅ Do NOT lift or transport the unit using either the door handle or the door.
∅ Do NOT lift units 400 and 720 by hand.
Lift units 53, 115, and 240 near the 4 unit feet from the pallet by aid of 4 persons.
∅ Lift units 400 and 720 using technical devices (fork lifter) from the pallet. Set the fork
lifter only from the rear in the middle of the unit. Make sure to place all the lateral
supports of the unit on the forks.
If necessary to send back the unit, please use the original packing and respect the advice for safe lifting
and transportation (chap. 4.2).
For disposal of the transport packing, see chap. 15.1.
FP 01/2006 page 15/52
4.2 Advice for safe lifting and transportation
The front castorsof units 720 can be blocked by brakes. Respect the advice for temporal
decommissioning (chap. 15.2).
CAUTION
Sliding or tilting of the unit.
Damage of the unit.
Transport the unit only in its original packaging.
Secure the unit with transport straps for transport.
∅ Do NOT lift or transport the unit using either the door handle or the door.
∅ Do NOT lift units 400 and 720 by hand.
Lift units size 53, 115, and 240 near the 4 unit feet by aid of 4 persons and place it on
a transport pallet with wheels. Push the pallet to the desired site and then lift the unit
near the 4 unit feet from the pallet.
Place units size 400 and 720 using technical devices (fork lifter) on the transport
pallet. Set the fork lifter only from the rear in the middle of the unit. Make sure to place
all the lateral supports of the unit on the forks.
∅ Transport units size 400 and 720 ONLY with the original transport pallet. Set the fork
lifter only to the pallet. Without the pallet the unit is in imminent danger of overturning.
• Permissible ambient temperature range: -10°C to +60°C.
You can order transport packing and pallets for transport purpose at the BINDER Service.
4.3 Storage
Intermediate storage of the unit is possible in a closed and dry room. Respect the advice for temporal
decommissioning (chap. 15.2).
• Permissible ambient temperature range: -10°C to +60°C.
If following storage in a cold location the unit is transferred to the installation site for start-up,
condensation is possible. Wait at least one hour until the chamber has attained ambient temperature and
is completely dry.
4.4 Location of installation and ambient conditions
Set up the heating/drying oven FP on a plane and non-flammable surface, free from vibration at a wellventilated, dry location and align it using a spirit level. The site of installation must be capable of
supporting the unit’s weight (see technical data, chap. 16.4).
CAUTION
Danger of overheating.
Damage of the unit.
∅ Do NOT set up units in non-ventilated recesses.
Ensure sufficient ventilation for carrying-off the heat.
FP 01/2006 page 16/52
• Permissible ambient temperature range: +18°C to +40°C. At elevated ambient temperature values,
fluctuations in temperature can occur.
The ambient temperature should not be substantially higher than the indicated ambient
temperature of +25°C to which the specified technical data relate. In the case of different
ambient conditions, deviations from the indicated data are possible.
• Installation height: max. 2000 m above sea level.
When placing several units of the same size side by side, maintain a minimum distance of 250 mm
between each unit. Wall distances: rear 100 mm, sides 160 mm.
Two devices up to size 115l can be piled on top of each other. For this purpose, place rubber pads under
all four feet of the upper unit to prevent the device from slipping.
CAUTION
Sliding or tilting of the upper unit.
Damage of the units.
∅ When stacking, place rubber pads under all four feet of the upper unit.
The unit must NOT be installed and operated in hazardous locations.
DANGER
Explosion hazard.
Danger of life.
∅ Do NOT operate the unit in potentially explosive areas.
∅ NO explosive dust or air-solvent mixture in the ambiance.
5. Installation of the equipment
5.1 Electrical connection
•FP 53, FP 115, FP 240:
Shockproof plug, mains voltage 230 V (1N~) +/- 10 %, 50/60 Hz
Fixed mains connection cable of 1800 mm in length
•FP 400, FP 720:
CEE plug 5 poles, mains voltage 400 V (3N~) +/- 10 %, 50/60 Hz
Fixed mains connection cable of 2700 mm in length
•FP 53-UL, FP 115-UL:
NEMA plug 5-20P, mains voltage 115 V (1N~) +/- 10 %, 60 Hz
Fixed mains connection cable of 1800 mm in length
•FP 240-UL, FP 400-UL, FP 720-UL:
NEMA plug L21-20P, mains voltage 208 V (3N~) +/- 10 %, 60 Hz
Fixed mains connection cable of 2700 mm in length
FP 01/2006 page 17/52
• Prior to connection and start-up, check the mains voltage. Compare the values to the data specified
on the type plate of the unit (unit front behind the door, bottom left-hand, chap. 1.4).
• When connecting, please observe the regulations specified by the local electricity supply company
and as well as the VDE directives (for Germany)
• Pollution degree (acc. to IEC 1010-1): 2
• Over-voltage category (acc. to IEC 1010-1): II
CAUTION
Danger of incorrect mains voltage.
Damage of the equipment.
Check the mains voltage before connection and start-up.
Compare the mains voltage to the data indicated on the type plate.
See also electrical data (chap. 16.4).
5.2 Connection to a suction plant (optional)
When directly connecting a suction plant the spatial temperature exactitude, the heating-up and the
recovering times and the maximum temperature will be negatively influenced. So no suction plant should
be directly connected to the outgoing air pipe.
Active suction from the oven must only be effected together with extraneous air. Perforate the
connecting piece to the suction device or place an exhaust funnel at some distance to the
outgoing air pipe.
CAUTION
The exhaust duct will become hot during operation.
Danger of burning.
∅ Do NOT touch the exhaust duct during operation.
6. Start up
Having connected the electrical supply (chap. 5.1), switch on the unit by the main switch (1).
6.1 Air change
Opening the air flap in the outgoing air pipe serves to adjust the air change.
Without connecting a suction plant:
• If the air flap is open and the fan is operating, fresh air comes in via aeration gaps.
• If the air flap is completely open, the spatial temperature accuracy can be negatively influenced.
FP 01/2006 page 18/52
6.2 Settings at the RD3 program controller
After turning the unit on with the main switch (1) the controller is in Normal Display / fixed value operation
mode.
Depending on the temperature value entered before LED (3a) is lit if the heating is active, or no LED if the
actual temperature equals the set-point.
In Display 1 of the controller the actual temperature value is displayed.
In Display 2 of the controller the temperature set-point is displayed.
Display 1
Display 2
Figure 6: RD3 program controller
LED function indications and their signification:
(3a) (yellow) Heating active
(3b) (yellow)
(3c) (yellow)
(3d) (green)
No function
No function
Illuminates: program operation
Flashes: program interruption due to exceeding of the tolerance limits
The program controller RD3 allows programming of temperature cycles. For each program section also
the fan speed can be regulated.
Two programs with up to 10 sections each or one program with up to 20 sections can be entered (setting
in the user level, chap. 10).
When changing from 2 programs to 1 program or vice-versa, existing programs are deleted
The maximum length of an individual program section can be set to either 99 hs 59 min or to 999 hs 59
min (setting in the user level, chap. 10). This setting is then valid for all program sections.
