iX T15B Installation Guide

1

Safety Precautions

Both the installer and the owner and/or operator of the operator panel must read and understand this installation manual.

1.1General

Read the safety precautions carefully.

Check the delivery for transportation damage. If damage is found, notify the supplier as soon as possible.

Do not use the operator panel in an environment with high explosive hazards.

The supplier is not responsible for modified, altered or reconstructed equipment.

Use only parts and accessories manufactured according to specifications of the supplier.

Read the installation and operating instructions carefully before installing, using or repairing the operator panel.

Never allow fluids, metal filings or wiring debris to enter any openings in the operator panel. This may cause fire or electrical shock.

Only qualified personnel may operate the operator panel.

Storing the operator panel where the temperature is lower/higher than recommended in this manual can cause the LCD display liquid to congeal/become isotopic.

The LCD display liquid contains a powerful irritant. In case of skin contact, wash immediately with plenty of water. In case of eye contact, hold the eye open, flush with plenty of water and get medical attention.

The figures in this manual serves an illustrative purpose. Because of the many variables associated with any particular installation, the supplier cannot assume responsibility for actual use based on the figures.

The supplier neither guarantees that the operator panel is suitable for your particular application, nor assumes responsibility for your product design, installation or operation.

It is recommended to turn on and shut down the operator panel at least once before installing any components/cards or before connecting the operator panel to external devices, like for example serial devices.

1.2UL and cUL Installation

This equipment is suitable for use in Class 2 non-hazardous locations only. [Combinations of equipment in your system are subject to investigation by the local authority having jurisdiction at the time of installation].

All devices have to be supplied by a Class 2 power supply.

Warning:

Do not disconnect equipment unless power has been removed or the area is known to be non-hazardous

For Canada also AVERTISSEMENT – AVANT DE DECONNECTER L’EQUIPEMENT, COUPER LE COURANT OUS’ASSURER QUE L‘EMPLACEMENT EST DESIGNE NON DANGEREUX.

Warning:

Only UL and cUL approved expansion units are allowed to be connected to the port designated “EXPANSION”. At the moment there are no such units evaluated or allowed.

Warning:

Do not replace expansion unit unless power has been switched off or the area is known to be non-hazardous.

This product contains a battery; this must only be changed in an area known to be non-hazardous.

Replace the battery with a BR 2032 battery. Use of another type of battery may present a risk of fire or explosion.

Warning:

Battery may explode if mistreated. Do not recharge, disassemble or dispose of in fire.

For use on a flat surface of a type 4X enclosure indoor use only.

Use 75 degree conductors only

Use copper conductors only

To make wiring connections to the power supply connector, follow the table with cable and torque specifications below:

Terminal Block No.

Wire Size AWG

TQ Lb.In.

 

 

 

X1/X100 Phoenix connectors

AWG 30–12

5–7

 

 

 

X1/X100 Anytek connectors

AWG 24–12

3.5

 

 

 

These devices are Class 2 supplied programmable controllers (industrial PCs) for the use in industrial control equipment and are intended to be (front) panel mounted (Type 1 and 4x for indoor use only).

1.3During Installation

The operator panel is designed for stationary installation on a plane surface, where the following conditions are fulfilled:

no high explosive risks

no strong magnetic fields

no direct sunlight

no large, sudden temperature changes

Install the product according to the accompanying installation instructions.

Ground the product according to the accompanying installation instructions.

Only qualified personnel may install the operator panel.

Separate the high voltage, signal and supply cables.

Make sure that the voltage and polarity of the power source is correct before connecting the product to the power outlet.

Peripheral equipment must be appropriate for the application and location.

1.4During Use

Keep the operator panel clean.

Emergency stop and other safety functions may not be controlled from the operator panel.

Do not use too much force or sharp objects when touching the keys, touchscreen etc.

1.5Service and Maintenance

Only qualified personnel should carry out repairs.

The agreed warranty applies.

Before carrying out any cleaning or maintenance operations, disconnect the equipment from the electrical supply.

Clean the display and surrounding front cover with a soft cloth and mild detergent.

Replacing the battery incorrectly may result in explosion. Only use batteries recommended by the supplier. During the warranty period, the battery needs to be replaced by an authorized Beijer Electronics service center.

1.6Dismantling and Scrapping

The operator panel or parts thereof shall be recycled according to local regulations.

The following components contain substances that might be hazardous to health and the environment: lithium battery, electrolytic capacitor and display.

1.7Appearance of Air in Touch Screen

The layer structure of the touch screen contains air and in rare cases appearance of bubbles can arise. This is purely cosmetic and does not affect any functionality of the panel. The appearance can occur under certain environmental conditions such as temperature, humidity, and atmospheric pressure.

