Basler Electric BE1-50/51B User Manual

INSTRUCTION MANUAL
FOR
OVERCURRENT RELAY
BE1-50/51B
Publication: 9252000991 Revision: R 09/11

INTRODUCTION

This instruction manual provides information about the operation and installation of the BE1-50/51B Overcurrent Relay. To accomplish this, the following information is provided:
General Information and Specifications Controls and Indicators Functional Description Installation and Maintenance Testing
WARNING!
To avoid personal injury or equipment damage, only qualified personnel should perform the procedures in this manual.
NOTE
Be sure that the relay is hard-wired to earth ground with no smaller than 12 AWG copper wire attached to the ground terminal on the rear of the unit case. When the relay is configured in a system with other devices, it is recommended to use a separate lead to the ground bus from each unit.
First Printing: April 1992
Printed in USA
© 1992-2011 Basler Electric, Highland Illinois 62249 USA
All Rights Reserved
September 2011
CONFIDENTIAL INFORMATION
of Basler Electric, Highland Illinois, USA. It is loaned for confidential use, subject to return on request, and with the mutual understanding that it will not be used in any manner detrimental to the interest of Basler Electric.
It is not the intention of this manual to cover all details and variations in equipment, nor does this manual provide data for every possible contingency regarding installation or operation. The availability and design of all features and options are subject to modification without notice. Should further information be required, contact Basler Electric.
BASLER ELECTRIC
12570 STATE ROUTE 143
HIGHLAND IL 62249 USA
http://www.basler.com, info@basler.com
PHONE +1 618.654.2341 FAX +1 618.654.2351
ii BE1-50/51B Introduction 9252000991 Rev R