Programming can be done directly via the controller keyboard or graphically at the computer using the
software APT-COM
®
3 DataControlSystem (option, chap. 13.1) specially developed by BINDER.
FP 01/2006 page 19/52
6.3 General indications
The program controller RD3 offers several functional levels:
Normal Display / fixed value operation:
•Display of the actual value of temperature (display 1) and of the actual temperature set-point (display
2).
•The chamber is in fixed value operating mode, adjusting to the entered set-points.
Fixed value entry mode (chap. 7)
•Entry of set-points for temperature and fan speed in fixed value operating mode
Program editor (chap. 8)
• Two programs with up to 10 sections each or one program with up to 20 sections can be entered.
Entry of set-points for temperature and fan speed in all program sections (chap. 8.2).
•Deleting a program section (chap. 8.4)
Program start level (chap. 9)
• Selection of an entered program
• Entry of settings affecting the program course, as start delay time or number of program cycles
• Program start
User level (chap. 10)
•User specific controller settings
Normal Display / Fixed value operation
Fixed value entry mode
If no button is touched during more than 120 sec. the controller returns from the actual level to Normal
Display.
Program editor
User level
5 seconds
5 seconds
Program start level
FP 01/2006 page 20/52
7. Fixed value entry mode
Basic entry principle: Call up the individual parameters with button X/W one after the other. Enter the
values with the arrow keys. A value flashing once after 2 seconds indicates that it has been taken over to
the controller.
Normal Display
Hit key
Display 1 shows e.g. 20.0 (actual temperature set-point)
Display 2 shows SP TEMPERATURE (variable: temperature in °C)
Enter temperature set-point in °C with arrow
keys
Hit key
Display 1 shows e.g. 100 (actual fan speed set-point)
Display 2 shows SP FAN SPEED (variable: fan speed in %)
Enter fan speed set-point in % with arrow
keys
Hit key
Only with option zero-voltage relay outputs via operation lines (chap 13.6):
Display 1 shows e.g. 000 (actual switching state of operation lines)
Display 2 shows OPERATION LINE (variable: switching state of operation lines)
Enter switching state with arrow keys
Hit key
If no button is hit for more than 120 sec, or if the EXIT button is hit, the controller changes to Normal
Display.
Value is displayed in display 1.
Value is displayed in display 1.
When changing the set-point, check the setting of the safety device (chap. 10).
If the fan is operated with less than 100 % speed, the temperature performance and the
spatial exactitude of the temperature can differ from the manufacturer’s specifications. Do
reduce the fan speed only if absolutely necessary due to special requirements.
The values entered in fixed-value entry mode remain valid after program run-off and are then
equilibrated.
FP 01/2006 page 21/52
t
8. Program editor
8.1 Selecting between set-point ramp and set-point step
Set-points always refer to the start of a program section, i.e., at the beginning of each program section,
the entered set-point will be reached. During program section operation, the temperature gradually
passes to the set-point entered for the following program section.
By appropriate design of the program section timing, all kinds of temperature transitions can be
programmed:
•Gradual temperature changes “set-point ramp“
The set-point gradually moves from one set-point to the one of the following program section during a
given interval. The actual temperature value (X) follows the continually moving set-point (W) at any
moment.
•Program sections with constant temperature
The initial values of two subsequent program sections are identical; therefore the temperature is kept
constant during the whole time of the first program section.
•Sudden temperature changes “set-point step”
Steps are temperature changes (ramps) that occur during a very short interval. Two program sections
with an identical set-point are followed by a section with a different set-point. If the duration of this
transitional program section is very short (minimum entry 1 min), the temperature change will
proceed rapidly in the possible minimum time.
* Only with option zero-voltage relay outputs via operation lines, see chap 13.6.
The values of such a program table can now be entered to the RD3 program controller (chap. 8.2).
Advice for the programming of the different temperature transitions
The end point of the desired cycle must be programmed with an additional section (in our examples S05
for set-point ramp and S08 for set-point step) with a section time of at least one minute. Otherwise the
program will stop one section too early because the program line is incomplete.
If the tolerance limits set in the user level (chap. 10) are exceeded, the program is halted until the actual
temperature value is again situated in the tolerance range. During this program interruption the LED (3d)
flashes. Therefore, the duration of the program might be extended due to the programming of tolerances
The programming is conserved even in case of power failure or after switching off the unit.
8.2 Set-point entry for program operation
From Normal Display the program editor is accessed by hitting button X/W for 5 sec. Here the set-points
are entered one after the other in all program sections of a selected program.
Two programs with up to 10 sections each or one program with up to 20 sections can be entered (setting
in the user level, chap. 10).
In order to avoid incorrect programming the values of the program course should be entered into a table
(template in chap. 8.3).
* Only with option zero-voltage relay outputs via operation lines, see chap 13.6.
Temperature set-
point
[°C]
TEMP
Section length
[hh.mm]
TIME
Fan speed
[%]
FAN
Operation lines *
O.LINE
The values of a program section are kept constant during the section length.
The values of the program table can now be entered to the RD3 program controller.
FP 01/2006 page 24/52
Step 1
– Selecting the program and the program section:
Normal Display
Press down key
for 5 sec.
Display 1 shows e.g. 0000
Display 2 shows PROGRAM EDITOR (you are in the program editor)
e.g. 0001
(basic setting, adjustable in the user level,
chap. 10).
Value is displayed in both displays.
Automatically forward after 2 sec.
Display 1 shows e.g. 01 (program P01 selected)
alternating
--- : --- PRG. (program can be selected) Display 2 shows
CONTINUE X/W (information: to 1
st
program section with X/W)
Select program P01 or P02 with arrow keysValue is displayed in display 1.
Hit key
In the selected program P01 or P02, program sections can be selected:
Display 1 shows e.g. 01 (section S01 selected)
alternating
P01: --- SEC. Display 2 shows
CONTINUE X/W
enter new set-points for the individual variables with button
section S01 has already been created.
X/W
or:
Display 1 shows e.g. 01 (section S01 selected)
P01: --- SEC. Display 2 shows
alternating
NEW SEC. X/W
Select sections S01 to S10 or to S20 with
enter set-points for the individual variables with button X/W
section S01 has not yet been created.
arrow keys
If no program section has been entered yet the display switches back to 01 with all entries > 01, because
all sections have to be entered one after, and each new section is created as NEWSEC.
If e.g. already three program sections have been entered, the next section to be entered is S04. Before
this, no section > S04 can be selected.
FP 01/2006 page 25/52
Next step – entry of set-points in the desired program sections:
Basic entry principle: The parameters of individual program sections are called up with button X/W one
after the other. The values of the individual parameters can be entered with the arrow keys. A value
flashes once after 2 seconds thus indicating that it has been taken over to the controller. If several
parameters are to be skipped (e.g. in order to change a parameter in a posterior program section), the
parameters can be rapidly jumped over by holding pressed down the X/W key. If no button is hit during
more than 120 sec the controller switches back to Normal Display. The program entered so far remains
saved.
