Beckett Damper Actuator User Manual

Damper Actuator
For Commercial Two-Stage Burners
Adjustment Instructions
Adjustment Instructions Printed on Cover
Disengaging Pin in the Engaged Position
Cam Stack
Adjustment Wrench
The Disengaging Pin allows the Damper and Cam Stack to be rotated by hand
The
Disengaging Pin
must be out when
Damper Position Indicator (Black mark on white ring)
Damper Position Scale
Red High Fire Cam with White adjustment Scale
Blue Low Fire Cam with White adjustment scale
Transition Cam shares Adjustment scale
Damper Actuator
For Commercial Two-Stage Burners
Adjustment Instructions
Setting the High Fire Air and Low Fire Air
Low Fire Air Set with Blue Cam
Adjustment Wrench
High Fire Air is set with the Red Cam
Adjustment Wrench
Setting the Transition
Cam is disengaged
Transition Cam is set with Screwdriver
The ORANGE CAM sets the transition point between Low Fire Oil and High Fire Oil.
It should be set halfway between the settings of the RED Cam and the BLUE Cam.
An old air setting specification of 7 is equal to 70° on the damper position scale of this new damper actuator. If adjusting the air settings while the burner is operating, it is necessary to cycle the burner from High to Low Fire or Low to High by using the lighted low fire hold switch.
After you complete your adjustments make certain the disengaging pin has been reengaged with the damper position set between the high fire and low fire limits. Replace the actuator cover, making sure it is correctly seated, and test the burner for proper firing at low fire, high fire and in transition between low and high.
For more information, contact: www.beckettcorp.com