English
Service&MaintenancemanualforiXPanelTA70
Foreword
This manual contains detailed information about iX Panel TA70, including descriptions of variousactions that can be carried out in orderto maintain or update the operator panelhardware and software.
The manual contains descriptionsof basic maintenance and replacement of common parts in iX Panel TA70.
The manual assumes thatthe most recent versions of the system program (firmware) and iX Developer are used.
The followingother manuals are available for i X Panel TA70: iX PanelTA70installation manual (MAEN009x) for information regarding
installation. iX Developer reference manual (MAEN831x) for a description of the
configuration tool. iX Developer user’s guide (MAEN832x) for function-based descriptions.
Foreword
Order no: MAEN012A
Copyright © 2010-12 Beijer Electronics AB.All rights reserved.
The information inthis document is subject tochangewithoutnoticeandisprovidedasavailableatthe
time of printing. Beijer Electronics AB reserves the rightto change any information without updating this
publication. Beijer Electronics AB assumes no responsibility for any errors that mayappear inthis document.
Read the entireinstallation manual prior to installing and usingthis equipment. Only qualified personnel
may install, operate or repair this equipment. Beijer ElectronicsAB is notresponsible for modified, altered
or renovated equipment. Because the equipment hasa widerangeofapplications,usersmustacquirethe
appropriate know l edge to use the equipment properly in their specific applications. Persons responsible
for the application and the equipment must themselves ensure that each application is in compliance with
all relevant requirements, standards and legislationinrespecttoconfigurationandsafety. Onlypartsand
accessories manufactured according to specifications set byBeijer ElectronicsAB may be used.
BEIJER ELECTRONICSAB SHALL NOTBE LIABLE TO ANYONE FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGESRESULTING FROMTHE INSTALLATION, USE OR REPAIR OF THIS EQUIPMENT, WHETHER ARISING IN TORT, CONTRACT, OR OTHERWISE. BUYER'S SOLE REMEDYSHALL BE THE REPAIR, REPLACEMENT, OR REFUND OF PURCHASE PRICE, ANDTHE CHOICE OF THE APPLICABLE REMEDYSHALLBEATTHESOLEDISCRETIONOFBEIJER ELECTRONICSAB .
BeijerElectronics, MAEN012A
Contents
Contents
1 Safety Precautions ....................................................... 5
1.1 General ...........................................................
1.2 During Installation ..............................................
1.3 During Use .......................................................
1.4 Service and Maintenance ........................................
1.5 Dismantling and Scrapping .....................................
2 Introduction ............................................................. 7
2.1 iX PanelTA70 ....................................................
2.2 Maintenance .....................................................
2.3 Serviceand Repairs ..............................................
2.4 Dismantling and Scrapping .....................................
2.5 Contact andSupport ............................................
3 Installation ............................................................... 10
3.1 Space Requirements .............................................
3.2 InstallationProcess ..............................................
3.2.1 ConnectionstotheController ..................................
3.2.2 OtherConnections andPeripherals ................... ..........
4 Technical Data ........................................................... 14
5 Chemical Resistance .................................................... 15
5.1 Metal Casing .....................................................
5.2 Touch Screen and Overlay .. .....................................
5.2.1 AutotexF157/207 ............................ ...................
5.2.2 TouchScreenSurface ............................... .............
5.2.3 AutoflexEB ...................................... ................
6 HardwareTests .......................................................... 18
7 Hardware Replacement ................................................. 19
7.1 Mode Switches ...................................................
7.2 Cables .............................................................
7.3 Replacing the Rear Cover ........................................
7.4 Replacing the Display/Displ
7.4.1 SelfTest of theDisplay ................................. ..........
7.4.2 Calibratingthe TouchScreen .................... ................
ay Cable ..........................
7.5 ReplacingtheCompleteFront ..................................
7.6 Replacing the Backlight . ........................................
7.7 Available SpareParts for iX PanelTA70 ........................
8 ServiceMenu ............................................................ 27
8.1 Service Menu in an Empty Panel ...............................
8.2 Service Menu in a Panel with Project ...........................
8.3 Service Menu Options ...........................................
8.3.1 IPSettings ........................... ............................
8.3.2 Date/Time ......... ..............................................
8.3.3 Erase Project .....................................................
8.3.4 TouchCalibrate .................................................
9 Hardware SelfTest ...................................................... 29
9.1 Self Test Items ....................................................
10 10
13
13
15 16
16 17 17
19 20
21 22
23
23
24 25 26
27 27 27
27 28
28 28
30
5 5 6
6 6
7 8
8 8 9
BeijerElectronics, MAEN012A
Contents
10 Additional Installation Tips ... ......................................... 31
10.1 Grounding theOperatorPanel .................................
10.2 Ethernet Connection in the Panel ..............................
10.3 To Achieve Better EMC Protection .............................
10.4 Ambient Temperature ...........................................
10.5 Safety .............................................................
10.6 GalvanicIsolation ................................................
10.7 Cable and Bus Termination RS485 .............................
31 32 33
34 35
36 37
11 Fault Tracing ............................................................. 38
12 Software .................................................................. 40
12.1 General Information aboutSoftware ...........................
12.1.1 SoftwareProducts ............................... ................
12.2 Update Software .................................................
12.2.1 iXDeveloper ..................................... ................
12.2.2 RemoteAccessViewer ..................... ......................
12.2.3 SystemProgram ......... ........................................
40
40
41
41 41
41
13 EnvironmentalAspects ................................................. 43
13.1 General Environmental Aspects ................................
13.2 EnvironmentalImpact of theOperator Panels .................
13.2.1 MechanicalComponents ........................... .............
13.2.2 Electronics .......................................................
13.3 Recycling .........................................................
13.4 Environmental Impact Report ..................................
43 43
43 43
44 44
BeijerElectronics, MAEN012A
Safety Precautions

1SafetyPrecautions

Both the installer andthe owner and/or operator of the operator panel must read and understand thisinstallation manual.

1.1 General

Read the safety precautionscarefully.
Check the delivery for transportation damage. If damage is found, notify the
supplier as soon as possible.
Donot use the operator panel in an environment with high explosive hazards.
Thesupplier is not responsible for modified, altered or reconstructed
equipment.
Use only parts and accessories manufactured accordingto specifications of
the supplier.
Read the installationand operating instructions carefully before installing,
using or repairingthe operator panel.
Neverallowfluids,metalfilingsorwiringdebristoenteranyopeningsinthe
operator panel. This may cause fire or electrical shock.
Only qualified personnel may operate the operator panel.
Storing theo perator panel where the temperature is lower/higher than
recommended in this manualcan cause the LCD display liquidto congeal/become isotopic.
The LCD display liquid contains apowerful irritant. In case of skincontact,
wash immediately with plenty of water. In case of eye contact, hold the eye open,flushwithplentyofwaterandgetmedicalattention.
Thefiguresinthismanualservesanillustrativepurpose. Becauseofthemany
variables associated with anyparticular installation, the supplier cannot assume responsibility for actual use based on the figures.
The supplier neither guarantees that the operatorpanel is suitable for your
particular application, nor assumesresponsibility for your product design, installation or operation.

