This manual contains detailed information about iX Panel TA70, including
descriptions of variousactions that can be carried out in orderto maintain or
update the operator panelhardware and software.
The manual contains descriptionsof basic maintenance and replacement of
common parts in iX Panel TA70.
The manual assumes thatthe most recent versions of the system program
(firmware) and iX Developer are used.
The followingother manuals are available for i X Panel TA70:
iX PanelTA70installation manual (MAEN009x) for information regarding
installation.
iX Developer reference manual (MAEN831x) for a description of the
configuration tool.
iX Developer user’s guide (MAEN832x) for function-based descriptions.
The information inthis document is subject tochangewithoutnoticeandisprovidedasavailableatthe
time of printing. Beijer Electronics AB reserves the rightto change any information without updating this
publication. Beijer Electronics AB assumes no responsibility for any errors that mayappear inthis document.
Read the entireinstallation manual prior to installing and usingthis equipment. Only qualified personnel
may install, operate or repair this equipment. Beijer ElectronicsAB is notresponsible for modified, altered
or renovated equipment. Because the equipment hasa widerangeofapplications,usersmustacquirethe
appropriate know l edge to use the equipment properly in their specific applications. Persons responsible
for the application and the equipment must themselves ensure that each application is in compliance with
all relevant requirements, standards and legislationinrespecttoconfigurationandsafety. Onlypartsand
accessories manufactured according to specifications set byBeijer ElectronicsAB may be used.
BEIJER ELECTRONICSAB SHALL NOTBE LIABLE TO ANYONE
FOR ANY DIRECT, INDIRECT, SPECIAL, INCIDENTAL OR
CONSEQUENTIAL DAMAGESRESULTING FROMTHE
INSTALLATION, USE OR REPAIR OF THIS EQUIPMENT, WHETHER
ARISING IN TORT, CONTRACT, OR OTHERWISE. BUYER'S SOLE
REMEDYSHALL BE THE REPAIR, REPLACEMENT, OR REFUND
OF PURCHASE PRICE, ANDTHE CHOICE OF THE APPLICABLE
REMEDYSHALLBEATTHESOLEDISCRETIONOFBEIJER
ELECTRONICSAB .
•All maintenance should be performed in a15-30 °C temperature range.
•Any damage tothe operator panel caused by personnelinvalidates the
warranty.
•Contracts with customers s upersede the information in this document.
2.4DismantlingandScrapping
•The operator panel,or parts thereof, should berecycled according to local
regulations.
•The followingcomponents contain substances that mightbe hazardous to
health and theenvironment: lithium battery, electrolytic capacitor, display.
BeijerElectronics, MAEN012A
8
Introduction
2.5ContactandSupport
If you wantto report a fault or have aquestion about the operator panels, please
contact your localsupplier or fill out the form on the web site.
1.
Enter the web site www.beijerelectronics.com and selectSupport.
2.
Select Contact inthe menu. Make sure to provideinformation about type
number, serial number, environmentand an installation description.
The form will besent to the manufacturer’s help deska nd they will answer your
question or registeryour improvement/fault.
To ensure quick resolution, provideas many details as possible in yourreport.
Include the date and time when the problem occurred, a description ofwhat you
were trying to do, thedetailed steps you took that led up to the problem, and
details about any error messages received.
–Connect cable A.
–Connect cable B, using an M5 screwa nd a grounding conductor (as short
as possible) with a cross-section of minimum 2.5 mm
–Connect cable C.
–Connect cable D.
5.
Carefully removethe laminated film over the operator panel display, to avoid
2
.
static electricity that could damage the panel.
BeijerElectronics, MAEN012A
12
Installation
3.2.1ConnectionstotheController
Forinformation about the cables to be used when connecting the operator panel to
the controller,please refer to the help file for the driver in question.
3.2.2OtherConnectionsandPeripherals
Cables, peripheral equipment and accessories must besuitable for the application
and its environment. Forfurther details or recommendations, please refer to the
supplier.
It isrecommended to use the Autoflex EB touch display protection film, that can
be ordered from BeijerElectronics.
SolventResistance
Autoflex EB withstands exposure to the same chemicals as Autotex F157 or F207
according to section AutotexF157/207.
OutdoorUse
In common withall polyester based films Autotex EBis not suitable for use in
conditions of long term exposure to direct sunlight.
