BECKHOFF CU8850-0000 User Manual

Installation- and Operating instructions for
USB-Extender-Rx CU8850-0000
Version: 1.2 Date: 2015-03-25
Table of contents
1.
General instructions 2
Notes on the Documentation 2 Liability Conditions 2 State at Delivery 2 Description of safety symbols 2
2.
Product Description 3
Product Overview 3 Power supply 4 UL requirements 4 Data Connectors 4
RJ 45 Port (X20) (standard CAT5-cable) 4 USB Typ A Port (X30) (standard-cable) 4
LED Diagnostics 5
3.
Installation Instructions 6
Transport and Unpacking 6
Transport 6 Unpacking 6
Mounting/ Unmounting 7 Connecting devices 8
Connecting cables 8 Check voltage rating and connect 8
4.
Operating Instructions 9
Architecture Description 9
5.
Appendix 10
Assembly dimensions 10 Beckhoff Support & Service 11
Beckhoff branches and partner companies 11 Beckhoff Headquarters 11 Beckhoff Support 11 Beckhoff Service 11
Technical data 12 Approvals for USA and Canada 12
FCC: Federal Communications Commission Radio Frequency Interference Statement 12 FCC: Canadian Notice 12
CU8850-0000 1
General instructions

General instructions

Notes on the Documentation

This description is only intended for the use of trained specialists in control
and automation engineering who are familiar with the applicable national standards. It is essential that the following notes and explanations are followed when installing and commissioning these components.

Liability Conditions

The responsible staff must ensure that the application or use of the products described satisfy all the requirements for safety, including all the relevant laws, regulations, guidelines and standards.
The documentation has been prepared with care. The products described are, however, constantly under development. For that reason the documentation is not in every case checked for consistency with performance data, standards or other characteristics. None of the statements of this manual represents a guarantee (Garantie) in the meaning of § 443 BGB of the German Civil Code or a statement about the contractually expected fitness for a particular purpose in the meaning of
§ 434 par. 1 sentence 1 BGB. In the event that it contains technical or editorial errors, we retain the right to make alterations at any time and without warning. No claims for the modification of products that have already been supplied may be made on the basis of the data, diagrams and descriptions in this documentation.
© This documentation is copyrighted. Any reproduction or third party use of this publication, whether in whole or in part, without the written permission of Beckhoff Automation GmbH & Co. KG, is forbidden.

State at Delivery

All the components are supplied in particular hardware and software
configurations appropriate for the application. Modifications to hardware or software configurations other than those described in the documentation are not permitted, and nullify the liability of Beckhoff Automation GmbH & Co. KG.

Description of safety symbols

The following safety symbols are used in this operating manual. They are
intended to alert the reader to the associated safety instructions.
This symbol is intended to highlight risks for the life or health of personnel.
Danger
This symbol is intended to highlight risks for equipment, materials or the environment.
This symbol indicates information that contributes to better understanding.
i
Warning
Note
2 CU8850-0000
Product Description

Product Description

Product Overview

View of the CU8850-0000 USB-Extender-Rx
The USB specification allows a distance of 5 m between the PC and the
USB devices. A further 5 metres of cable can be added by using a USB hub. In the construction of machines and plants, larger distances must be bridged without having to insert a USB hub every 5 metres. The CU8800 USB Extender sends the USB signal via a CAT5 cable that can be up to 50 m long to the CU8850 USB Extended receiver, which converts the signal back to USB. Data rates of up to 12 Mbit/s can be transmitted. Both USB Extender boxes are designed for DIN rail mounting.
Other outstanding features are:
user-friendly installation via integrated top hat rail adapter
24 V
12 Mbit, and 1.5 Mbit support for compatibility to all USB1.1
standards
standard CAT5 network cable for extension
compact industrial design
clear quick diagnosis by separate LEDs for power supply in and
out
supply voltage – the standard in industrial evironments
DC
CU8850-0000 3
Product Description

Power supply

Additional 24 VDC power supply Normally the USB-Extender-Rx CU8850 is
powered via the USB-extension. The device can also be powered by an additional power supply (X10).
If a USB device needs more than the specified max. of 300mA, the additional power supply must be connected.
The pins have to be connected as shown on the front panel of the CU8850-device.
Power Supply

UL requirements

For the compliance of the UL requirements the USB-Extender-Rx
should only be supplied
by a 24 V protected by means of a fuse (in accordance with UL248), rated maximum 4 Amp.
supply voltage, supplied by an isolating source and
DC
by a 24 V
power source, that has to satisfy NEC class 2.
DC
A class 2 power supply shall not be connected in series or parallel with another (class 2) power source!
To meet the UL requirements, the USB hub CU8800-0000 must not be
Danger
connected to unlimited power sources!