2 Installation

2.1Space Requirements

Maximum installation plate thickness: 8 mm

Space requirements in millimeters when installing the operator panel:

100

286

50

50

100

100

410

Note:

The dimensions on the drawing are not proportional.

2.2

Installation Process

The following is needed:

A Torx TX7 screwdriver

1.Unpack and check the delivery. If damage is found, notify the supplier.

Note:

Place the operator panel on a stable surface during installation. Dropping the panel or letting it fall may cause damage.

2.Use the cut out dimensions that are included on the outline drawing, found in section Operator Panel Drawings and in the Technical Data table, to cut a correct opening in the cabinet. A separate cut out drawing is available for download from the Beijer Electronics web site.

3.Secure the operator panel in position by screwing the M4 Torx screw, allowing the built-in bracket to tighten against the panel:

M4 x 20.7

0.4 Nm

4.Connect the cables in the specified order, according to the drawing and steps below.

Caution:

Ensure that the operator panel and the controller system have the same electrical grounding (reference voltage level), otherwise errors in communication may occur.

The operator panel must be brought to ambient temperature before it is started up. If condensation forms, ensure that the operator panel is dry before connecting it to the power outlet.

Ensure that the voltage and polarity of the power source is correct.

Use only shielded communication cables.

Separate high voltage cables from signal and supply cables.

 

 

B

 

 

Controller

RS232/

 

 

RS422/

 

 

RS485

 

24V DC

 

24V DC

 

 

C

 

 

 

D

A

 

 

Ethernet

 

 

Connect cable A.

Connect cable B, using an M5 screw and a grounding conductor (as short as possible) with a cross-section of minimum 2.5 mm2.

Connect cable C.

Connect cable D. The recommended cross-section of the cable is 1.5 mm2.

5.Carefully remove the laminated film over the operator panel display, to avoid static electricity that could damage the panel.

2.2.1Connections to the Controller

For information about the cables to be used when connecting the operator panel to the controller, please refer to the help file for the driver in question.

2.2.2Other Connections and Peripherals

Cables, peripheral equipment and accessories must be suitable for the application and its environment. For further details or recommendations, please refer to the supplier.

3

Technical Data

Parameter

iX T15B

Front panel, W × H × D

410 × 286 × 83 mm

 

 

Cut out dimensions, W × H

394 × 270 mm

 

 

Mounting depth

76 mm (176 mm including clearance)

 

 

Standalone mounting

VESA 75 × 75

 

Note: Maximum screw length for VESA

 

mounting is 4 mm. Usage of longer screws

 

may lead to damage.

 

 

Front panel seal

IP 65

 

 

Rear panel seal

IP 20

 

 

Touch screen material

Polyester on glass, resistive.

 

Overlay: Autoflex EBA 180L(1).

Touch screen operations

1 million finger touch operations

 

 

Reverse side material

Powder-coated aluminum

 

 

Frame material

Powder-coated aluminum

 

 

Weight

3.85 kg

 

 

Serial port for

9-pin D-sub contact with RS232 RTS/CTS,

COM1 RS232 and

chassis-mounted female with standard

COM2 RS422/RS485

locking screws 4-40 UNC

 

 

Serial port for

9-pin D-sub contact with RS232 RTS/CTS,

COM3 RS232 and

chassis-mounted female with standard

COM4 RS422/RS485

locking screws 4-40 UNC

 

 

Ethernet

1 × 10/100/1000 Mbit/s and 1 × 10/100

 

Mbit/s. Shielded RJ45

 

 

USB

3 × USB Host 2.0, max output current 500 mA

 

 

Processor

Intel® Atom

 

 

External storage media

1 × SD card (optional). Only compatible

 

with the standard SD format with up to 2 GB

 

storage capacity.

 

 

Memory RAM

1 GB

 

 

LED

1 × multi-color

 

 

Real time clock

Yes (on chip)

 

 

Battery

Lithium battery type BR 2032 (or CR 2032),

 

exchangeable

 

 

Power consumption at

24 W

rated voltage

 

 

 

Fuse

3.15 A Slow

 

 

Power supply

+24 V DC (18-32 V DC)

 

CE: The power supply must conform with the

 

requirements according to IEC 60950 and

 

IEC 61558-2-4.

 

UL and cUL: The power supply must conform

 

with the requirements for class II power

 

supplies.

 

 

Display

TFT-LCD with LED backlight. 1280 × 800 pix-

 

els, 262 k colors

 

 

Active area of display,

331.2 × 207.0 mm

W × H

 

 

 

Operating temperature

-10 °C – +50 °C

 

 

Storage temperature

-20 °C – +70 °C

 

 

Relative humidity

5% – 85% non-condensed

 

 

Approvals and

Information is available on the web site

certifications

www.beijerelectronics.com

 

 

(1) See section Chemical Resistance for more information.