BeijerElectronics, MAEN012A
17
Hardware Tests
6HardwareTests
Before the operator panels are approved for market introduction, theyare tested
by independent authorities. The iX Panelsare examined by several authorities
before being approvedfor market introduction. All operator panels are designed
to fulfill standards such as CE. The quality policy and environmental policy place
demands on all suppliersand subcontractors.
The manufacturer performs extensive hardware testing before an operator panel
is approved. Some tests are performed byexternal testing companies, such as
the SwedishNational Testing andResearch Institute. All operator panels are
submitted to testingbefore leaving the manufacturer.
BeijerElectronics, MAEN012A
18
Hardware Replacement
7HardwareReplacement
This section containsinstructions on how to replace operatorpanel hardware.
Only componentsincluded in the latest billof material and spareparts list are
allowed. See Available Spare Parts for iX Panel TA70.
7.1ModeSwitches
The iX Panel TA70 has fourmode switches (DIP switches) located on the rear side
of the operatorpanel.
1 2 3 4
MODE
ON DIP
10/100
EXPANSION
RS232
COM 2
24V DC
1
1 2 3 4
MODE
ON DIP
CF CARD
BUSY
COM 1
RS422
RS485
Warning:
Themodes belowaretobeusedwithcaution.
Themodeswitcheshavethefollowingfunctions: 1=ON,0=OFF
Each letter in“MODE” has a corresponding mode switch.
•Anewrearcover,seeAvailable Spare Parts for iX Panel TA70
•AtorxT10screwdriver
Note:
MakesuretouseadequateESDprotection.
Follow the stepsbelow to replacethe rear cover:
1.
Poweroff the operator panel.
2.
Remove the rear cover of the operator panel by loosening the 4torx screws.
4 x torx screws
3.
Re-assemble withthe new rear coverin reverse order.
BeijerElectronics, MAEN012A
21
Hardware Replacement
7.4ReplacingtheDisplay/Display
Cable
The followingis needed:
•A new display including plastic frame and display cable, see
Available Spare Parts for iX Panel TA70
•AtorxT10screwdriver
Note:
MakesuretouseadequateESDprotection.
Followthe steps belowto replace the display/displaycable:
1.
Poweroff the operator panel.
2.
Followthe instructions under Replacing the Rear Cover to remove the rear
cover.
3.
Disconnect the two flex cables from thepower card, according to the
illustration below, and removethe two plastic nuts that hold the powercard
in place.
plastic nut
flex cables
plastic nut
4.
Lift the powercard and gently remove thebacklight cable from the rear side.
guide pins
backlight cable
guide pins
snap-in closure for plastic frame
5.
Gently loosen the complete plastic frame anddisplay from the front plate.
Scrap the displayand frame.
6.
Mountthe new display/display cable and frame and re-assemblethe complete
operator panel. Make sure theguide pins ontheframeareproperlyfastenedin
theholesinthefrontplate.
BeijerElectronics, MAEN012A
22
Hardware Replacement
7.4.1SelfTestoftheDisplay
To perform a self test of the display, follow the steps below:
1.
Start theoperator panel in a self test mode(see table in the Mode Switches section).
2.
Go to the display test, byr unning or skipping thepreceding tests. Verify that
the display works.
3.
If the screendoes not work, try fault tracing, seethe Fault Tracing section.
7.4.2CalibratingtheTouchScreen
Followthe steps below to calibrate the touch screen:
1.
Set the MODE switches to the correct positions in order to enterthe Service
Menu mode (see table in the Mode Switches section).
2.
Switchon the power and followthe instructions.
3.
Poweroff the operating panel.
4.
Reset all MODE switches to theOFF position.
BeijerElectronics, MAEN012A
23
Hardware Replacement
7.5ReplacingtheCompleteFront
The followingis needed:
•Anewfront,seeAvailable Spare Parts for iX Panel TA70
•AtorxT10screwdriver
Note:
MakesuretouseadequateESDprotection.
Followthe steps belowto replace the completefront of the iX Panel TA70:
1.
Poweroff the operator panel.
2.
Followthe steps 1-3 and 5 in the Replacingthe Display/Display Cable instructions, but in step 3, do not remove thedisplay cable .
3.
Attach the new front.
4.
Re-assemble the unit.
BeijerElectronics, MAEN012A
24
Hardware Replacement
7.6ReplacingtheBacklight
If the backlight of the iXPanel TA70is broken, the entire display must be replaced.
