CX8190 | Embedded PC with different Ethernet protocols
The CX8190 is a controller with two Ethernet ports, one of which is switched to two RJ45 sockets. It supports protocols such as
real-time Ethernet, ADS UDP/TCP or EAP (EtherCAT Automation Protocol). K-bus or E-bus terminals can be attached as required; the
CX8190 automatically recognises the type of I/O system connected during the start-up phase. The control system is programmed
with TwinCAT 3 via the fieldbus interface or the additional Ethernet interface. TwinCAT 3 licenses must be ordered via the
TwinCAT 3 price list.
Technical data CX8190
Processor ARM Cortex™-A9, 800 MHz (TC3: 20)
Flash memory slot for microSD card, 512 MB included (expandable)
Main memory 512 MB DDR3 RAM (not expandable)
Protocol real-time Ethernet, ADS UDP, ADS TCP, EAP (EtherCAT Automation Protocol)
Programming TwinCAT 3
Interfaces 1 x RJ45 10/100 Mbit/s, bus interface
Bus interface 2 x RJ45 (switched)
Data transfer rates 100 Mbit/s
I/O connection E-bus or K-bus, automatic recognition
Power supply 24 V DC (-15 %/+20 %)
Clock internal battery-backed clock for time and date (battery behind the front flap, exchangeable)
UPS 1-second UPS
Operating system Microsoft Windows Embedded Compact 7
Current supply E-bus/K-bus 2 A
Max. power consumption 4 W
Max. power consumption (with
loading UPS)
9 W
Dimensions (W x H x D) 71 mm x 100 mm x 73 mm
Weight approx. 230 g
Operating/storage temperature -25…+60 °C/-40…+85 °C
Relative humidity 95 %, no condensation
Vibration/shock resistance conforms to EN 60068-2-6/EN 60068-2-27
EMC immunity/emission conforms to EN 61000-6-2/EN 61000-6-4
Protection class IP 20
Approvals/markings CE, UL
TC3 performance class Economy (20); please see here for an overview of all the TwinCAT 3 performance classes
System
Ethernet TCP/IP For further Ethernet TCP/IP products please see the system overview.
CX8190
Coupler supply
Power contacts
E-bus or K-bus
Front flap
Input for
power contacts
Power LEDs
Ethernet RJ 45
(switched)
Link/Act
Link/Act
Ethernet port
Address selector
Ethernet RJ 45
(switched)
CX8190
BECKHOFF New Automation Technology
We reserve the right to make technical changes.