1.2 DuringInstallation

The operator panelis designed for stationary installation on a plane surface,
where thefollowing conditions arefulfilled:
no high explosive risks no strong magnetic fields no direct sunlight no large, sudden temperature changes
Install the product according to the accompanying installation instructions.
Ground theproduct according to the accompanying installation instructions.
Only qualified personnel may install the operator panel.
Separate the high voltage,signal and supply cables.
Make surethat the voltage and polarity of the power source is correctbefore
connecting the product to the power outlet.
Peripheralequipment must be appropriate for theapplication and location.
BeijerElectronics, MAEN012A
5
Safety Precautions

1.3 DuringUse

Keep the operator panel clean.
Emergency stop and othersafety functions may not be controlled from the
operator panel.
Do not usetoo much force or sharp objects when touching the keys, touch
screenetc.

1.4 ServiceandMaintenance

Only qualified personnel should carry out repairs.
The agreed warranty applies.
Before carrying out any cleaning or maintenanceoperations, disconnect the
equipment from theelectrical supply.
Clean the display andsurrounding front cover with a soft cloth and mild
detergent.
Replacing the battery incorrectly may resultin explosion. Only use batteries
recommended by thesupplier.

1.5 DismantlingandScrapping

The operator panelor parts thereof shall be recycledacc
regulations.
The followingcomponents contain substances t
to health andthe environment: lithium batter display.
hat might be hazardous
y, electrolytic capacitor and
ording to local
BeijerElectronics, MAEN012A
6
Introduction

2Introduction

This manual describes how to maintain the iXPanel TA70. The functions availablein iX Developer depend on which operator panel model is
used.

2.1 iXPanelTA70

The followingdrawings are available for iX Panel TA70:
Outline drawing
Panelcut-out
BeijerElectronics, MAEN012A
7
Introduction

2.2 Maintenance

Carefully read the instructions beforebeginning maintenance on the operator panel.
Only qualified personnel should carry out maintenance.
The agreed warranty and license agreements apply.
Any damage tothe operator panel caused by personnelinvalidates the
warranty.
Before carrying out any cleaning or maintenanceoperations, disconnect the
operator panel fromthe power supply.
Clean the display andsurrounding front cover with a soft cloth and mild
detergent. Recommended cleaning fluids for the display are water and IPA (Isopropyl Alcohol or Hexane).
Replacing the battery incorrectly may resultin explosion. Only use batteries
recommended by thesupplier.
A 6-month warrantyon all service parts is provided.
Maintenance personnel are permitted tocarry out the following actions:
Replacing the Rear Cover
Replacing the Display/Display Cable
Replacing the Complete Front

2.3 ServiceandRepairs

Only accredited companies are permitted to perform service and repairs.
Ifanon-accreditedcompanyconductsanykindofserviceorrepair,theagreed
warranty will beinvalidated.
If training is required,contact the supplier.
All maintenance should be performed in a15-30 °C temperature range.
Any damage tothe operator panel caused by personnelinvalidates the
warranty.
Contracts with customers s upersede the information in this document.

2.4 DismantlingandScrapping

The operator panel,or parts thereof, should berecycled according to local
regulations.
The followingcomponents contain substances that mightbe hazardous to
health and theenvironment: lithium battery, electrolytic capacitor, display.
BeijerElectronics, MAEN012A
8
Introduction

2.5 ContactandSupport

If you wantto report a fault or have aquestion about the operator panels, please contact your localsupplier or fill out the form on the web site.
1.
Enter the web site www.beijerelectronics.com and selectSupport.
2.
Select Contact inthe menu. Make sure to provideinformation about type number, serial number, environmentand an installation description.
The form will besent to the manufacturer’s help deska nd they will answer your question or registeryour improvement/fault.
To ensure quick resolution, provideas many details as possible in yourreport. Include the date and time when the problem occurred, a description ofwhat you were trying to do, thedetailed steps you took that led up to the problem, and details about any error messages received.
BeijerElectronics, MAEN012A
9

3Installation

3.1 SpaceRequirements

Installation plate thickness: 1.5 - 9.0mm (0.06 - 0.35 inch)
Space requirementswhen installing the operator panel:
100 mm (4.0 inch)
154 mm
(6.06 inch)
50 mm
(2.0 inch)
100 mm (4.0 inch)
219 mm
(8.62 inch)
50 mm
(2.0 inch)
56 mm
(2.20 inch)
Installation
100 mm (4.0 inch)
Caution:
Theopeningsontheenclosureareforairconve
ction. Donot covertheseopenings.

3.2 InstallationProcess

1.
Unpack and check the delivery. If
Note:
Placethe operatorpanelonastablesurfaceduringinstallation. Droppingitorlettingitfallmaycausedamage.
damage is found, notify the supplier.
Panel cut out 188.5 x 137.5 mm
(7.42 x 5.41 inch)
x 4
BeijerElectronics, MAEN012A
10
2.
Place thepanel cut out where theoperator panel is to besituated, draw along the outer sides of the holes and cutaccording to the markings.
3.
Secure the operator panel in position, using allthe fastening holes and the provided brackets and screws:
x 4
Installation
0.5 - 1.0 Nm
BeijerElectronics, MAEN012A
11
Installation
4.
Connect the cables in the specified order, according to the drawing and steps below.
Caution:
Ensurethattheoperatorpanelandthecontrollersystemhavethesameelectrical
grounding(referencevoltagelevel),otherwiseerrors incommunicationmay occur.
Theoperatorpanelmustbebroughttoambienttemperaturebeforeitisstarted
up. Ifcondensation forms,ensurethattheoperatorpanelisdrybeforeconnecting itto thepoweroutlet.
Ensurethatthevoltageandpolarityofthepowersourceiscorrect.
Useonly shieldedcommunicationcables.
Separatehighvoltagecablesfromsignalandsupplycables.
Power
CF CARD
B
1
Controller
RS422/RS485
RS232
24V DC
24V DC
C
D
A
Ethernet
Connect cable A. Connect cable B, using an M5 screwa nd a grounding conductor (as short
as possible) with a cross-section of minimum 2.5 mm
Connect cable C. Connect cable D.
5.
Carefully removethe laminated film over the operator panel display, to avoid
2
.
static electricity that could damage the panel.
BeijerElectronics, MAEN012A
12
Installation

3.2.1 ConnectionstotheController

Forinformation about the cables to be used when connecting the operator panel to the controller,please refer to the help file for the driver in question.