To replace the display you will needa new display including plastic frame and display cable, see the Available Spare Parts for iX Panel TA70 section. For information
about changingthe display, see theReplacing the Display/Display Cable section.
The service menu for theoperator panel can be accessed beforea project is
downloaded, or by settingthe mode switches in mode 1000. The location of the
mode switches is described in the Mode Switches section.
8.1ServiceMenuinanEmptyPanel
When no project isloaded in the panel memory,the panel will boot, displayingthe
Welcome screen. Press anywhere onthe panel display to enter the service menu.
8.2ServiceMenuinaPanelwith
Project
When a project is loaded in the panel memory, the panel w ill automatically start to
execute theproject. To display the service menu atboot-up:
1.
Disconnect the powersupply from the panel.
2.
Set the mode switches in mode 1000 (Service Menu mode).
3.
Connect the powersupply.
When the panelboots up it will suggest togo into the Touch Calibrate mode.
This ensures that it willbe possible to recover froma bad calibration.
4.
Pressanywhere on the panel display to interrupt thetimer and to enter the
service menu.
5.
Make desiredsettings in the service menu.
6.
Disconnect the powersupply from the panel.
7.
Set themode switches in mode 0000 (Run mode).
8.
Reconnect thepower supply.
8.3ServiceMenuOptions
The followingoptions are available in the Ser vice Menu:
8.3.1IPSettings
The panel hastwo built-in Ethernet ports, accordingto the drawing below. For
each port, selectto obtain an IP address automatically viaDHCP, or specify an
IP address for the first Ethernet port.
Port 1
The port that is currently connected is recognized by a*.
BeijerElectronics, MAEN012A
Port 2
27
Service Menu
8.3.2Date/Time
Use the Date/Time Settingsdialog to set the time zone, date and timefor the
panel.
8.3.3EraseProject
The erase functionwill detect if the project is located in the panel memory or on a
memory card. Pressing Erase Project will completely removethe project and all its
components from the panelmemory/the memory card.
8.3.4TouchCalibrate
SelectTo uc h Ca li br at e if the touch screen needs to be calibrated. Follow the
instructions on the screento perform a calibration.
BeijerElectronics, MAEN012A
28
Hardware Self Test
9HardwareSelfTest
The self testprogram can be used to test aspects of operator panel functionality
and thecommunication ports. To run the testyou will need:
•Test plugs, including two Ethernet test p lugs; see Te st pl u g d ra wi ng .
•24 V DC, min. 3 A.
•SD card
Followthe steps below to run the self test programon the operator panel:
1.
Poweroff the operator panel.
2.
Go tothe self test. Set the mode switches tothe self test positions,see the table
in the Mode Switches section.
3.
Power on the operator paneland follow the instructions at the bottom of the
display.
4.
When using thetest plugs, make sure the + 5 V DC LED on the RS422 test
plug and theLED of the RS232 test plug areon.
5.
When the selftest is finished, power off the operator panel and set all mode
switches tothe OFF position.
If an error occursduring the self test, try to fault trace. See Fault Traci
ng.
BeijerElectronics, MAEN012A
29
Hardware Self Test
9.1SelfTestItems
The following tests, of whichsome may be dismissed, are performed:
When experiencing communication problems in for example noisy environments
or when operating close to temperaturelimits, the following recommendations
are to be noticed.
10.1 GroundingtheOperatorPanel
Door
Operator panel
1
Ferrite core
3
2
5
6
4
Mounting plate in the cabinet
Power supply
24 V DC
5350
The operator panel’s mounting clamps do not provide a securegrounding
connection between the panel and the device cabinet, see 1 in drawing above.
1.
Connect a 2.5 mm
and the panel chassis, see 2 in drawi
2.
Connect a 6 or 4mm
2
wire betweenthe ope
rator panel’s quick-connect plinth
ng above.
2
wire or groundingbraid between the panel’s chassis and
the closest grounding point on thedoor, see 3 in drawing above.
3.
Connect a strong but short grounding braid between the door and the device
cabinet,see 4 in drawing above.
4.
Twist the cables onto the24 V DC feed, see 5in drawing above.
2 turns aroundthe ferrite core provide4 times the suppression of 1turn.
3 turns aroundthe ferrite core provide9 times the suppression of 1turn.
A ferrite core suppresses disturbances to the 24 V feed, see 6 in drawing above.
In some industrialunits for Ethernet, the RJ45 contact’s shield is connected to the
chassis via a capacitor, see1 in drawing above.