Display 1 shows e.g. 40.0
Hit key
C
(actual temperature set-point)
S01: TEMP 40.0 (variable: temperature in °C) Display 2 shows
alternating
CONTINUE X/W (information: go on with X/W)
Enter temperature set-point of S01 in °C
with arrow keys
Hit key
Display 1 shows e.g. 00.30 (actual section length set-point)
S01: TIME 00:30 (variable: section length in hh:mm) Display 2 shows
alternating
CONTINUE X/W (information: go on with X/W)
Enter section length set-point of S01 in
Value is displayed in both displays.
hh.mm with arrow keys
Hit key
Display 1 shows e.g. 50 (actual fan speed set-point)
S01:FAN 50 (variable: fan speed in %) Display 2 shows
alternating
Enter fan speed set-point of S01 in % with
CONTINUE X/W (information: go on with X/W)
Value is displayed in both displays.
arrow keys
Hit key
Only with option zero-voltage relay outputs via operation lines (chap 13.6):
Display 1 shows e.g. 000 (actually set switching state)
enter new set-points for the individual parameters with X/W.
enter set-points for the individual parameters with X/W
Section S02 has already been created.
or:
Section S02 has not yet been created.
Select the next section to be entered with
arrow keys
Display 1 shows e.g. 60.0C (actual temperature set-point)
S02:TEMP 60.0 (variable: temperature in °C) Display 2 shows
alternating
Enter the temperature set-point of S02 in °C
If all sections up to S10 or up to S20 have been programmed follows again section S01. In order to quit
the entry mode hit several times the EXIT button or wait 120 sec → the controller returns to Normal
Display.
When changing the set-point, check the setting of the safety device (chap. 10).
If the fan is operated with less than 100 % speed, the temperature performance and the
spatial exactitude of the temperature can differ from the manufacturer’s specifications. The fan
speed rate should only be reduced if absolutely necessary to meet special requirements.
CONTINUE X/W (information: go on with X/W)
with arrow keys
Etc.
FP 01/2006 page 27/52
8.3 Program table template
Program editor
Program title
Project
Program No.
Date:
Section
SEC
S01
S02
S03
S04
S05
S06
S07
Temperature
set-point
[°C]
TEMP
Section length
[hh.mm]
TIME
Fan speed
[%]
FAN
Operation lines *
O.LINE
S08
S09
S10
S11
S12
S13
S14
S15
S16
S17
S18
S19
S20
* Only with option zero-voltage relay outputs via operation lines, see chap 13.6.
At the standard device the operation lines (O.LINE) are without any function.
FP 01/2006 page 28/52
8.4 Deleting a program section
A program section is deleted from the program by setting the section duration to Zero.
Normal display
Press down Hit key
for 5 sec.
Display 1 shows e.g. 0000
Display 2 shows PROGRAM EDITOR (you are in the program editor)
DELETE SEC. X/W (information: delete section with X/W)
Hit key
FP 01/2006 page 29/52
The following section (in our example now S03) is displayed:
Display 1 shows e.g. 03 (actually selected section: S03)
P01:S03 (program section can be selected) Display 2 shows
alternating
If you delete a program section which is followed by further sections, those following move up
to the place of the deleted section.
In our example section S03 has been deleted. Sections S04, S05, etc., in case they have been
programmed earlier, will now receive the preceding sections numbers, i.e., S04 is now called S03 etc.
It is thus not possible to temporarily inactivate a program section, but deletion leads to overwriting the
section by the following one. To enter a section later to a program also the sections following the new one
must be entered again.
CONTINUE X/W (information: set-point entry with X/W)
Hit keyEXIT or wait 120 sec
Controller returns to Normal Display
9. Program start level
In a first step a program is selected. This on condition that a program has been entered previously (chap.
8.2) and that program type “2 programs with 10 sections each” has been selected in the user level (chap.
10).
Then the settings for the program course are defined. Two parameters can be set:
•Program delay time, i.e. a defined time before program start. It can be entered with precision of 1 min
and is max. 99.59 (99 hs 59 min). If the value is 00.00 the program is started without any delay.
• Number of program cycles, i.e. the desired number of program repeats. Values from 1 to 99 can be
entered. If the program is not to be repeated, enter value 0. For infinite repeats enter value –1. The
program is repeated as a whole, it is not possible to repeat individual sections.
In a last step the selected program is started. These steps must be carried out subsequently.
Step 1 – Program selection (only with program type “2 programs” set):
Normal Display
Hit program key
Display 1 shows e.g. 1 (actually selected program)
Display 2 shows SEL.PRG. (select program 1 or 2)
Enter program number 1 or 2 with arrow
keys
Value is displayed in display 1.
FP 01/2006 page 30/52
Next step–entry of program course settings
Hit program key
Display 1 shows e.g. 00.00 (entered delay time hh.mm)
Display 2 shows RUN TIME (enter delay time of program start)
Set delay time in hh.mm with arrow keysValue is displayed in display 1.
Hit program key
Display 1 shows e.g. -1 (actually selected number of program cycles)
Display 2 shows REPEAT (enter number of program cycles)
Select number of cycles -1, 0, 1 etc. with
Value is displayed in display 1.
arrow keys
Last step – program start:
Hit program key
Display 1 shows e.g. 1 (selected program)
Display 2 shows RUN PRG. (Question: start selected program?)
Hit program key
Display 1 shows e.g. 25.5C actual temperature value
Display 2 shows P01:S01 00:29:39
(actual program P01, actual section S01, and remaining
(time running backwards)
time of program section S01)
Program is running. The green LED (3d) lights up.
Additionally to the green LED (3d) indicating a running program LED (3a) is lit if the heating is active, or
no LED if the actual temperature equals the set-point.
During program course the arrow keys and the EXIT button are not functional.
By hitting the program key the program course can be terminated.
If during program course button is hit, the entered set-points of the actually running program section
are shown one after the other for 5 sec. each:
Display 1 shows e.g. 65.5
C
(actual temperature value)
Display 2 shows P01:S03 00:47:12 (actual program P01, actual section S03, and remaining time of
program section S03)
Hit key
Display 1 shows e.g. 90 (actual temperature set-point)
Display 2 shows SP TEMPERATURE
5 seconds
Display 1 shows e.g. 100 (actual fan speed setting)
Display 2 shows SP FAN SPEED
5 seconds
Only with option zero-voltage relay outputs via operation lines:
Display 1 shows e.g. 000 (actual operating contact setting)
Display 2 shows OPERATION LINE
FP 01/2006 page 31/52
After program runoff (and, if appropriate, of the program repeats) the controller returns to fixed value
operation showing Normal Display and adjusting to the temperature and fan speed values that have been
previously entered in the fixed value entry mode.
10. User level
In this menu the following parameters can be se (in brackets the corresponding abbreviated information
given in display 2):
•Unit address (Adress)
Setting of controller address (1 to 255) for operation with the communication software APT-COM
•User code (User-cod)
Modification of the user code setting (factory setting 0001) for access to the user level and the
program editor.
Keep in mind any modification of the user code. There is no access to these levels
without a valid user code.