3.2.2 OtherConnectionsandPeripherals

Cables, peripheral equipment and accessories must besuitable for the application and its environment. Forfurther details or recommendations, please refer to the supplier.
BeijerElectronics, MAEN012A
13
Technical Data

4TechnicalData

Parameter iX Panel TA70
Frontpanel,WxHxD 219x154x6mm Mountingdepth 56mm (156mmincludingclearance) Frontpanel seal IP66 Rear panel seal IP 20 Keyboard
material/Front panel
Reverseside material
Weight 1.2 kg Serialport
RS422/RS485 SerialportRS232C 9-pinD-subcontact,malewithstandardlockingscrews4-40
Ethernet 2x shieldedRJ45 USB HosttypeA(USB 2.0),max outputcurrent 500m A Memoryslots 1x SDcard Realtimeclock ±30PPM +errorbecauseofambienttemperature. Total
Power consumption atrated voltage
Display TFT-LCD.640x480pixels,64Kcolors.
Activeareaof display,WxH
Fuse InternalDCfuse,3.15AT, 5x20mm Powersupply +24VDC (20-30VDC).Powersupplyconnector.
Ambient temperature
Storagetemperature -20°to+70°C Relativehumidity 5- 85%non-condensed Approvalsand
certications
Touchscreen: Polyesteronglass,1 millionngertouch operations. Overlay: AutotexF157orF207*.
Powder-coatedaluminum
25-pinD-sub contact,chassis-mountedfemalewith standardlo cking screws4-40UNC
UNC
maximumerror: 77seconds/monthat25°C. Temperature coefcient: -0.034±0.006ppm/°C Rechargeablebattery.
Normal: 0.4A Maximum: 0.9A
CCFLbacklight lifetimeat theambienttemperatureof +25°C:>50,000h.
131.5x 98.6m m
CE:The powersupplymustconformwiththerequirements accordingtoIEC60950andIEC 61558-2-4. ULand cUL:Thepowersupplymustconformwith the requirementsforclassIIpowersupplies.
Verticalinstallation: 0°to+50°C Horizontalinstallation: 0°to +40°C
Informationisavailableon thewebsite
www.beijerelectronics.com
2
*SeesectionChemicalResistanceformoreinformation.
BeijerElectronics, MAEN012A
14
Chemical Resistance

5 ChemicalResistance

5.1 MetalCasing

The frame andcasing material is powder-coated aluminum. This powder paint withstands exposure to the following chemicals without visible change:
Aceticacid 10% Phosphoricacid4% Citricacid10% Phosphoricacid10% Diesel Seawater Distilledw ater Sodiumchloride2% Edibleoil Sodiumchloride20% Fueloil Sulphuricacid 20% Hydrogenperoxide3% Tapwater
The powderpaint shows limited resistance to the f
ollowing chemicals atroom
temperature:
Butanol Nitricacid3% Hydrochloricacid5% Nitricacid10% Isopropylalcohol Phosphoricacid43% Na-hypochlorite10% Turpentine
Note:
Ifexposureto anyofthe abovechemicalsisdemanded,itisrecommendedtorsttest thechemical onan“invisible”spotofthemetalcasing.
Thepowderpaintshowslittleornoresistancetothefollowingchemicalsatroom temperature:
Aceticacid, conc. Methyl-ethylketone Toluene Acetone Nitricacid 30% Trichlorethylene Ammonia5% Phenol Xylene Ammonia,conc. Sodiumhydroxide5% 97octanunleadedpetrol Ethylacetate Sodiumhydroxide30% 98octanle ad edpetrol
BeijerElectronics, MAEN012A
15
Chemical Resistance

5.2 TouchScreenandOverlay

5.2.1 AutotexF157/207

Autotex F157 or F207 covers the overlay surrounding thetouch screen.
SolventResistance
Autotex F157/F207 withstands exposure of more than 24hours duration under DIN42115Part2tothefollowingchemicalswithoutvisiblechange:
Acetonitrile DieselDowney/Lenor Ajax/ Vimin solution EthanolPotassiumferricyanide Alkalicarbonatesolution1Glycerine Potassiumhydroxide
Ammonia(<40%) Aceticacid (<50%) Gumption Arielpowderinsolution
1
Bleach Castoroil Methanol Trichloroaceticacid
Causticsoda(<40%) Cuttingoil Parafnoil Windex Cyclohexanol Persilpowderinsolution1Wisk Diacetonealcohol Petroleumspirit
1
Extremelyfaintglossingofthe texturewasnoted.
1
1
Glycol PureTurpentine
1
1
Hydrochloricacid(<36%) Sulfuricacid (<10%) Linseedoil Tomatoketchup
Nitricacid (<10%) WhiteSpirit
1
Phosphoricacid(<30%)
(<30%)
SBP60/95
(<50%)
1
-
1
1
Autotex withstands DIN 42 115Part 2 exposure of up to1 hour duration to glacial acetic acid withoutvisible change.
Autotex is no
t resistant tohigh pressure steam at over 100 °C or the following
chemicals:
Concentratedmineralacids Benzylalcohol Concentratedcaustic solution Methylenechloride
OutdoorUse
In common withall polyester based films AutotexF157/F207 is not suitable for use in conditions of long term exposure to directsunlight.
BeijerElectronics, MAEN012A
16
Chemical Resistance

5.2.2 TouchScreenSurface

Thetouchscreensurfaceonthepanelwithstandsexposuretothefollowing solvents without visible change:
Solvents Time
Acetone 10minutes Isopropanol 10minutes Toluene 5 hours
5.2.3 AutoexEB
It isrecommended to use the Autoflex EB touch display protection film, that can be ordered from BeijerElectronics.
SolventResistance
Autoflex EB withstands exposure to the same chemicals as Autotex F157 or F207 according to section AutotexF157/207.
OutdoorUse
In common withall polyester based films Autotex EBis not suitable for use in conditions of long term exposure to direct sunlight.
BeijerElectronics, MAEN012A
17
Hardware Tests

6 HardwareTests

Before the operator panels are approved for market introduction, theyare tested by independent authorities. The iX Panelsare examined by several authorities before being approvedfor market introduction. All operator panels are designed to fulfill standards such as CE. The quality policy and environmental policy place demands on all suppliersand subcontractors.
The manufacturer performs extensive hardware testing before an operator panel is approved. Some tests are performed byexternal testing companies, such as the SwedishNational Testing andResearch Institute. All operator panels are submitted to testingbefore leaving the manufacturer.
BeijerElectronics, MAEN012A
18
Hardware Replacement

7 HardwareReplacement

This section containsinstructions on how to replace operatorpanel hardware. Only componentsincluded in the latest billof material and spareparts list are allowed. See Available Spare Parts for iX Panel TA70.