The operator panel’s Ethernet shield is directly
connected to the chassis, see 2 in
drawing above.
1.
Check whether the other Ethernetunit has its shield directly grounded or
grounded via a capacitor.
Note:
Inmanycases,connecting theshieldedEthernetcablingtothechassisatbothendsis
inappropriate. Humo r groundingloopscanoccur. Unshielded cablingmayevenresult
infewercommunicationerrors.
A good solution may beto use a shielded Ethernet cable, but toconnect the shield
at one end only.
One option isto break the shield, see 3 in drawing above.
A more elegantmethod is to expand the shielded Ethernet cabling with a piece of
unshielded Ethernetcable, see 4 in drawing above.
You can ground the shield via an external 0.1 uF/250 V plastic capacitor, see 5 in
drawing above. This will connect theHF transients to the ground.
BeijerElectronics, MAEN012A
32
Additional InstallationTips
10.3 ToAchieveBetterEMCProtection
•Initially,use the original cabling from BeijerElectronics primarily.
•Use shielded cables for RS232 communication.
•Use twisted pair andshielded cabling for RS422 and RS485.
•Use the cabling intended for the bus type; Ethernet,Profibus, CC-Link,
CAN, Device Netetc.
•Install and connect according to applicablespecifications for the relevant bus
standard.
•Use shielded cabling forEthernet, preferably with foil + braided shield.
•D-sub covers should be shielded, and the shield shoul d be connected to the
cover 360° where the cable comes in.
•Connect the shield at both ends.
Shielded cable
0.1 uF/250 V
Ground plane 1Ground plane 2
Ground plateGround plate
Not same potential
in another building
5352
With longer distances, thereis a risk that the ground potential may bedifferent.
In that case,the shield should only be connected at oneend. A good alternative
is to connect the ot her end of the shield to the ground viaa 0.1 uF/250 V plastic
capacitor. Both endsare then connected to the groundin terms of HF, but only
connected to the ground at one end in terms ofLF, thusavoiding the 50 Hz
grounding loops.
Metal cabinetMetal cabinet
Terminal or connectorTerminal or connector
Cable clamp
in steel
Short distance
EMC cable glandPlastic cable gland
Shielded cableShielded cable
1.
Usean EMC cable gland or regular plastic cable gland, removethe outer jacket
5353
and connect theshield to the installation plate with a360 ° metal cable clamp.
2.
Place the 24V DC and communications cabling in one cable trunk/cable duct
and 230/380 V AC in another. If the cables need to be crossed, cross them at
90 ° only. Avoidcombining the cabling for stronger 24V DC outputs with
the communication cabling.
Ferritecores that are snappedonto the shielded cabling m ay remove minor
disturbances. Large ferrite pieces that aresnapped onto unshielded cabling and
where the wiresgo 2-4 times around the cores are approximately 5-25 timesmore
efficient.
BeijerElectronics, MAEN012A
33
Additional InstallationTips
10.4 AmbientTemperature
The maximum ambient temperature for the operator panel is providedin the
specifications. The ambient temperature refers to the temperature inthe device
cabinet which cools the panel’s electronics.
Top
50 °C inside
Operator
panel
30 °C outside
Middle
45 °C inside
Bottom
40 °C inside
Power
Power
Power
Axial fan
120 x 120 mm
Airflow
5354
Inmostcases,theambienttemperaturefortheoperatorpanelissignificantly
higher than the device cabinet’s ambient temperature.
If the cabinetis tall and there area number of hea
temperature at thetop of the cabinet will be con
theoretical temperature increasethat would
sensitivetoheat. Thelifespanofanelectro
° increase in temperature. A 15-20 ° tempera
t-generating devices,the
siderably higher than the
be expected. All electronics are
lytic capacitor iscut in half with an 8-10
ture increase results in a quarter of the
lifespan etc.
Rittal has a good program for estimating the anticipated averagetemperature in
the cabinet as well as a large program for controlling the temperature in the device
cabinet.
An enamel-coated steelcabinet has
a radiant heat value of 5.5 W/m
2
and degrees
C.
Installing a faninside the cabinet will even out the temperature, while moving air
provides considerably better cooling than still air. A suitable fan is a120 x 120 mm
axial fan, availablein 24 V DC, 115 and 230 V AC.
Installthefansothatitsit
operator panel. If the fan i
ambient temperaturewill
s in thecooler area and will blowcold air against the
s mounted at the top and sucks air upwards,the fan’s
be higher = shorter lifespan.