Data Connectors

The CU8850 has two kinds of connectors: RJ45 and USB type A. The
pin layouts are described below.

RJ 45 Port (X20) (standard CAT5-cable)

RJ 45 Port
Pin 1
Pin 8
X20

USB Typ A Port (X30) (standard-cable)

Pin Signal Belegung
1 15 V 15 V + 2 GND GND 3 TX USB TX 4 RX USB RX 5 RX USB RX 6 TX USB TX 7 15 V 15 V + 8 GND GND
USB Typ A Port
4
3 2
1
Shield
X30
Pin Signal
1 VCC 2 Data ­3 Data + 4 GND Shield Shield
4 CU8850-0000
Product Description

LED Diagnostics

LED Diagnostics
P30
P22
P21
P20
The following table shows the possible states for the LEDs:
LED Assignment Status Meaning
off No power supply connected P10 Power Supply
lights green 24 V
Off USB is operational P20 USB Suspend
Lights USB is in suspend mode/ no device
Off No 15 V supplied P21 USB 15 V
Lights 15 V supplied to USB extension
Full-Speed
Low-Speed
USB Port
Off Full-speed device connected P22 USB Device
Lights No device connected
Off Low-speed device connected P23 USB Device
Lights No device connected
lights green Current < 500 mA P30 Current load at
lights red Current > 500 mA
connected
DC
connected
P23
P10
CU8850-0000 5
Installation Instructions

Installation Instructions

Please also refer to chapter General instructions.

Transport and Unpacking

The specified storage conditions must be observed (see chapter Technical
data).

Transport

Despite the robust design of the unit, the components are sensitive to
strong vibrations and impacts. During transport, the unit should therefore be protected from excessive mechanical stress. Therefore, please use the original packaging.
Danger of damage to the unit!
Warning
If the device is transported in cold weather or is exposed to extreme variations in temperature, make sure that moisture (condensation) does not form on or inside the device.
Prior to operation, the unit must be allowed to slowly adjust to room temperature. Should condensation occur, a delay time of approximately 12 hours must be allowed before the unit is switched on.

Unpacking

Proceed as follows to unpack the unit:
1. Remove packaging.
2. Do not discard the original packaging. Keep it for future relocation.
3. Check the delivery for completeness by comparing it with your order.
4. Please keep the associated paperwork. It contains important information for handling the unit.
5. Check the contents for visible shipping damage.
6. If you notice any shipping damage or inconsistencies between the contents and your order, you should notify Beckhoff Service.
6 CU8850-0000
Installation Instructions

Mounting/ Unmounting

The CU8850 can be snapped onto a 35 mm mounting rail conforms to
EN 50022.
Mounting the USB-Extender-Rx
Just push the unit on the lower side under the rail (fig. 1) and snap in the upper side (fig. 2) as shown below:
Unmounting the USB-Extender-Rx
To release the CU8850 USB-Extender-Rx from the mounting rail push up the unit (fig. 1) and pull off the device from the rail (fig. 2):
CU8850-0000 7
Installation Instructions

Connecting devices

Warning
The connectors are documented in the section Product Description.
The power supply plug must be withdrawn!
Please read the documentation for the external devices prior to connecting them.
During thunderstorms, plug connector must neither be inserted nor removed.
When disconnecting a plug connector, always handle it at the plug. Do not pull the cable!

Connecting cables

When connecting the cables to the CU8850 USB-Extender-RX, proceed according to the following sequence:
Switch off all the devices that are to be connected.
Disconnect all the devices that are to be connected from the power
supply.
Connect all the cables between the CU8850 and to the devices
that are to be connected.
Reconnect all devices to the power supply.