7.1 ModeSwitches

The iX Panel TA70 has fourmode switches (DIP switches) located on the rear side of the operatorpanel.
1 2 3 4
MODE
ON DIP
10/100
EXPANSION
RS232
COM 2
24V DC
1
1 2 3 4
MODE
ON DIP
CF CARD
BUSY
COM 1
RS422
RS485
Warning:
Themodes belowaretobeusedwithcaution.
Themodeswitcheshavethefollowingfunctions: 1=ON,0=OFF Each letter in“MODE” has a corresponding mode switch.
MODE Description
0000 “Runmode” -bootsCE,normaloperation. 0010 Notused. 0100 Notused. 1000 ServiceMenumode,theservicemenuforthesystemprogramis
shown. Allowsthe usertosetIPconguration,erasethe project,
calibratethe touchscreenetc. SeesectionServiceMenufordetails. 1100 Notused(runmode). 1110 Selftest. xxx1 Not used.
To change mode switches, follow the steps below:
1.
Disconnect powerfrom the operator panel.
2.
Set the mode switches using a ballpoint pen.
3.
BeijerElectronics, MAEN012A
nnect power to the operator panel.
Reco
19
Hardware Replacement

7.2 Cables

Mostoftheoperatorpanelsusethesametypeofflexcableconnectors.
connector flanges
Flex cable connector
To release the flex cables fromthe connector, gently push the two flangeson the cable connector towards the flex cable.
Note:
Theconnectorsmustbeunlockedonbothsidesbeforeremovingthecable,otherwise theexcablemaybedamaged.
BeijerElectronics, MAEN012A
20
Hardware Replacement

7.3 ReplacingtheRearCover

The followingis needed:
Anewrearcover,seeAvailable Spare Parts for iX Panel TA70
AtorxT10screwdriver
Note:
MakesuretouseadequateESDprotection.
Follow the stepsbelow to replacethe rear cover:
1.
Poweroff the operator panel.
2.
Remove the rear cover of the operator panel by loosening the 4torx screws.
4 x torx screws
3.
Re-assemble withthe new rear coverin reverse order.
BeijerElectronics, MAEN012A
21
Hardware Replacement

7.4 ReplacingtheDisplay/Display Cable

The followingis needed:
A new display including plastic frame and display cable, see
Available Spare Parts for iX Panel TA70
AtorxT10screwdriver
Note:
MakesuretouseadequateESDprotection.
Followthe steps belowto replace the display/displaycable:
1.
Poweroff the operator panel.
2.
Followthe instructions under Replacing the Rear Cover to remove the rear cover.
3.
Disconnect the two flex cables from thepower card, according to the illustration below, and removethe two plastic nuts that hold the powercard in place.
plastic nut
flex cables
plastic nut
4.
Lift the powercard and gently remove thebacklight cable from the rear side.
guide pins
backlight cable
guide pins
snap-in closure for plastic frame
5.
Gently loosen the complete plastic frame anddisplay from the front plate. Scrap the displayand frame.
6.
Mountthe new display/display cable and frame and re-assemblethe complete operator panel. Make sure theguide pins ontheframeareproperlyfastenedin theholesinthefrontplate.
BeijerElectronics, MAEN012A
22
Hardware Replacement

7.4.1 SelfTestoftheDisplay

To perform a self test of the display, follow the steps below:
1.
Start theoperator panel in a self test mode(see table in the Mode Switches sec­tion).
2.
Go to the display test, byr unning or skipping thepreceding tests. Verify that the display works.
3.
If the screendoes not work, try fault tracing, seethe Fault Tracing section.

7.4.2 CalibratingtheTouchScreen

Followthe steps below to calibrate the touch screen:
1.
Set the MODE switches to the correct positions in order to enterthe Service Menu mode (see table in the Mode Switches section).
2.
Switchon the power and followthe instructions.
3.
Poweroff the operating panel.
4.
Reset all MODE switches to theOFF position.
BeijerElectronics, MAEN012A
23
Hardware Replacement

7.5 ReplacingtheCompleteFront

The followingis needed:
Anewfront,seeAvailable Spare Parts for iX Panel TA70
AtorxT10screwdriver
Note:
MakesuretouseadequateESDprotection.
Followthe steps belowto replace the completefront of the iX Panel TA70:
1.
Poweroff the operator panel.
2.
Followthe steps 1-3 and 5 in the Replacingthe Display/Display Cable instruc­tions, but in step 3, do not remove thedisplay cable .
3.
Attach the new front.
4.
Re-assemble the unit.
BeijerElectronics, MAEN012A
24
Hardware Replacement

7.6 ReplacingtheBacklight

If the backlight of the iXPanel TA70is broken, the entire display must be replaced. To replace the display you will needa new display including plastic frame and dis­play cable, see the Available Spare Parts for iX Panel TA70 section. For information about changingthe display, see theReplacing the Display/Display Cable section.
BeijerElectronics, MAEN012A
25
Hardware Replacement

7.7 AvailableSparePartsforiXPanel TA70

Ordernumber Description
601009274 COMPLETEFRONT
Includingfrontcover,touchoverlay, gasketsandlabels
601009014 DISPLAY
Includingframeandcable
N/A BACKLIGHT
Isnot replaceable. Changethecompletedisplay. 601009015 DISPLAYCABLE 321099040 POWERCONNECTOR 601009011 REARCOVER 601009003 CFCOVER 601009001 MOUNTINGBRACKETS 601009024 TOUCHPROTECTIONSHEET 601009294 FRONTLABEL 601009120 COMPLETEBOX 601009008 TESTPLUGETHERNET
EthernetRJ45testconnector 601009006 TESTPLUGRS232
RS232test connector 601009007 TESTPLUGRS422/485
RS422/485testconnector 601009069 TESTPLUGUSBH
USBHosttestconnector
BeijerElectronics, MAEN012A
26
Service Menu

8ServiceMenu

The service menu for theoperator panel can be accessed beforea project is downloaded, or by settingthe mode switches in mode 1000. The location of the mode switches is described in the Mode Switches section.