Agoodfanwithaball-bearingmountinghasanexpectedlifespanofatleast
40,000 hours (nota guaranteed lifespan) at 40 °C.This corresponds to at least4
years of continuoususe. If a thermostatis installed, the fan only needs tocome
on when needed.
Large graphic termi
lighting is off. Th
nals draw only one fifth of thecurrent when the background
e loss effect drops from e.g. 25 Wto only 5 W.
The operator panel’s loss effect = supply voltagex current. Virtuallyno power goes
to external users and no loss effects due to inputs.
BeijerElectronics, MAEN012A
34
10.5 Safety
Most of the operator panels are fed with 24 V DC.
Power supply
1
2
3
230 V AC to 24 V DC
Power supply
230 V AC to 24 V DC
Power supply
230 V AC to 24 V DC
230 V AC
+24 V
0 V
4
+24 V
0 V
4
Distance?
+24 V
0 V
4
Operator panel
Operator panel
Operator panel
Small controller with expansion unit
COM1
COM100
Ch0
Ch1
Ch100
Ch101
5355
Additional InstallationTips
Ifyouuseapowersupplythatmeetssafetystandardsandonlyfeedstheoperator
panel, there is no problem. See 1 in drawing above.
However,ifyouhavea24Vunitthatalsofeedsotherunits,thereisreasontobe
cautious, see 2 indra wing above. The operator panel doesnot have insulation that
meets safety requirementsin the event ofa potential short circuit between230 V
AC and 24V DC. It is assumed that the 24V feed is secure, for example, SELV
according to EN 60950 (protection against electric shock) and UL 950.
ial distance between therelay contacts for 24 V DC and230 V
same 24 V devices for all feeds. See 3 in drawing above.
Connect 0 V on the 24 V feed to the ground, see4 in drawing above. This offers
three advantages:
•Safety is increa
connection or s
•Tr a n si en t s o n
•No risk that th
is not unusua
sed. The24Vfeedwillnotbeliveintheeventofafaulty
hortcircuitbetween0V(24V)and230Vphase.
the 24 V feed are connected to the ground.
e 24 V feedis at a high level in relationship to the ground. This
l since there is high static electricity.
BeijerElectronics, MAEN012A
35
10.6 GalvanicIsolation
r
Additional InstallationTips
+24 V DC
DC/DC
galvanic isolation
Filter
0 V
1.5 m
Internal electronic
VCC
0 V (GND)
RS232RS422/485
USB
USB
DC/AC
Ethernet
CFL
5356
The operator panelhas galvanic isolation against the 24 V DC feed but no galvanic
isolation between the communication ports for RS232, RS422/485 and USB.
Only the Ethernetconnection has galvanic isolation.
Operator panelModular controllerPrinte
RS422 RS232 USB
**
**
Not same ground potential
* = Internal 0 V (GND) connection
When a PC is connected to the panel, the panel’s internal 0V (G
*
Power CPU COM COM2
***
*
PCPC
5357
ND) will be
connected to the protective groundvia the PC.
A number of USB devices can have the shield connected together with the
protective ground. Here, the panel’s 0 V (GND) is connected to the protective
ground when, for example, a USB memory stick, keyboard or similar device is
plugged in.
If a number of units are connectedthat have a 0 V a
these are connected to various grounding poin
problems. Grounding currents go through com
of the controller, and internally in th
e operator panel, and can cause errors.
nd a ground c onnection, and
ts, there is a substantial risk of
munication cables, the rearplate
Use e xternal units to improvecommunication and achieve galvanic isolation.
Westermo has good industry-standard insulators that arealso insulated from the
24 V DC feed.
•Use sh ielded and twisted pair cable. The pair capacitance may not exceed52.5
2
pF/m and areaat least 0.25 mm
(AWG24), if you want to usethe maximum
transfer distance and maximumtransfer speed.
•0 V, the reference voltage for communication should be included in
the cabling. With two-way communication use two pairs; one pair for
communication and one pairfor 0 V.
•The shield must be grounded atone end. The other end is usually grounded,
but with longer d istances or whenthere is a difference in the ground potential,
theshieldshouldbeconnectedtothegroundvia0.1uF/250Vplastic
capacitor to prevent ground currentin the braided shield. A number of
manufacturers recommendthat the shield be groundedat each node. Various
manufacturers have differentsystems for bus termination. The RS485
standard does notdescribe how the “FailSafe” function would be carried out,
justthatthesystemshouldbeabletohandletheerror.