•Decimal point position (Decimal)
®
.
Selection if integer values or one position after the decimal point can be entered. The integer
representation is displayed in Display 2 (set-point entry) while the actual value in Display 1 is always
displayed with one decimal point.
•Buzzer (Buzzer)
Inactive: no acoustic signal (buzzer) in case of an alarm event.
Active: in case of an alarm event (see chap. 11.2) an acoustic signal (buzzer) will run. It can be
reset by hitting button EXIT.
•Selection of controller menu language (Language)
German, English, or French can be selected.
•Counter of operating hours (Oper.hs)
Information about the number of operating hours reached up to now or since the last reset. (no
setting, display only).
•Max. number of operating hours (Op.limit)
Entry of a limit number of operating hours, i.e., the maximal number of operating hours that can be
run. Maximum setting: 9999. Reaching the limit has no effect.
•Reset operating hours (Op.back)
Reset operating hours to zero.
•Interface protocol (Protocol)
“Modbus”: The chamber interface can be used as a communication interface to connect it to a
computer. This serves to control the chamber by the communication software APT-COM
®
. It is
possible to read and write the values of all parameters.
“Printer”: A protocol printer (option) for data printouts can be connected to the chamber interface.
The printer regularly protocols the actual temperature value with fixed formatting and with adjustable
print intervals (chap. 13.2).
In both cases an interface converter RS 422 / RS 232 is used.
•Print interval (Prt.-Inv.)
Setting of the print interval in minutes. Function available only if setting “Printer” has been selected in
the previous menu point.
FP 01/2006 page 32/52
•Display illumination (Disp.LED)
Selection between continuous display illumination and limited illumination that will automatically go
off 300 sec after the last entry.
•Program type selection (PrgSelec)
Select between entry of two programs with up to 10 sections each or of one program with up to 20
sections.
When changing from 2 programs to 1 program or vice-versa, existing programs are
deleted in the program editor!
•Maximum section duration (Prg.Time)
The maximum length of an individual program section can be set to either 99 hs 59 min or to 999 hs
59 min. This setting is then valid for all program sections.
When changing the maximum duration setting, pre-existing programs will be deleted in the
program editor.
•Tolerance limit range (Tol.band)
Entry of a tolerance limit value in °C. If the actual value of temperature exceeds the set-point of a
program section by more than the entered tolerance limit value, the program is halted (LED (3d)
flashing) until the actual temperature value is again situated within the tolerance range.
Entry of “0” means tolerance limits off.
Normal Display
Press down key
Display 1 shows e.g. 0000
Display 2 shows PROGRAM EDITOR (you are in the program editor)
Press down key
Display 1 shows 0000
Display 2 shows USER – LEVEL (you are in the user level)
Set value in °C with arrow keysSetting is displayed in display 2.
Hit key
Controller returns to normal display.
Hit key EXIT or wait for 120 sec.
FP 01/2006 page 35/52
11. Behavior at failures
11.1 Behavior after power failure
Power failure during fixed-value operation (Normal Display): the entered parameters remain saved. After
power return operation continues with the set parameters.
Power failure during program operation: After power return program course continues with the set-points
that have been reached during program operation.
11.2 Alarm messages
Alarm messages, e g. “RANGE ERROR CH1” in case of sensor rupture, are displayed in Display 2 only
in Normal Display.
A buzzer can be activated / inactivated in the user level (chap. 10). It can be reset by pressing the EXIT
button. The alarm text displayed in Normal Display goes off only if the alarm cause does not exist any
more.
12. Temperature safety devices
12.1 Temperature safety device class 2 (DIN 12880)
The temperature safety device class 2 protects the unit, its environment and the charging material
against impermissible excess temperatures.
Please also observe the regulations BGR 120 of the German professional association of the chemical
industry (formerly ZH 1/119 laboratory guidelines of the employers’ liability insurance association) (for
Germany).
In the event of a fault in the temperature controller, the safety device (2) permanently switches off the
unit. This status is reported visually by the indicator lamp (2a).
The operation of the safety device (2) is checked by moving it slowly anti-clockwise until it is switched off.
The safety device cut-off is reported visually by the indicator lamp (2a).
The safety device is then released again by pressing the reset button (2b) and the unit is switched on as
described.
(2b)
(2)
(2a)
Figure 8: Safety thermostat class 2
Function:
The safety thermostat class 2 is functionally and electrically independent of the temperature control
device and switches off permanently at all poles.
When the control knob (2) is set to the end stop (position 10), the safety thermostat class 2 acts as a unit
protection device. If it is set somewhat higher than the set-point temperature selected on the controller, it
acts as a material protection device.
FP 01/2006 page 36/52
When the safety device has switched off the unit, which can be seen from the illumination of the red
alarm lamp (2a), perform the following steps:
• Disconnect the unit from the mains.
• Have the cause of the fault examined and rectified by a technician.
• Release safety thermostat class 2 by pressing reset button (2b).
• Restart the unit as described in chap. 6.
Setting:
In order to check at which temperature the safety device activates, start the unit and set the required
nominal value on the temperature controller.
The scale division from 1 to 10 corresponds to the temperature range from 30°C up to 320°C and serves
as a setting aid.
• Turn the control knob (2) of the safety device using a coin to its
end-stop (position 10) (unit protection).
• When the set point is reached, turn back the control knob (2) until
its trip point (turn it anti-clockwise).
• The trip point is identifiable by the red alarm lamp (2a) lighting up;
the reset button (2b) jumps out.
• The optimum setting of the safety device is obtained by turning the
knob clockwise by around one graduation mark on the scale.
• Push the reset button (2b) in again.
The unit is only active with the reset button (2b) pushed in.
When the safety thermostat class 2 kicks in, the red alarm lamp (2a) illuminates, the reset button (2b)
jumps out and the unit switches off permanently at all poles.
Check the safety thermostat with every change of the set point value and readjust it if
necessary.
Figure 9: Setting the safety
device class 2
12.2 Temperature safety device class 3.1 (DIN 12880) (option)
The temperature safety device class 3.1 protects the unit, its environment and the charging material
against impermissible excess temperatures. In the event of a fault, it limits the temperature inside the
oven to the value set here.
Please also observe the regulations BGR 120 of the German professional association of the chemical
industry (formerly ZH 1/119 laboratory guidelines of the employers’ liability insurance association) (for
Germany).
(2)
(2a)
Figure 10: Temperature safety device class 3.3
FP 01/2006 page 37/52
Function:
When the control knob (2) is set to the end stop (position 10), the safety thermostat class 3.1 acts as a
unit protection device. If it is set somewhat higher than the set-point temperature selected on the
controller, it acts as a material protection device.
When the safety device class 3.1 has taken over control, which can be seen from the illumination of the
red alarm lamp (2a), perform the following steps:
• Disconnect the unit from the mains
• Have examined and rectified the cause of the fault by an expert
• Start up the unit again as described in chapter 6.
Adjustment:
To check the response temperature of the safety device class 3.1, switch on the oven and set the desired
set point at the temperature controller.