8.1 ServiceMenuinanEmptyPanel

When no project isloaded in the panel memory,the panel will boot, displayingthe Welcome screen. Press anywhere onthe panel display to enter the service menu.

8.2 ServiceMenuinaPanelwith Project

When a project is loaded in the panel memory, the panel w ill automatically start to execute theproject. To display the service menu atboot-up:
1.
Disconnect the powersupply from the panel.
2.
Set the mode switches in mode 1000 (Service Menu mode).
3.
Connect the powersupply. When the panelboots up it will suggest togo into the Touch Calibrate mode.
This ensures that it willbe possible to recover froma bad calibration.
4.
Pressanywhere on the panel display to interrupt thetimer and to enter the service menu.
5.
Make desiredsettings in the service menu.
6.
Disconnect the powersupply from the panel.
7.
Set themode switches in mode 0000 (Run mode).
8.
Reconnect thepower supply.

8.3 ServiceMenuOptions

The followingoptions are available in the Ser vice Menu:

8.3.1 IPSettings

The panel hastwo built-in Ethernet ports, accordingto the drawing below. For each port, selectto obtain an IP address automatically viaDHCP, or specify an IP address for the first Ethernet port.
Port 1
The port that is currently connected is recognized by a*.
BeijerElectronics, MAEN012A
Port 2
27
Service Menu

8.3.2 Date/Time

Use the Date/Time Settingsdialog to set the time zone, date and timefor the panel.

8.3.3 EraseProject

The erase functionwill detect if the project is located in the panel memory or on a memory card. Pressing Erase Project will completely removethe project and all its components from the panelmemory/the memory card.

8.3.4 TouchCalibrate

SelectTo uc h Ca li br at e if the touch screen needs to be calibrated. Follow the instructions on the screento perform a calibration.
BeijerElectronics, MAEN012A
28
Hardware Self Test

9 HardwareSelfTest

The self testprogram can be used to test aspects of operator panel functionality and thecommunication ports. To run the testyou will need:
Test plugs, including two Ethernet test p lugs; see Te st pl u g d ra wi ng .
24 V DC, min. 3 A.
SD card
Followthe steps below to run the self test programon the operator panel:
1.
Poweroff the operator panel.
2.
Go tothe self test. Set the mode switches tothe self test positions,see the table in the Mode Switches section.
3.
Power on the operator paneland follow the instructions at the bottom of the display.
4.
When using thetest plugs, make sure the + 5 V DC LED on the RS422 test plug and theLED of the RS232 test plug areon.
5.
When the selftest is finished, power off the operator panel and set all mode switches tothe OFF position.
If an error occursduring the self test, try to fault trace. See Fault Traci
ng.
BeijerElectronics, MAEN012A
29
Hardware Self Test

9.1 SelfTestItems

The following tests, of whichsome may be dismissed, are performed:
Maybe
Test item
RS422(short-circuit) No 25pinD-sub plug(male);
RS232(short-circuit) No 9pinD-subplug(female);
EEPROM No ­CoreTemperature No ­BoardTemperature No ­Touch Yes ­Buzzer Yes ­Power LED Yes ­Backlight Yes ­Display Yes ­SDCard Yes SDcardmustbe
BurnIn (loopwith 6repeating tests)
CoreTemperature ­BoardTemperature ­Ethernet1 RJ 45 plug Ethernet2 RJ 45 plug RS422 25pinDSUB plug(male) RS232
dismissed Plug
maynot beconnected
mayno t bepluggedin
connected
Yes
9pinDSUBplug(female)
BeijerElectronics, MAEN012A
30
Additional InstallationTips

10 AdditionalInstallationTips

When experiencing communication problems in for example noisy environments or when operating close to temperaturelimits, the following recommendations are to be noticed.

10.1 GroundingtheOperatorPanel

Door
Operator panel
1
Ferrite core
3
2
5
6
4
Mounting plate in the cabinet
Power supply
24 V DC
5350
The operator panel’s mounting clamps do not provide a securegrounding connection between the panel and the device cabinet, see 1 in drawing above.
1.
Connect a 2.5 mm and the panel chassis, see 2 in drawi
2.
Connect a 6 or 4mm
2
wire betweenthe ope
rator panel’s quick-connect plinth
ng above.
2
wire or groundingbraid between the panel’s chassis and
the closest grounding point on thedoor, see 3 in drawing above.
3.
Connect a strong but short grounding braid between the door and the device cabinet,see 4 in drawing above.
4.
Twist the cables onto the24 V DC feed, see 5in drawing above. 2 turns aroundthe ferrite core provide4 times the suppression of 1turn. 3 turns aroundthe ferrite core provide9 times the suppression of 1turn.
A ferrite core suppresses disturbances to the 24 V feed, see 6 in drawing above.
Note:
Thegroundingwiress hould beshortandtheconductorshouldhavealargearea. Along, thingroundingwirehasaveryhighimpedance(resistance)athighfrequencies andwill notguidedisturbancestotheground. Multi-wireconductors arebetterthansinglewireconductorswiththesamearea. Abraidedconductorwirewith thesameareaisevenbetter. Thebestisashort,thick groundingbraid.
BeijerElectronics, MAEN012A
31
Additional InstallationTips

10.2 EthernetConnectioninthePanel

Industrial Ethernet
RJ45
RJ45
RJ45
RJ45
Operator panel
RJ45
1
2
Operator panel
RJ45
Operator panel
RJ45
Operator panel
RJ45
5351
Shielded
0.1 uF 250 V
3
4
1-1 2-2 3-3
8-8
Short and unshielded
5
In some industrialunits for Ethernet, the RJ45 contact’s shield is connected to the chassis via a capacitor, see1 in drawing above.
The operator panel’s Ethernet shield is directly
connected to the chassis, see 2 in
drawing above.
1.
Check whether the other Ethernetunit has its shield directly grounded or grounded via a capacitor.
Note:
Inmanycases,connecting theshieldedEthernetcablingtothechassisatbothendsis inappropriate. Humo r groundingloopscanoccur. Unshielded cablingmayevenresult infewercommunicationerrors.
A good solution may beto use a shielded Ethernet cable, but toconnect the shield at one end only.
One option isto break the shield, see 3 in drawing above. A more elegantmethod is to expand the shielded Ethernet cabling with a piece of
unshielded Ethernetcable, see 4 in drawing above. You can ground the shield via an external 0.1 uF/250 V plastic capacitor, see 5 in
drawing above. This will connect theHF transients to the ground.
BeijerElectronics, MAEN012A
32
Additional InstallationTips