Depending on therecipients’ design, the bus wires may be on the same level or
require pull-upor pull-down to ensure that nofaulty signals are detected when the
bus is in resting mode (all transmitters are disconnected).
Inside operator panel
+5 V
0 V
123
1 K
120 ohm120 ohm
1 K
+5 V
(120 ohm)
14
1 K
2
15
6
19
1 K
7
8
0 V
0 V
4
55
17
50
Operator
panel
RS422
1 2 3 4 5 6 7 8
CAB8CAB8Bus
2
15
3
16
17
4
14
+5 V
VCC
8
0 V
7
0 V
VCC
1 K
120 ohm
1 K
RS485
1
2
3
4
5
6
Shield
7
8
Bus termination
0 V
0 V
5358
Some (older) operatorpanels had pull-up and pull-down resistance except for
the actual bus termination at 120 ohm, similar to Westermo and Profibus. See 1
in drawing above.
Newer panelshave another type of recipient, so-called built-in “Fail Safe”,where
simple bus termination resistanceis sufficient. See 2in drawing above.
If other nodes onthe RS485 network require pull-up and pull-down and the
operator panel isat one end of the loop,one of the following procedures can be
carried out:
•Connect two 1k/0.25 W resistorsin the 25-pole D-sub contact. See 3 in
drawing above. Set jumperpins 6-19.
•Use CAB8. It offers the option of bus termination with pull-up/-down. It
Check if the display hasa wide vertical or horizontal area across the
display. It should be at least2-3 cm wide with a grey or black color. See
Replacing the Display/Display Cable for instructions on howto correct this.
2.
Make sure the display cable is correctlyfitted.
3.
Make surethe display cable is not folded or damaged in any way. Replace the
display cableaccording to the Replacingthe Display/Display Cable section.
Fault T racing
BeijerElectronics, MAEN012A
39
Software
12Software
This chapter describeshow to maintain and update the softwarein the iX Panels.
The chapter includes a general description of the operator panel software and
instructions about how t o upgrade the software and load projects andsystem
programs.
12.1 GeneralInformationabout
Software
The software requiredto run and maintain the operator panelsis found on the
software USB stick. It isalso available through your local distributor.
The software istested by the manufacturer’s own testing department before
market introduction is approved. The test procedure is closelyintegrated with the
development process. The test group works in close concert withthe developers
andisISEBCertifiedforSoftwareTesting.
12.1.1SoftwareProducts
The followingsoftware products are used:
•iX Developer
iX Developer is used for creating application projects for iXPanels and their
accessories.
•Remote AccessViewer
Remote AccessViewer is a program for remote ac
It ispossible to access, reflect and control t
client programRemote Access Viewer (freew
server (Remote Accessfunction) in th
•System Program
The iX Panel TA70 is delivered with an image (operating system) pre-stored in the
operator panel memory.
eiXPanels.
cess and control of the iX Panels.
he iX Panels from a PC usingthe VNC
are) together with thebuilt-in VNC
BeijerElectronics, MAEN012A
40
12.2 UpdateSoftware
When an update is available, an e-mail is sent to the distributors. The software is
also available onthe manufacturer’s web site.
Theupdateshouldbeinstalledbyqualifiedpersonnel.
12.2.1iXDeveloper
iX Developer is not a freeware product.
A demo versioncan be downloaded from www.beijerelectronics.com.
To update iX Developer, an accredited iX Panels dealer must becontacted.
12.2.2RemoteAccessViewer
This software isincluded on the iX Developer USB stick.
To update the Remote Access Viewer, go to www.beijerelectronics.com and select
Support/Downloads inthemenu. BrowsethesoftwarefoldertolocateRemote
Access Viewer. Run the .exe file and followthe instructions.
Software
12.2.3SystemProgram
An upgrade of the complete software package is sometimes needed to take
advantage of new functionality.
The upgrade is done by running theImage Loader execu
IML_TA70–150_bxxx.exe. The Image Loader applica
through the upgrade.
Upgrading of the operator panel system program requiresthe following:
•APC
•An Ethernet connection between the PC and the operator panel or an empty
USB memory stick.
•The Image Loader executable file from the web site
UpgradingtheSystemProgramUsingaUSBMemory
Stick
When upgrading the system program using a memory stick, you can select to
delete or to keepthe project in the operator panel.