The sections of the scale from 1 to 10 correspond to the temperature range from 63°C to 350°C and
serve as a setting aid.
• Turn the control knob (2) of the safety device using a coin to its endstop (position 10) (unit protection).
• When the set point is reached, turn back the control knob (2) until its
trip point (turn it anti-clockwise).
• The trip point is identifiable by the red alarm lamp (2a) lighting up.
• The optimum setting for the safety device is obtained by turning the
control knob clockwise by approximately one scale division, which
leads to extinguish the red alarm lamp.
Check the setting regularly and adjust it following changes of set-point.
Figure 11: Setting the safety
device class 3.1
13. Options
13.1 Communication software APT-COM® 3 DataControlSystem (option)
The unit is regularly equipped with a serial interface RS 422 to which the BINDER communication
software APT-COM
established using the FP interface via an interface converter RS 422 / RS 232.
Make sure that the interface mode is correctly set to “Modbus” in the user level (chap. 10).
®
3 DataControlSystem can be connected. The connection to a computer is
In adjustable intervals the actual temperature, and fan speed values are put out. Programming can be
performed graphically via PC. Up to 30 chambers with RS 422 interface can be cross linked. Further
information can be obtained in the operating manual of the BINDER communication software APT-COM
Pin allocation of the RS 422 interface at the rear of the incubator: Pin 2: RxD (+)
The protocol printer is connected using the FP interface via an interface converter RS 422 / RS 232.
Make sure that the interface mode is correctly set to “Printer” in the user level (chap. 10).
Interface configuration:
Baud rate: 9600
Stop bit: 1
Parity: none
Figure 12: Protocol printer
The actual temperature values are put out regularly with fixed formatting.
Printout: one printed line for each print interval with relative time stamp, temperature value with one
decimal point, curve representation (see “Manual for Setting Matrix Printer Epson LX-300+“, Art. No.
7001-0041). In every 5th line the set print interval “Ptime” in minutes is noted. The printer interval is set in
the user level (chap. 10).
In this example the print interval is set to 1 min, i.e., every minute a new temperature value is printed.
In connection with the set print interval, referring to real time can be achieved by noting down
the start time of the registration.
13.3 HEPA fresh air filter (option)
With this option, the introduced fresh air is cleaned by means of a high efficiency submicron particulate
air filter type HEPA class H 14 (acc. to DIN EN 1822). Replace the filter insert, if necessary, by removing
the metal cover of the filter at the left side of the unit (Art. No. 6014-0003).
FP 01/2006 page 39/52
13.4 Additional measuring channel for digital object temperature indicator with
flexible temperature sensor Pt 100 (option)
The object temperature display enables the determination of the actual temperature of the specimen
during the whole process. The object temperature is measured via a flexible Pt 100 temperature sensor
and can be viewed at Display 2 of the RD3 controller.
The object temperature data are put out together with the data of the temperature controller to the RS
422 interface as a second measuring channel and can be documented by the communication software
APT-COM
®
developed by BINDER (option, chap. 13.1).
The sensor top protective tube of the flexible Pt 100 can be immersed into liquid substances.
Technical data of the Pt 100 sensor:
• Three-wire technique
• Class B (DIN EN 60751)
• Temperature range up to 320°C
• Stainless steel protective tube 45 mm length, material no. 1.4501
13.5 Analog output for temperature (option)
With this option the chamber is equipped with an analog output 4-20 mA for temperature. This output can
be used to transmit data to external data registration systems or devices.
The connection is carried out as a DIN socket at the back of the incubator as following:
3
2
1
4
6
5
ANALOG OUTPUT 4-20 mA DC
PIN 1: Temperature –
PIN 2: Temperature +
Temperature range: 0°C to 300°C
A suitable DIN plug is enclosed.
Figure 13: Pin configuration of the DIN socket
13.6 Zero-voltage relay outputs via operation lines (option)
Operation lines 1, 2 und 3 are used to switch any device connected to the zero-voltage relay outputs via
a DIN socket at the rear of the incubator. The operation lines allow switching on and off the individual
zero-voltage relay outputs through the program controller. They can be programmed in fixed value entry
mode (chap. 7) as well as in the program editor (chap. 8.2) via the operation lines (switching state 0 =
Off, switching state 1 = On).
Connection occurs via the DIN socket at the rear of the incubator:
3
2
1
4
6
5
Figure 14: Pin configuration of the DIN socket
A suitable DIN plug is enclosed.
Operation line 1 Operation line 2 Operation line 3
1 2 1
Pin 1: Pin
Pin 2: Make
2
3
Pin 3: Pin
Pin 4: Make
4
5
Pin 5: Pin
6
Pin 6: Make
Switching state On: 1xx Switching state On: x1x Switching state On: xx1
FP 01/2006 page 40/52
Maximum loading capacity of the switching contacts: 24V AC/DC – 2.5 A
DANGER
Electrical hazard.
Danger of life.
Damage of switching contacts and connection socket.
∅ Do NOT exceed the maximum switching load of 24V AC/DC – 2.5A.
∅ Do NOT connect any devices with a higher loading capacity.
13.7 Mostly gas-tight version (option for FP 53 and FP 115)
With this option the heating/drying oven is additionally sealed, so the loss when introducing gases is
decreased. The unit is not completely gas-tight, so it is impossible to establish overpressure. The sealing
diminishes the release of vapors via the housing that may be set free from the charging material when
heated. Carrying-off via the regular evacuation duct, e.g. into a waste air installation, is likely to further
reduce emissions.
The unit is not completely gas-tight. Gases from inside the heating/drying oven can escape
into the surrounding atmosphere.
Respect the maximum working place concentration of the released substance. Respect the
relevant regulations.
Any harmful gas that might escape has to be led out via good room ventilation or a suitable
exhaust system. Place the unit, if necessary, below a gas vent.
13.8 Inert gas connection (option for FP 53 and FP 115)
With this option, the heating/drying oven is equipped with two ports for inert gas (on top in the middle, and
down at the right, both on the rear of the unit). Each of these ports can be used as inlet or outlet,
depending on the nature of the inert gas (heavy gas: upper port as inlet, lighter gas: lower port as inlet).
Connect a flexible gas tube to the gas tube connection adapter (diameter 10mm) used for gas inlet, and
secure it with hose clamps (not enclosed).
The unit is not gas-tight. Gases from inside the high performance temperature chamber can escape into
the surrounding atmosphere.
Any gas that might escape has to be led out via good room ventilation or a suitable exhaust system
WARNING
High concentration of inert gas.
Danger of poisoning.
∅ Do NOT set up units in non-ventilated recesses
Ensure technical ventilation measures
Respect the relevant regulations for handling these gases.
The “Mostly gas-tight version” (option for FP 53 and FP 115, chap. 13.7) reduces the loss of
gas.
FP 01/2006 page 41/52
14. Maintenance, cleaning, and service
14.1 Maintenance intervals, service
DANGER
Electrical hazard.
Danger of life.
Put off-circuit the unit before conducting maintenance work. Pull the power plug.
∅ The unit must NOT become wet during operation or maintenance works.