10.3 ToAchieveBetterEMCProtection

Initially,use the original cabling from BeijerElectronics primarily.
Use shielded cables for RS232 communication.
Use twisted pair andshielded cabling for RS422 and RS485.
Use the cabling intended for the bus type; Ethernet,Profibus, CC-Link,
CAN, Device Netetc.
Install and connect according to applicablespecifications for the relevant bus
standard.
Use shielded cabling forEthernet, preferably with foil + braided shield.
D-sub covers should be shielded, and the shield shoul d be connected to the
cover 360° where the cable comes in.
Connect the shield at both ends.
Shielded cable
0.1 uF/250 V
Ground plane 1 Ground plane 2
Ground plate Ground plate
Not same potential
in another building
5352
With longer distances, thereis a risk that the ground potential may bedifferent. In that case,the shield should only be connected at oneend. A good alternative is to connect the ot her end of the shield to the ground viaa 0.1 uF/250 V plastic capacitor. Both endsare then connected to the groundin terms of HF, but only connected to the ground at one end in terms ofLF, thusavoiding the 50 Hz grounding loops.
Metal cabinet Metal cabinet
Terminal or connector Terminal or connector
Cable clamp in steel
Short distance
EMC cable gland Plastic cable gland
Shielded cable Shielded cable
1.
Usean EMC cable gland or regular plastic cable gland, removethe outer jacket
5353
and connect theshield to the installation plate with a360 ° metal cable clamp.
2.
Place the 24V DC and communications cabling in one cable trunk/cable duct and 230/380 V AC in another. If the cables need to be crossed, cross them at 90 ° only. Avoidcombining the cabling for stronger 24V DC outputs with the communication cabling.
Ferritecores that are snappedonto the shielded cabling m ay remove minor disturbances. Large ferrite pieces that aresnapped onto unshielded cabling and where the wiresgo 2-4 times around the cores are approximately 5-25 timesmore efficient.
BeijerElectronics, MAEN012A
33
Additional InstallationTips

10.4 AmbientTemperature

The maximum ambient temperature for the operator panel is providedin the specifications. The ambient temperature refers to the temperature inthe device cabinet which cools the panel’s electronics.
Top 50 °C inside
Operator panel
30 °C outside
Middle 45 °C inside
Bottom 40 °C inside
Power
Power
Power
Axial fan 120 x 120 mm
Airflow
5354
Inmostcases,theambienttemperaturefortheoperatorpanelissignificantly higher than the device cabinet’s ambient temperature.
If the cabinetis tall and there area number of hea temperature at thetop of the cabinet will be con theoretical temperature increasethat would sensitivetoheat. Thelifespanofanelectro ° increase in temperature. A 15-20 ° tempera
t-generating devices,the
siderably higher than the
be expected. All electronics are
lytic capacitor iscut in half with an 8-10
ture increase results in a quarter of the
lifespan etc. Rittal has a good program for estimating the anticipated averagetemperature in
the cabinet as well as a large program for controlling the temperature in the device cabinet.
An enamel-coated steelcabinet has
a radiant heat value of 5.5 W/m
2
and degrees
C. Installing a faninside the cabinet will even out the temperature, while moving air
provides considerably better cooling than still air. A suitable fan is a120 x 120 mm axial fan, availablein 24 V DC, 115 and 230 V AC.
Installthefansothatitsit operator panel. If the fan i ambient temperaturewill
s in thecooler area and will blowcold air against the
s mounted at the top and sucks air upwards,the fan’s be higher = shorter lifespan.
Agoodfanwithaball-bearingmountinghasanexpectedlifespanofatleast 40,000 hours (nota guaranteed lifespan) at 40 °C.This corresponds to at least4 years of continuoususe. If a thermostatis installed, the fan only needs tocome on when needed.
Large graphic termi lighting is off. Th
nals draw only one fifth of thecurrent when the background
e loss effect drops from e.g. 25 Wto only 5 W.
The operator panel’s loss effect = supply voltagex current. Virtuallyno power goes to external users and no loss effects due to inputs.
BeijerElectronics, MAEN012A
34

10.5 Safety

Most of the operator panels are fed with 24 V DC.
Power supply
1
2
3
230 V AC to 24 V DC
Power supply 230 V AC to 24 V DC
Power supply 230 V AC to 24 V DC
230 V AC
+24 V
0 V
4
+24 V
0 V
4
Distance?
+24 V 0 V
4
Operator panel
Operator panel
Operator panel
Small controller with expansion unit
COM1
COM100
Ch0 Ch1
Ch100 Ch101
5355
Additional InstallationTips
Ifyouuseapowersupplythatmeetssafetystandardsandonlyfeedstheoperator panel, there is no problem. See 1 in drawing above.
However,ifyouhavea24Vunitthatalsofeedsotherunits,thereisreasontobe cautious, see 2 indra wing above. The operator panel doesnot have insulation that meets safety requirementsin the event ofa potential short circuit between230 V AC and 24V DC. It is assumed that the 24V feed is secure, for example, SELV according to EN 60950 (protection against electric shock) and UL 950.
Example:
Hereis anexamplethatexplainswhyasecure24V DCfeedcanberuinedbymixing24 Vrelaycontactswith230VACrelaycontactsinasmallercontroller. Checkthatthe “clearancesand creepagedistancesbetween24VDCand230VACfulllEN60950orUL 950”. Ifnot, inputaseparate24V unitintotheoperatorpanel.
If there is a substant AC, it is OK to use the
ial distance between therelay contacts for 24 V DC and230 V
same 24 V devices for all feeds. See 3 in drawing above.
Connect 0 V on the 24 V feed to the ground, see4 in drawing above. This offers three advantages:
Safety is increa
connection or s
Tr a n si en t s o n
No risk that th
is not unusua
sed. The24Vfeedwillnotbeliveintheeventofafaulty
hortcircuitbetween0V(24V)and230Vphase.
the 24 V feed are connected to the ground.
e 24 V feedis at a high level in relationship to the ground. This
l since there is high static electricity.
BeijerElectronics, MAEN012A
35