Followthe steps below:
1.
Connect an empty USB memory stick to your PC.
2.
Double-click on the executable Image Loader file.
3.
Select the driveof the desired USB stick and click Create.
The files arecopied to the USB stick.
4.
Connect the USB memory stick tothe operator panel.
5.
Cyclethepowertoinitiatetheupgrade.
Software
UpgradingtheSystemProgramviaEthernet
When upgrading the system programvia Ethernet, the project in the operator
panel is retained.
Followthe steps below:
1.
Make sure tha t your PC and the operator panelare connected via Ethernet.
2.
Double-click on the executable Image Loader file.
3.
Enter the IP address of the operator panel.
4.
Click Update, and followthe instructions.
The files aretransferred to the operator panel. The panel will reboot
automatically when the transfer is finished.
BeijerElectronics, MAEN012A
42
Environmental Aspects
13EnvironmentalAspects
This chapter includes info rmation about theenvironmental impact of iX Panels.
More information can be found on the manufacturer’s web site.
13.1 GeneralEnvironmentalAspects
The manufacturer’s activities meet internal requirementsas well as those of the
SS-EN ISO 9001:2000and SS-EN ISO 14001:2004 internationalstandards.
13.2 EnvironmentalImpactofthe
OperatorPanels
13.2.1MechanicalComponents
The aluminum and stainless steel used in the mechanical components are judged
to be non-environmentally hazardous. The expanded rubber packing for the front
and the expanded polyethylenepacking for the display contain an adhesivethat is
not classified as environmentally hazardous.
Screws may haveundergo ne the following surface treatments: Bright
nickel-plating or bright zinc-plating. Themembranekeyboardismadeof
polyester with silver wiring. On some models the keyboard contains LEDs.
Display framesand CF covers are madeof halogen-free plastic, PC/ABS.
13.2.2Electronics
CircuitBoard
Note:
AlloperatorpanelsareRoHScompliant.
The electronics are complex andalmost all elements of theperiodic table are
represented.
Display
There is a separate circuit board for the display. The liquid crystals in thedisplay
are cyclohexanecompounds. The fluorescenttube contains mercury and lead
solder.
Batteries
The operator
classified a
(1997:645
panel contains a buttoncell lithium battery. The battery is not
s environmentally hazardousby the Swedish Battery Ordinance
).
BeijerElectronics, MAEN012A
43
Environmental Aspects
13.3 Recycling
The operator panelsconsist largely of aluminum. It is a greatadvantage in terms of
both resources andthe environment if it can be recycled. Make sure that operator
panels taken out ofservice are sent tofacilities for electronic scrap.
The manufacturer’s electronic waste is recycled by Stena Technoworld AB.
Aluminum front/rearcasings and othercovers can be removed and recycled.
Plastic display frames and CF covers must be recycledas hard plastic. The circuit
board containsmany valuable metals and should thereforebe recycled.
Remove the lith ium battery. Electrolytic capacitors and displays are currently not
classified as hazardouswaste, but may be harmful tohealth and the environment.
The electrolytic capacitors should behandled as per Handbook 2001:7 (NFS)
and displays asper NFS 2001:8.
Thefluorescenttubemustbehandledashazardouswaste.
The packagingis made from wood fiberand shouldberecycled. Thelargeprinted
label on the front,however, must first be removed as it is made of PVC vinyl. The
label and theplastic bag for the bracketsare recycled as soft plastic.
The manufacturer isa member of the REPAregister. The protective film on the
front is recycledas soft plastic. When theoperator panel is no longer useful it
can be returnedto the manufacturer for environmentally responsible recycling.
Contact the company for further information.
13.4 EnvironmentalImpactReport
An operator panel impactsthe environment through its function, i.e., controlling
industrial equipment. The energy and the scrapped parts that can be saved with
efficient management meanthat the operator panel contributes to reduced
environmental impact.
Listed below are examples of how you can reduce environmental impact during
operator panel use.
•Switch the system off when not in use.
•Use green electricity.
•Use energy-saving options, e.g.,turn off the backlight to both save en ergy and
reduce wearon the fluorescent tube.
•Ifpossible, reduce the backlight brightness to reduce energy consumption
and increase fluorescent tube service life.
Supplythe operator panel with 2
effect increases. Ensure that
recycled in an environmentall
4 V DC. Ifthe input voltage is lower, the loss
the operator panel, battery, and packaging are
y responsible manner.