Have all maintenance work conducted by professional electricians or experts
authorized by BINDER.
Have conducted regular maintenance work at least once a year.
Change the door gasket in cold condition only. Otherwise the door gasket will be damaged.
We recommend entering a maintenance agreement. Please consult the BINDER service department.
BINDER telephone hotline: +49 (0) 7462 2005 555
BINDER fax hotline: +49 (0) 7462 2005 93555
BINDER e-mail hotline: service@binder-world.com
BINDER service hotline USA: +1 866 816 8191 (toll-free in the USA)
BINDER Asia Pacific: + 603 6204 2855
BINDER Internet homepage http://www.binder-world.com
BINDER address BINDER GmbH, post office box 102, D-78502 Tuttlingen
International customers, please contact your local BINDER distributor.
14.2 Cleaning and decontamination
DANGER
Electrical hazard.
Cleaning
Danger of life.
∅ Do NOT spill water or cleaning agents over the inner and outer surfaces.
Put off-circuit the chamber before cleaning. Pull the power plug.
Completely dry the appliance before switching it on again.
Disconnect the chamber from the mains before cleaning. Pull the power plug!
Wipe the surfaces with a moistened towel. In addition, you can use the following cleaning agents:
Exterior surfaces
inner chamber
shelves
door gaskets
Instrument panel Standard commercial cleaning detergents free from acid or Halogenide.
FP 01/2006 page 42/52
Standard commercial cleaning detergents free from acid or Halogenide.
Alcoholic solutions.
We recommend using the neutral cleaning agent Art. No. 1002-0016.
We recommend using the neutral cleaning agent Art. No. 1002-0016.
For surface protection, perform cleaning as fast as possible.
After cleaning completely remove cleaning agents from the surfaces with a moistened towel.
Decontamination
Disconnect the chamber from the mains prior to decontamination. Pull the power plug.
You can use the following disinfectants:
Inner chamber Standard commercial surface disinfectants free from acid or Halogenide.
Alcoholic solutions.
We recommend using disinfectant Art. No. 1002-0022.
In case of impurity of the interior with biological or chemical hazardous goods, there are three possible
procedures depending on the type of contamination and of the charging material.
(1) The heating/drying ovens FP can be hot air sterilized at 190°C for at least 30 minutes. All
inflammable goods must be removed from the interior before.
(2) Spray the inner chamber with an appropriate disinfectant.
Before start-up, the unit must be absolute dry and ventilated, because explosive gases might form
during the decontamination process.
(3) If necessary, have strongly contaminated inner chamber parts removed by an engineer for cleaning,
or have them exchanged. Sterilize the inner chamber parts in a sterilizer or autoclave.
With every decontamination method, ensure adequate personal safety.
CAUTION
Danger of corrosion.
Damage of the unit.
∅ Do NOT use acidic or chlorine cleaning detergents.
We recommend using the neutral cleaning agent Art. No. Art. Nr. 1002-0016 for a thorough
and mild cleaning.
Any corrosive damage that might arise following use of other cleaning agents is excluded from
liability by the BINDER GmbH.
FP 01/2006 page 43/52
15. Disposal
15.1 Disposal of the transport packing
Packing element Material Disposal
Straps to fix packing on pallet Plastic Plastic recycling
Wooden sticks for stabilizing and for
take out (from size 240 on)
Foamed plastic stuffing (pallet, top
cover)
Top cover (from size 240 on) Cardboard Paper recycling
(sizes 240 and 400
only)
matchwood, IPPC standard)
Metal Metal recycling
Cardboard Paper recycling Transport box
Metal Metal recycling
Solid wood (IPPC standard) Wood recycling
PE foam Plastic recycling
Cardboard Paper recycling Take out assistance
Plastic Plastic recycling
Wood recycling Wooden transport box (option)
Edge protection Styropor® Plastic recycling
Protection of doors and racks PE foam Plastic recycling
Bag for operating manual PE foil Plastic recycling
Insulating air cushion foil (packing of
optional accessories)
If recycling is impossible, all packing parts can also be disposed of in the household waste.
PE foil Plastic recycling
15.2 Decommissioning
Switch off main switch (1). Disconnect the unit from the mains.
When switching off the main switch ON / OFF (1), the stored parameters remain saved.
• Temporal decommissioning: See indications for appropriate storage, chap. 4.3.
• Final decommissioning: Dispose of the unit as described in chap. 15.3.
15.3 Disposal of the unit
CAUTION
Alteration of the environment.
¾ For final decommissioning and disposal of the unit, please contact the BINDER
service.
¾ Observe the regulations under public law for appropriate disposal protecting the
environment.
The main board of the heating/drying oven includes a lithium cell. Please dispose of it according to the
national regulations.
FP 01/2006 page 44/52
16. Technical description
16.1 Factory calibration and adjustment
This unit was calibrated and adjusted in factory. Calibration and adjustment were performed using
standardized test instructions, according to the QM-system of DIN EN ISO 9001 applied by BINDER
(certified since December 1996 by TÜV CERT under registration number 70 100 M 926). All test
equipment used is subject to the administration of measurement and test equipment that is also
constituent part of the BINDER QM-systems of DIN EN ISO 9001. They are controlled and calibrated in
relation to a DKD-Standard on regular intervals.
Adjustment in factory in the center of the usable volume: 150°C.
16.2 Over current protection
Single-phase devices are protected by one miniature fuse against over current, accessible from the
outside. The miniature fuse is located at the rear of the chamber below the strain relief of the power cord.
The fuse holder is equipped with a fuse clip 5mm x 20 mm. (CUL-Version 6,3x32 mm). The fuse may be
replaced only with a substitute of the same ratings. Refer to the technical data of the respective device
type.
Three-phase devices are equipped with internal fuses not accessible from outside. If these fuses are
blown, please inform an electronic engineer or the BINDER service.
16.3 Definition of usable space
The usable volume illustrated below is calculated as follows:
C
a
c
A
c
b
a
b
The technical data refer to the so defined usable space.
Do NOT place samples outside this usable volume.
Do NOT load this volume more than half to enable sufficient airflow inside the chamber.
Do NOT divide the usable volume into separate parts with large area samples.
A, B, C = internal dimensions (W, H, D)
a, b, c = wall separation
B
a = 0.1*A
b = 0.1*B
c = 0.1*C
V
= (A - 2 * a) * (B - 2 * b) * (C - 2 * c)
USE
Figure 15: Determination of the usable volume
Do NOT place samples too close to each other in order to allow circulation between them and
thus obtain a homogenous distribution of temperature and humidity.
FP 01/2006 page 45/52
16.4 Technical data
Unit size 53 115 240 400 720
Exterior dimensions
Width mm
inch
Height (incl. feet/roller) mm
inch
Depth mm
inch
incl. door handle, instrument panel,
and exhaust duct
mm
inch
Wall clearance rear mm
inch
Wall clearance side mm
inch
Exhaust duct, outer diameter mm
inch
Steam space volume l
cu.ft.