10.6 GalvanicIsolation

r
Additional InstallationTips
+24 V DC
DC/DC galvanic isolation
Filter
0 V
1.5 m
Internal electronic
VCC
0 V (GND)
RS232RS422/485
USB
USB
DC/AC
Ethernet
CFL
5356
The operator panelhas galvanic isolation against the 24 V DC feed but no galvanic isolation between the communication ports for RS232, RS422/485 and USB. Only the Ethernetconnection has galvanic isolation.
Operator panel Modular controller Printe
RS422 RS232 USB
**
* *
Not same ground potential
* = Internal 0 V (GND) connection
When a PC is connected to the panel, the panel’s internal 0V (G
*
Power CPU COM COM2
***
*
PCPC
5357
ND) will be
connected to the protective groundvia the PC. A number of USB devices can have the shield connected together with the
protective ground. Here, the panel’s 0 V (GND) is connected to the protective ground when, for example, a USB memory stick, keyboard or similar device is plugged in.
If a number of units are connectedthat have a 0 V a these are connected to various grounding poin problems. Grounding currents go through com of the controller, and internally in th
e operator panel, and can cause errors.
nd a ground c onnection, and
ts, there is a substantial risk of
munication cables, the rearplate
Use e xternal units to improvecommunication and achieve galvanic isolation. Westermo has good industry-standard insulators that arealso insulated from the 24 V DC feed.
Note:
Itis veryimportanttomakesurethatthe 24Vfeedintheexternalinsulation unitisnot connectedtooneofthe communicationoutlets. Ifitdoesnothav e 100%insulation againstthe24Vfeed,disturbancesandgroundingcurrentsfromthe0Vonthe 24V sidewill disruptcommunication. Usingthis typeofunitsolvesoneproblembutcreatesalargerproblem! Asubstandard installationmayworknow,but problemsmay arisewhenotherdevicesareconnected.
BeijerElectronics, MAEN012A
36
Additional InstallationTips

10.7 CableandBusTerminationRS485

Use sh ielded and twisted pair cable. The pair capacitance may not exceed52.5
2
pF/m and areaat least 0.25 mm
(AWG24), if you want to usethe maximum
transfer distance and maximumtransfer speed.
0 V, the reference voltage for communication should be included in
the cabling. With two-way communication use two pairs; one pair for communication and one pairfor 0 V.
The shield must be grounded atone end. The other end is usually grounded,
but with longer d istances or whenthere is a difference in the ground potential, theshieldshouldbeconnectedtothegroundvia0.1uF/250Vplastic capacitor to prevent ground currentin the braided shield. A number of manufacturers recommendthat the shield be groundedat each node. Various manufacturers have differentsystems for bus termination. The RS485 standard does notdescribe how the “FailSafe” function would be carried out, justthatthesystemshouldbeabletohandletheerror.
Depending on therecipients’ design, the bus wires may be on the same level or require pull-upor pull-down to ensure that nofaulty signals are detected when the bus is in resting mode (all transmitters are disconnected).
Inside operator panel
+5 V
0 V
1 23
1 K 120 ohm 120 ohm 1 K
+5 V
(120 ohm)
14
1 K
2
15
6
19
1 K
7 8
0 V 0 V
4
55
17
50
Operator panel RS422
1 2 3 4 5 6 7 8
CAB8CAB8 Bus
2 15
3 16
17 4
14
+5 V
VCC
8
0 V
7
0 V
VCC
1 K 120 ohm
1 K
RS485
1 2
3 4
5 6
Shield
7 8
Bus termination
0 V 0 V
5358
Some (older) operatorpanels had pull-up and pull-down resistance except for the actual bus termination at 120 ohm, similar to Westermo and Profibus. See 1 in drawing above.
Newer panelshave another type of recipient, so-called built-in “Fail Safe”,where simple bus termination resistanceis sufficient. See 2in drawing above.
If other nodes onthe RS485 network require pull-up and pull-down and the operator panel isat one end of the loop,one of the following procedures can be carried out:
Connect two 1k/0.25 W resistorsin the 25-pole D-sub contact. See 3 in
drawing above. Set jumperpins 6-19.
Use CAB8. It offers the option of bus termination with pull-up/-down. It
isalsoeasytoconnectthebuscableviathescrewterminalblock. See4in drawing above.
BeijerElectronics, MAEN012A
37
Fault T racing

11 FaultTracing

This section includesdifferent fault scenarios and steps to followto trace the fault.
TheiXPanelTA70isnotworkingproperly,andthe powerLEDis off
1.
Isthepowervoltagecorrect?
2.
Does the powersupply deliver enough current?
3.
Check the fuse.
4.
Check the power card.
5.
Is thepower card correctly mounted?
TheiXPanelTA70isnotcommunicatingwiththe controller
1.
Check the communication cable between the units.
2.
Check that the operator panelhas a controller driver downloaded.
3.
Checkthatthecorrectcontrollerdriverisused.
4.
Check the communicationports on the CPU board.
TheiXPanelTA70isworkingbutthebacklightisoff
1.
Check the backlight dimming.
2.
Check that the backlight is connected to the power card.
3.
Replace the backlight according tothe Replacing th
4.
Check the DC/AC onthe power card.
eBacklightsection.
TheiXPanelTA70isnotworking,thebacklightisoff butthepowerLEDison
1.
Check the backlight dimming.
2.
Check the CPUboard for burned components.
3.
Download new firmwareto the operato
rpanel.
TheiXPanelTA70doesnotincludethelatestimage
1.
Check the versionsincluded with the operator panel.
2.
Make sure to save a copy of the project tothe PC.
3.
Download anupdated image wi in the System Programsectio
th the Image Loaderand follow the directions
n.
BeijerElectronics, MAEN012A
38
Thetouchscreenismalfunctioningorisnot respondingatall
1.
Re-calibrate the touch screenaccording to the Calibrating the Touch Screen sec- tion.
2.
Check that the flex cableis correctly fitted.
3.
Replace the display of the operator panel according to the
Replacing the Display/Display Cable section.
4.
Check the touch interface on the powercard.
Linesindisplayhavewrongcolororthedisplay pictureisshifted
1.
Check if the display hasa wide vertical or horizontal area across the display. It should be at least2-3 cm wide with a grey or black color. See
Replacing the Display/Display Cable for instructions on howto correct this.
2.
Make sure the display cable is correctlyfitted.
3.
Make surethe display cable is not folded or damaged in any way. Replace the display cableaccording to the Replacingthe Display/Display Cable section.
Fault T racing
BeijerElectronics, MAEN012A
39
Software

12 Software

This chapter describeshow to maintain and update the softwarein the iX Panels. The chapter includes a general description of the operator panel software and instructions about how t o upgrade the software and load projects andsystem programs.

12.1 GeneralInformationabout Software

The software requiredto run and maintain the operator panelsis found on the software USB stick. It isalso available through your local distributor.
The software istested by the manufacturer’s own testing department before market introduction is approved. The test procedure is closelyintegrated with the development process. The test group works in close concert withthe developers andisISEBCertifiedforSoftwareTesting.