REVISION HISTORY

The following information provides a historical summary of the changes made to this instruction manual (9252000991). Revisions are listed in reverse chronological order.
Manual
Revision and Date
R, 09/11
P, 12/08
N, 03/08
M, 11/00
L, 12/99
K, 02/99
J, 05/98
I, 07/97
Change
Updated year of IEEE C37.90 specifications in Section 1. Improved description of Locator H (Active/Pickup LED) in Table 2-1. Updated Storage statement in Section 4.
Improved Figure 5-2, Target Operational Test Setup. Corrected sensing input terminal number references listed in
Section 3.
Updated front panel drawings to show new target reset button. Added GOST-R to Section 1. Moved content of Section 7, Manual Change Information, to manual
Introduction.
Moved Characteristic Curve graphs from Section 1 to new
Appendix A.
Moved content of Section 6, Maintenance, into Section 4,
Installation.
Updated drawings in Section 2 to reflect changes to the PC board. Updated the manual to reflect the change in switch call out from
SW8 to SW3.
Added new functionality to the PICKUP LED. It is now the
ACTIVE/PICKUP LED and will be green when active and red when picked up.
Changed all drawings to show the newly designed front cover. Changed all references to the current for testing the targets to an ac
only type of current.
Page 2-2: added description to Locator K for 100 series relays, unit
revision Q and previous.
Deleted Figure 2-2 from Section 2 and added it to new Section 8. Page 3-2: added description to Auxiliary Output Contacts for 100
series relays, unit revision R and subsequent.
Added new Section 8, Relay Differences.
Added Patent Number to Specifications and changed the manual
format to reflect current manual styles.
Added Model # BE1-50/51B-203 to Table 1-1. Corrected Tables 1-3 and 1-4, Figure Number. Changed “pickup setting” to “pickup” on pages 1-7, Time
Characteristics equation, page 1-9, Time Reset, and Figures 1-6 through 1-14.
Added Oscillatory to Surge Withstand Capability on page 1-11. Corrected Figure 1-18 to reflect the correct Time Dial range: 0.5 to
9.9.
Changed Table 7-1 to add ECA and date data.
9252000991 Rev R BE1-50/51B Introduction iii
Manual
Revision and Date
H, 02/96
G, 10/95
F, 02/95
E, 09/94
D, 05/94
C, 06/93
B, 09/92
A, 05/92
Change
Incorporated changed in series 200 relays that added five
characteristic curves and changed switch SW8-3 functionality.
Changed Section 5, Testing, to incorporate setting all sections of
switch SW8.
Corrected minor typographical errors in Section 1 and 2. Corrected Table 2-1, locator item K, Function. Changed Figure 5-2 and all testing target current source references
from 0.2 ampere to 1.0 ampere.
Changed Table 7-1 to add ECA and date data.
Changed all sections to reflect 200 series relay additions and relay
modifications that deleted P2 and P3 jumpers and added switch SW8.
Changed Specifications, TIME and ISNT PICKUP accuracy; Output
Circuits, and Isolation (Dielectric Test).
Corrected Figure 4-8.
Clarified TIME PICKUP and INST PICKUP specification ranges,
page 1-3.
Changed Figure 1-2 to also show one ampere unit burden data. Changed time characteristics accuracy statement, page 1-6. Added (repeated) equation for the characteristic curve time
functions, page 1-8.
Changed Figure 1-4 to show one ampere unit starting data. Separated Section 4, Installation, into Section 4, Installation, and
Section 5, Testing, and bumped all subsequent sections.
Added column for CT secondary to Table 1-1 and UL Recognition
and CSA Certification to specifications.
Page 3-2: Deleted “or reset” from last sentence in paragraph
Outputs. Changed from “The targets will not operate or reset…” to “The targets will not operate…”
Page 4-1: Corrected dielectric test leakage current per terminal.
Page 1-1: Application, deleted reference to dust tight cover. Page 1-3: Specifications, TIME Dropout to not less than 95% of
pickup value.
Page 1-6: Specifications, Time Reset, added statement to insure
sufficient power to power-up relay when using decaying characteristic.
Page 1-7: Specifications, corrected Storage Range Temperature
degrees F.
Page 1-8: Defined British Standard curve types. Page 2-1: INST and TIME PICKUP selectors, added statement that
changing selectors while relay is in service may cause tripping.
Page 4-4: Changed Figures 4-4 and 4-5. Page 4-6: Changed Figure 4-8. Page 4-9: Time Pickup Test, Step 1, changed 0.45 A to 0.485 A. Page 4-11: Time Pickup Test, Step 1, changed 0.09 A to 0.096 A. Page 4-13: Added paragraph SETTING THE RELAY. Added Section 6.
Changed manual title to BE1-50/51B and incorporated engineering
changes accordingly.
iv BE1-50/51B Introduction 9252000991 Rev R
Manual
Revision and Date
, 04/92
Change
Initial release.
9252000991 Rev R BE1-50/51B Introduction v
vi BE1-50/51B Introduction 9252000991 Rev R