Number of door(s) 1 1 2 2 2
Interior dimensions
Width mm
inch
Height mm
inch
Depth mm
inch
Interior volume l
cu.ft.
Number of racks regular /
max.
Load per rack Kg
lbs
Permitted total load Kg
lbs
Weight (empty) Kg
lbsTemperature data
Temperature range, 5°C above
ambient up to
Temperature variation 1)
at 70°C± °C 0.8 0.7 0.8 1 1
at 150°C± °C 2 1.8 2 2.5 2
°C
°F
at 300°C± °C 3.7 3.9 4.3 4.8 5.5
Temperature fluctuation
Heating up time 2)
to 70°CMin 6 7 12 18 25
≤± °C
to 150°CMin 24 30 27 35 39
to 250°CMin 45 49 50 60 65
Recovery time after door
was open for 30 sec 2)
at 70°CMin 2 2 2 2 2
at 150°CMin 5 8 10 17 20
at 300°CMin 10 15 16 21 24
Air change
at 70°Cx/h 59 29 19 17 11
at 150°Cx/h 64 32 20 18 12
at 300°Cx/h 53 26 18 16 10
634
24.96
617
24.29
575
22.64
105
4.13
100
3.94
160
6.30
52
2.05
77
2.72
400
15.75
400
15.75
330
12.99
53
1.9
834
32.83
702
27.64
645
25.39
105
4.13
100
3.94
160
6.30
52
2.05
158
5.58
600
23.62
480
18.90
400
15.75
115
4.1
1034
40.71
822
32.36
745
29.33
105
4.13
100
3.94
160
6.30
52
2.05
308
10.88
800
31.50
600
23.62
500
19.69
240
8.6
1234
48.58
1022
40.24
765
30.12
105
4.13
100
3.94
160
6.30
52
2.05
498
17.60
1000
39.37
800
31.50
500
19.69
400
14.3
1234
48.58
1528
60.16
865
34.06
105
4.13
100
3.94
160
6.30
52
2.05
869
30.71
1000
39.37
1200
47.24
600
23.62
720
25.7
2/5 2/6 2/7 2/10 2/16
15
33
40
88
45
99
300
572
20
44
50
110
62
137
300
572
30
66
70
155
98
216
300
572
35
77
90
199
145
320
300
572
45
99
120
265
184
406
300
572
0.3 0.3 0.3 0.3 0.3
FP 01/2006 page 46/52
Unit size 53 115 240 400 720
Electrical data
IP system of protection acc. to EN 60529 20 20 20 20 20
Nominal voltage (±10%) 50/60 Hz V 230 1N~230 1N~230 1N~ 400 3N~400 3N~
Nominal power kW 1.2 1.6 2.7 3.4 5.0
Energy consumption
Unit fuse 5 x 20 mm
230V / 10A / middle-time-lag (M)
Over-current release category B -- -- -- 3 x 16A
Mains plug shock proof plug CEE plug 5 poles
Installation category acc. to IEC 1010-1 II II II II II
Pollution degree acc. to IEC 1010-1 2 2 2 2 2
at 70°CW 145 230 370 520 570
at 150°CW 300 544 850 1200 1320
at 300°CW 720 1100 1400 2340 2600
A 10 A
external
10 A
external
16 A
external
-- --
internal
3 x 16A
internal
Electrical connection data FP-UL acc. to CUL standard (for USA and Canada):
Unit size 53-UL 115-UL 240-UL 400-UL 720-UL
Electrical data
Nominal voltage (±10%) 60 Hz V 115 1N~115 1N~208 3N~ 208 3N~208 3N~
Nominal power kW 1.20 1.60 2.70 3.40 5.00
Mains plug NEMA 5-20P 5-20P L21-20P L21-20PL21-20P
Unit fuse
6,3 x 32 mm / 250V / super-time-lag TT
Installation category acc. to IEC 1010-1 II II II II II
Pollution degree acc. to IEC 1010-1 2 2 2 2 2
A external external 3 x
internal
3 x
internal
3 x
internal
Legend: 1) without outer glass door 2) up to 98 % of the set value
All technical data are specified for units with standard equipment at an ambient temperature of +25°C and
a mains voltage fluctuation of ±10. The temperature data are determined in accordance to DIN 12880,
part 2, respecting the recommended wall clearances of 10 % of the height, width and depth of the inner
chamber. Technical data refer to 100% fan speed.
All indications are average values, typical for units produced in series. We reserve the right to
alter technical specifications at all times.
If the cabinet is fully loaded, the specified heating up times may vary according to the load.
16.5 Equipment and Options
To operate the heating/drying oven, use only original BINDER accessories or accessories of
third-party suppliers authorized by BINDER. The user is responsible for any risk when using
unauthorized accessories.
Unit size 53 115 240 400 720
Regular equipment
Multifunction program controller RD3 with
digital display
Temperature safety controller class 2 acc. to
DIN 12880
Communication and printer interface RS 422
Rear exhaust duct, internal diameter 50 mm /
1,97 inch with ventilation slide
Adjustable air change by means of rear
exhaust duct (50 mm) with ventilation flap
and front ventilation slide
Four castors (2 lockable) -- -- -- --
FP 01/2006 page 47/52
Unit size 53 115 240 400 720
Options / accessories
Access ports with various diameters, with
silicone plug
Rack, chrome-plated or stainless steel
Perforated rack, stainless steel
Rack lockings (4 pieces)
Rubber pads for safe stacking (4 pieces)
Reinforced rack stainless steel, with 1 set shelf
lockings
Reinforced inner chamber with 2 reinforced
racks
Temperature safety device class 3.1 acc. to DIN
12880, part 1
Door with window and interior lightning
Lockable door
Viton door gasket (temperature resistant up to
200°C)
Fresh air filter, class EU 14
Measurement of air change rate acc. to ASTM
2436
-- --
-- --
-- --
Additional measuring channel for digital object
temperature indicator with flexible temperature
sensor Pt 100
Construction almost gas-tight
Inertgas connection (gas inlet and outlet)
Increased air change by stronger fan
Analog output 4-20 mA for temperature with 6
pole DIN socket, DIN plug included
Zero-voltage relay outputs via DIN socket 6
poles
Serial printer with interface, for numerical and
graphical temperature registration
2-channel pen recorder, external
Unit acc. to CUL standard in 115V 1N~60Hz
Unit acc. to CUL standard in 208 V 3N~60Hz -- --
Factory calibration certificate
Extension to factory calibration certificate
(additional value)
Measuring protocol acc. to DIN 12880, Part 2
Qualification folder
Evaporating dish with rim, small or large
Instrument tray with lid, small or large
Neutral cleaning agent (liquid concentrate)
Stable table on wheels with castors and locking
brakes
-- -- --
-- -- --
-- -- --
--
Legend:
Standard equipment Optional -- Not available
FP 01/2006 page 48/52
16.6 Spare parts
The BINDER GmbH is responsible for safety-related unit properties only if skilled electricians
or qualified personnel authorized by BINDER perform all maintenance and repair, and if
components with relating to chamber safety are replaced in case of failure with original spare
parts. The user is responsible for any risk when using unauthorized accessories.