12.1.1 SoftwareProducts

The followingsoftware products are used:
iX Developer
iX Developer is used for creating application projects for iXPanels and their accessories.
Remote AccessViewer
Remote AccessViewer is a program for remote ac It ispossible to access, reflect and control t client programRemote Access Viewer (freew server (Remote Accessfunction) in th
System Program
The iX Panel TA70 is delivered with an image (operating system) pre-stored in the operator panel memory.
eiXPanels.
cess and control of the iX Panels.
he iX Panels from a PC usingthe VNC
are) together with thebuilt-in VNC
BeijerElectronics, MAEN012A
40

12.2 UpdateSoftware

When an update is available, an e-mail is sent to the distributors. The software is also available onthe manufacturer’s web site.
Theupdateshouldbeinstalledbyqualifiedpersonnel.

12.2.1 iXDeveloper

iX Developer is not a freeware product. A demo versioncan be downloaded from www.beijerelectronics.com. To update iX Developer, an accredited iX Panels dealer must becontacted.

12.2.2 RemoteAccessViewer

This software isincluded on the iX Developer USB stick. To update the Remote Access Viewer, go to www.beijerelectronics.com and select
Support/Downloads inthemenu. BrowsethesoftwarefoldertolocateRemote Access Viewer. Run the .exe file and followthe instructions.
Software

12.2.3 SystemProgram

An upgrade of the complete software package is sometimes needed to take advantage of new functionality.
The upgrade is done by running theImage Loader execu IML_TA70–150_bxxx.exe. The Image Loader applica through the upgrade.
Two upgrade options are available:
Upgradingthe System Program Usinga USB Memory S
Upgradingthe System Program via Ethernet
Whentheupgradeisfinished,theoperatorpanelwillreceivethedefaultIPaddress
192.168.1.1. Followthe instructions on the screen afterstartup to changethe IP
address.
Note:
TheImageLoadersoftware isonlyintendedforcustomersandpartnersthathavean operatorpanel. Nootherdistributionisallowed.
Note:
Whenupgradinganoperatorpanel,itisimp ortantto ensurethatpower isnot interruptedduring theupgrade.
table file,
tion will help andguide you
tick
BeijerElectronics, MAEN012A
41
Requirements
Upgrading of the operator panel system program requiresthe following:
APC
An Ethernet connection between the PC and the operator panel or an empty
USB memory stick.
The Image Loader executable file from the web site
UpgradingtheSystemProgramUsingaUSBMemory Stick
When upgrading the system program using a memory stick, you can select to delete or to keepthe project in the operator panel.
Followthe steps below:
1.
Connect an empty USB memory stick to your PC.
2.
Double-click on the executable Image Loader file.
3.
Select the driveof the desired USB stick and click Create. The files arecopied to the USB stick.
4.
Connect the USB memory stick tothe operator panel.
5.
Cyclethepowertoinitiatetheupgrade.
Software
UpgradingtheSystemProgramviaEthernet
When upgrading the system programvia Ethernet, the project in the operator panel is retained.
Followthe steps below:
1.
Make sure tha t your PC and the operator panelare connected via Ethernet.
2.
Double-click on the executable Image Loader file.
3.
Enter the IP address of the operator panel.
4.
Click Update, and followthe instructions. The files aretransferred to the operator panel. The panel will reboot
automatically when the transfer is finished.
BeijerElectronics, MAEN012A
42
Environmental Aspects

13 EnvironmentalAspects

This chapter includes info rmation about theenvironmental impact of iX Panels. More information can be found on the manufacturer’s web site.

13.1 GeneralEnvironmentalAspects

The manufacturer’s activities meet internal requirementsas well as those of the SS-EN ISO 9001:2000and SS-EN ISO 14001:2004 internationalstandards.

13.2 EnvironmentalImpactofthe OperatorPanels

13.2.1 MechanicalComponents

The aluminum and stainless steel used in the mechanical components are judged to be non-environmentally hazardous. The expanded rubber packing for the front and the expanded polyethylenepacking for the display contain an adhesivethat is not classified as environmentally hazardous.
Screws may haveundergo ne the following surface treatments: Bright nickel-plating or bright zinc-plating. Themembranekeyboardismadeof polyester with silver wiring. On some models the keyboard contains LEDs.
Display framesand CF covers are madeof halogen-free plastic, PC/ABS.

13.2.2 Electronics

CircuitBoard
Note:
AlloperatorpanelsareRoHScompliant.
The electronics are complex andalmost all elements of theperiodic table are represented.
Display
There is a separate circuit board for the display. The liquid crystals in thedisplay are cyclohexanecompounds. The fluorescenttube contains mercury and lead solder.
Batteries
The operator classified a (1997:645
panel contains a buttoncell lithium battery. The battery is not
s environmentally hazardousby the Swedish Battery Ordinance
).
BeijerElectronics, MAEN012A
43
Environmental Aspects

13.3 Recycling

The operator panelsconsist largely of aluminum. It is a greatadvantage in terms of both resources andthe environment if it can be recycled. Make sure that operator panels taken out ofservice are sent tofacilities for electronic scrap.
The manufacturer’s electronic waste is recycled by Stena Technoworld AB. Aluminum front/rearcasings and othercovers can be removed and recycled. Plastic display frames and CF covers must be recycledas hard plastic. The circuit board containsmany valuable metals and should thereforebe recycled.
Remove the lith ium battery. Electrolytic capacitors and displays are currently not classified as hazardouswaste, but may be harmful tohealth and the environment.
The electrolytic capacitors should behandled as per Handbook 2001:7 (NFS) and displays asper NFS 2001:8.
Thefluorescenttubemustbehandledashazardouswaste. The packagingis made from wood fiberand shouldberecycled. Thelargeprinted
label on the front,however, must first be removed as it is made of PVC vinyl. The label and theplastic bag for the bracketsare recycled as soft plastic.
The manufacturer isa member of the REPAregister. The protective film on the front is recycledas soft plastic. When theoperator panel is no longer useful it can be returnedto the manufacturer for environmentally responsible recycling. Contact the company for further information.

13.4 EnvironmentalImpactReport

An operator panel impactsthe environment through its function, i.e., controlling industrial equipment. The energy and the scrapped parts that can be saved with efficient management meanthat the operator panel contributes to reduced environmental impact.
Listed below are examples of how you can reduce environmental impact during operator panel use.
Switch the system off when not in use.
Use green electricity.
Use energy-saving options, e.g.,turn off the backlight to both save en ergy and
reduce wearon the fluorescent tube.
Ifpossible, reduce the backlight brightness to reduce energy consumption
and increase fluorescent tube service life.
Supplythe operator panel with 2 effect increases. Ensure that recycled in an environmentall
4 V DC. Ifthe input voltage is lower, the loss
the operator panel, battery, and packaging are
y responsible manner.
BeijerElectronics, MAEN012A