CONTENTS

SECTION 1 GENERAL INFORMATION ................................................................................................ 1-1
SECTION 2 CONTROLS AND INDICATORS ........................................................................................ 2-1
SECTION 3 FUNCTIONAL DESCRIPTION ........................................................................................... 3-1
SECTION 4 INSTALLATION .................................................................................................................. 4-1
SECTION 5 TESTING ............................................................................................................................ 5-1
SECTION 6 RELAY DIFFERENCES...................................................................................................... 6-1
APPENDIX A TIME CHARACTERISTIC CURVES ................................................................................ A-1
9252000991 Rev R BE1-50/51B Introduction vii
viii BE1-50/51B Introduction 9252000991 Rev R
SECTION 1 GENERAL INFORMATION
TABLE OF CONTENTS
SECTION 1 GENERAL INFORMATION ................................................................................................ 1-1
Introduction ............................................................................................................................................ 1-1
Features ................................................................................................................................................. 1-1
Advantages ........................................................................................................................................ 1-1
Model Numbers ...................................................................................................................................... 1-2
Specifications ......................................................................................................................................... 1-4
Current Sensing Input ........................................................................................................................ 1-4
Time Overcurrent (51) Element .......................................................................................................... 1-4
Instantaneous Overcurrent (50) Element ........................................................................................... 1-6
Burden ................................................................................................................................................ 1-8
Frequency Response ......................................................................................................................... 1-8
Transient Response ........................................................................................................................... 1-8
Harmonic Response ........................................................................................................................... 1-8
Target Indicators ................................................................................................................................ 1-9
Output Contacts ................................................................................................................................. 1-9
AUX Output Contact ........................................................................................................................... 1-9
Type Tests .......................................................................................................................................... 1-9
Environment ....................................................................................................................................... 1-9
Agency Recognition ......................................................................................................................... 1-10
Patent ............................................................................................................................................... 1-10
Physical ............................................................................................................................................ 1-10
Figures
Figure 1-1. BE1-50/51B, S1 Case ............................................................................................................. 1-2
Figure 1-2. Integrating Reset Characteristic Curve Figure 1-3. Instantaneous Characteristic Curves
Figure 1-4. Burden Characteristics ............................................................................................................ 1-8
Figure 1-5. Harmonic Rejection
Tables
Table 1-1. BE1-50/51B Overcurrent Relays, One Ampere CT Secondary, 50/60 Hz ............................... 1-3
Table 1-2. BE1-50/51B Overcurrent Relays, Five Ampere CT Secondary, 50/60 Hz Table 1-3. Time Characteristic Curve Constants with SW3-3 Open (Off) (Series 100 Relays or Series 200 Relays) Table 1-4. Time Characteristic Curve Constants with SW3-3 Closed (On) (Series 200 Relays)
................................................................................... 1-6
...................................................................................... 1-7
................................................................................................................. 1-9
............................... 1-3
....................................................................................................................................................... 1-5
............. 1-5
9252000991 Rev R BE1-50/51B General Information i
ii BE1-50/51B General Information 9252000991 Rev R
SECTION 1 GENERAL INFORMATION

Introduction

BE1-50/51B overcurrent relays are microprocessor based, non-directional phase or ground relays that monitor the magnitude of a single-phase ac current to provide accurate instantaneous and time overcurrent protection for 50 or 60 Hz power systems. Models are available with fifteen popular time characteristics and a wide range of pickup settings.

Features

A wide range of pickup settings and front panel selectable time characteristics permit applications involving coordination with fuses, reclosers, cold load pickup, motor starting, and fixed time requirements. Also, an integrating reset function is available to simulate the disk reset of electromechanical relays.
BE1-50/51B overcurrent relays have the following standard features.
Independent time and instantaneous elements
A secure method to manually trip the breaker at the relay front panel
Direct reading front panel controls
Minimum pickup setting for safety during installation
Time characteristics extend to a pickup multiple of 40
Rugged draw-out construction with steel case
Gravity latching targets retain indication without power
Built-in accuracy eliminates internal adjustments
Minimum transient overreach
Field selectable characteristic curve selection
Field selectable instantaneous or integrating reset
Field selectable 50 or 60 Hz operation
Field selectable fixed instantaneous delay (0.0, 0.1, 0.2, or 0.3 second on 100 series relays and
0.0 or 0.1 second on 200 series relays.).
Individual models are available for 1 ampere and 5 amperes sensing input currents and installed in A1 or S1 cases. BE1-50/51B overcurrent relays may be tested without removing the relay from the case. Shorting contacts are provided for all current inputs when the connection plug or relay chassis is removed from the relay case. Figure 1-1 shows the front panel of the BE1-50/51B overcurrent relay, in an S1 case.