Accessories and spare parts:
Unit size 53 115 240 400 720
Description Art. No.
Rack, chrome-plated 6004-0002 6004-0003 6004-0004 6004-0005 6004-0006
Rack, stainless steel 6004-0007 6004-0008 6004-0009 6004-0011 6004-0010
Perforated rack, stainless steel 6004-0029 6004-0030 6004-0031 6004-0032 6004-0033
Door gasket silicone 6005-0095 6005-0096 6005-0097 6005-0069 6005-0099
Door gasket made of Viton (temperature
resistant up to 200°C)
Stable table on wheels with castors and
locking brakes
Rubber pads for safe stacking (4 pieces) 8012-0001 8012-0001 8012-0001 -- -Unit fuse 5x20mm / 250V / 10Amp
semi time lag (M)
Unit fuse 5x20mm / 250V / 16Amp
semi time lag (M)
Over-current release category B 16 A -- -- -- 5006-0042 5006-0042
Controller RD3 5014-0081
Thermostat class 2 30° to 320°C 5006-0031
Turning knob for thermostat class 2 8009-0004
Pilot lamp red 5008-0003
Temperature sensor Pt 100 bend-off 5002-0022
Rack lockings (4 pieces) 8012-0531
Protocol printer 8012-0418
2-channel pen recorder, external 8012-0152
Fresh air filter, class EU 14 8012-0076
Measurement of air change rate acc. to
ASTM 2436
Calibration certificate 8012-0030
Extension for calibration certificate (additional
value)
Measuring protocol acc. to DIN 12880, Part 28012-0156
Qualification folder 8012-0422
Instrument tray with lid, small 4022-0123
Instrument tray with lid, large 4022-0124
Evaporating dish, small 4022-0125
Evaporating dish, large 4022-0126
Neutral cleaning agent, 1 kg 1002-0016
8012-0494 8012-0495 8012-0496 8012-0497 8012-0498
9051-0018 9051-0018 9051-0019 9051-0019--
5006-0012 5006-0012-- -- --
-- -- 5006-0013 -- --
8012-0195
8012-0022
FP 01/2006 page 49/52
17. Contamination clearance certificate
Unbedenklichkeitsbescheinigung
Declaration of harmlessness with regard to safety and health
Erklärung zur Sicherheit and gesundheitlichen Unbedenklichkeit
The German Ordinance on Hazardous Substances (GefStofV), and the regulations regarding safety at
the workplace, require that this form be filled out for all products that are returned to us, so that the safety
and health of our employees can be warranted. In the absence of a completely filled out form, a repair is
not possible.
Die Sicherheit und Gesundheit unserer Mitarbeiter, die Gefahrstoffverordnung GefStofV und die Vorschriften zur
Sicherheit am Arbeitsplatz machen es erforderlich, dass dieses Formblatt für alle Produkte, die an uns
zurückgeschickt wird. Ohne Vorliegen des vollständig ausgefüllten Formblattes ist eine Reparatur nicht möglich.
•A completely filled out form should be transmitted by Fax (+49 (0) 7462 2005 93555) or by letter in
advance to us, so that this information is available before the equipment/component part arrives. A
second copy of this form should accompany the equipment/component part. Eventually the carrier
should be informed.
Eine vollständig ausgefüllte Kopie dieses Formblattes soll per Telefax (Nr. +49 (0) 7462 2005 93555) oder Brief
vorab an uns gesandt werden, so dass die Information vorliegt, bevor das Gerät/Bauteil eintrifft. Eine weitere
Kopie soll dem Gerät/Bauteil beigefügt sein. Ggf. ist auch die Spedition zu informieren.
•Incomplete information or non-conformity with this procedure will inevitably lead to substantial delays
in processing. We hope you will have understanding for this measure, which lies outside of our area
of influence, and that you will help us to speed up this procedure.
Unvollständige Angaben oder Nichteinhalten dieses Ablaufs führen zwangsläufig zu beträchtlichen
Verzögerungen in der Abwicklung. Bitte haben Sie Verständnis für Maßnahmen, die außerhalb unserer
Einflussmöglichkeiten liegen und helfen Sie mit, den Ablauf beschleunigen.
•Please fill out this form completely.
Bitte unbedingt vollständig ausfüllen!
1. Unit/ component part / type: /
2. Serial No./ Serien-Nr.:
3. Details about utilized substances / biological substances / Einzelheiten über die eingesetzten
Substanzen/biologische Materialien:
3.1 Designations / Bezeichnungen:
Gerät / Bauteil / Typ:
a) ____________________________________________________________________________
b) ____________________________________________________________________________
c) ____________________________________________________________________________
3.2 Safety measures required for handling these substances / Vorsichtsmaßnahmen beim Umgang
mit diesen Stoffen:
a) ____________________________________________________________________________
b) ____________________________________________________________________________
c) ____________________________________________________________________________
FP 01/2006 page 50/52
3.3 Measures to be taken in case of skin contact or release into the atmosphere /
bei Personenkontakt oder Freisetzung:
Maßnahmen
a) ____________________________________________________________________________
b) ____________________________________________________________________________
c) ____________________________________________________________________________
We herewith declare that the following measures have been taken /
Maßnahmen getroffen wurden:
Wir erklären, dass folgende
Hazardous substances were removed from the unit / component part, so that no hazard exists for
corresponding persons in the handling or repair of these items /
befreit, so dass bei Handhabung/Reparaturen für die betreffenden Person keinerlei Gefährdung besteht
das Gerät/Bauteil wurde von Gefahrstoffen
The unit was securely packaged and properly identified / das Gerät wurde sicher verpackt und vollständig
gekennzeichnet.
Information about the hazardousness of the shipment (if required) has been provided to the
transporter /
We herewith commit ourselves and guarantee that we will indemnify BINDER GmbH for all damages
that are a consequence of incomplete or incorrect information provided by us, and that we will exempt
BINDER GmbH from eventual damage claims by third parties./
jeden Schaden, der durch unvollständige und unrichtige Angaben entsteht, haften und BINDER gegen eventuell entstehende
Schadenansprüche Dritter freistellen.
We are aware that, in accordance with Article 823 of the German Civil Code (BGB), we are directly liable
with regard to third parties, in this instance especially the employees of BINDER GmbH, who have been
entrusted with the handling / repair of the unit / component. /
insbesondere mit der Handhabung/Reparatur des Geräts/des Bauteils betraute Mitarbeiter der Firma BINDER - gemäß §823 BGB
direkt haften
der Spediteur wurde (falls vorgeschrieben) über die Gefährlichkeit der Sendung informiert.
Wir versichern, dass wir gegenüber BINDER für
Es ist uns bekannt, dass wir gegenüber Dritten – hier
Equipment that is returned to the factory for repair must be accompanied by a completely filled
out contamination clearance certificate. For service and maintenance works on site, such a
contamination clearance certificate must be submitted to the service technician before the
start of the works. No repair or maintenance of the equipment is possible, without a properly
filled out contamination clearance certificate.
FP 01/2006 page 52/52
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.