Check voltage rating and connect

1. Check that the external power supply is providing the correct
voltage.
2. Connect the unit to your external 24 VDC power supply.
8 CU8850-0000
Operating Instructions

Operating Instructions

Architecture Description

Within the USB-Extender-TX (CU8800) and USB-Extender-RX (CU8850)
the length of USB data transmission can be increased from 35 meters (1 host, 5 USB hubs and a device each connected with 5 meters of cable) up to 61 meters. Due to the USB signal runtime, it is not possible to connect more than one USB hub in the chain.
Configuration
The USB hub has to be connected after the CU8850-Box.
The maximal distance is 61 meters: 1 meter of cable from USB host to the USB extension box CU8800; up to 50 meters extension cable; 5 meters from extension box CU8850 to the USB hub and 5 meters of cable to the USB device.
CU8850-0000 9
Appendix

Appendix

Assembly dimensions

The product is characterized by small overall installed size. With a height of
approx. 100 mm, the module dimensions exactly match those of the Beckhoff Bus Terminals. Together with the lowered connector surfaces, this means that it can be used in a standard terminal box with a height of 120 mm.
10 CU8850-0000
Appendix

Beckhoff Support & Service

Beckhoff and their partners around the world offer comprehensive support
and service, guaranteeing fast and competent assistance with all questions related to Beckhoff products and system solutions.

Beckhoff branches and partner companies

Please contact your Beckhoff branch office or partner company for local
support and service on Beckhoff products!
The contact addresses for your country can be found in the list of Beckhoff branches and partner companies: www.beckhoff.com
You will also find further documentation for Beckhoff components there.

Beckhoff Headquarters

Beckhoff Automation GmbH & Co. KG Huelshorstweg 20 33415 Verl Germany
Phone: Fax: +49(0)5246/963-198 e-mail: info@beckhoff.com
+49(0)5246/963-0

Beckhoff Support

Beckhoff offers you comprehensive technical assistance, helping you not only with the application of individual Beckhoff products, but also with wide­ranging services:
worldwide support
design, programming and commissioning of complex automation
systems
training program for Beckhoff system components
Hotline: Fax: +49(0)5246/963-9157 e-mail: support@beckhoff.com
+49(0)5246/963-157

Beckhoff Service

The Beckhoff service center supports you in all matters of after-sales service:
on-site service
repair service
spare parts service
hotline service
Hotline: Fax: +49(0)5246/963-479 e-mail: service@beckhoff.com
Quote the project number If servicing is required, please quote the project number of your product.
+49(0)5246/963-460
CU8850-0000 11
Appendix

Technical data

Number of ports USB Type A ports (upstream): 1 USB Extender Rx ports (RJ45): 1 Supported standard USB 1.1 Supported baud rates 12 Mbit (Full Speed), 1.5 Mbit (Low Speed) Status display 2 LEDs USB extension wiring
Maximum 50 meters
length USB wiring length Maximum 5 meters Additional Power supply 24 V
(-15% to +20%), protected against polarity reversal.
DC
To meet the UL requirements use 4 A fuse or class 2 power supply!
Power output (USB)
Maximum 300 mA (without additional power supply) Maximum 500 mA (with connected additional power supply)
Power consumption device Maximum 500 mW
The following conditions must be observed during operation:
Environmental conditions Ambient temperature: 0 to 55°C (operation)
-25°C to +70°C (transport/ storage)
Atmospheric humidity: Maximum 95%, non-condensing Vibration/ Shock resistance EN 60068-2-6 / EN 60068-2-27 EMC resistance burst/ ESD EN 60000-6-2 / EN 60000-6-4 Protection class IP20
Do not use the CU8850 in
The DVI splitter may not be used in areas of explosive hazard.
areas of explosive hazard
Dimensions (W x H x D) Approx. 34 mm x 100 mm x 76 mm (with mounting for DIN rail) Weight Approx. 95 g Assembly On 35 mm mounting rail conforms to EN 50022 Installation position Any Approvals CE
UL (for details see chapter UL requirements)

Approvals for USA and Canada

FCC Approval for USA
FCC Approval for Canada
FCC: Federal Communications Commission
Radio Frequency Interference Statement
This equipment has been tested and found to comply with the limits for a Class A
digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is
operated in a commercial environment. This equipment generates, uses, and can
radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his
own expense.

FCC: Canadian Notice

This equipment does not exceed the Class A limits for radiated emissions as
described in the Radio Interference Regulations of the Canadian Department of
Communications.
12 CU8850-0000
Loading...