Advantages

BE1-50/51B overcurrent relays have many advantages over other overcurrent relays. The primary advantages are:
Time characteristics are defined by equations and graphs
Field selectable time characteristics
Very low burden extends the linear range of the CTs
Self powered from the sensed current
Continuous automatic calibration
9252000991 Rev R BE1-50/51B General Information 1-1
Figure 1-1. BE1-50/51B, S1 Case

Model Numbers

Model number variations in the BE1-50/51B overcurrent relays are specified by a three digit extension to the model number. Tables 1-1 and 1-2 provide model number, case style, switch SW3-3 selections, and sensing current input ranges. Internal switches provide for selecting system operating frequencies of 50 or 60 Hz, instantaneous element delays, curve sets, and instantaneous or integrating reset characteristics. The location and description of these switches is provided in Section 2. Integrating reset is available in 100 series relays (e.g. - BE1-50/51B-105) when there is adequate input current to power the relay. Integrating reset is available in 200 series relays (e.g. - BE1-50/51B-205) even when the input current falls to zero. Two-hundred series relays also have additional characteristic curves available through curve set selection.
1-2 BE1-50/51B General Information 9252000991 Rev R
Table 1-1. BE1-50/51B Overcurrent Relays, One Ampere CT Secondary, 50/60 Hz
Model Number Case Style SW3-3 Selects
BE1-50/51B-101
BE1-50/51B-201
BE1-50/51B-102
BE1-50/51B-202
BE1-50/51B-103
BE1-50/51B-203
Table 1-2. BE1-50/51B Overcurrent Relays, Five Ampere CT Secondary, 50/60 Hz
Model Number Case Style SW3-3 Selects
BE1-50/51B-105
BE1-50/51B-205
BE1-50/51B-106
S1 (Projection Mount)
S1 (Projection Mount)
S1 (Semi-Flush Mount)
S1 (Semi-Flush Mount)
S1 (Projection Mount)
A1
A1
A1
A1
0.2 Second Delay 0.1 - 3.18 0.2 - 19.8
Curve Set 0.1 - 3.18 0.2 - 19.8
0.2 Second Delay 0.1 - 3.18 0.2 - 19.8
Curve Set 0.1 - 3.18 0.2 - 19.8
0.2 Second Delay 0.1 - 3.18 0.2 - 19.8
Curve Set 0.1 - 3.18 0.2 - 19.8
0.2 Second Delay 0.5 - 15.9 1.0 - 99.0
Curve Set 0.5 - 15.9 1.0 - 99.0
0.2 Second Delay 0.5 - 15.9 1.0 - 99.0
Sensing Input Range (Amps)
TIME INST
Sensing Input Range (Amps)
TIME INST
BE1-50/51B-206
BE1-50/51B-107
BE1-50/51B-207
NOTE: 100 series relays (e.g. - BE1-50/51B-105) have the integrating reset function when there is adequate input current to power the relay. 200 series relays (e.g. - BE1-50/51B-205) have the integrating reset function even when the input current falls to zero.
S1 (Projection Mount)
S1 (Semi-Flush Mount)
S1 (Semi-Flush Mount)
Curve Set 0.5 - 15.9 1.0 - 99.0
0.2 Second Delay 0.5 - 15.9 1.0 - 99.0
Curve Set 0.5 - 15.9 1.0 - 99.0
9252000991 Rev R BE1-50/51B General Information 1-3

Specifications

KBD
CM
AD
T
N
T
++=
-
BE1-50/51B electrical and physical specifications are listed in the following paragraphs.

Current Sensing Input

1 Ampere Unit
Continuous Current.................... 2.8 Aac
One Second Rating ................... 80 Aac
5 Ampere Unit
Continuous Current.................... 14 Aac
One Second Rating ................... 400 Aac

Time Overcurrent (51) Element

Setting the TIME PICKUP control at the minimum pickup setting (0.1 on the 1 ampere unit and 0.5 on the 5 ampere unit), places the relay in the most sensitive state and may be used as a safety setting.
1 Ampere Unit Pickup
Setting Range ............................ 0.1 to 3.18 Aac
Setting Increment ....................... 0.02 Aac
Accuracy .................................... ±2%, ±5 milliamperes at or above 0.1 ampere setting
5 Ampere Unit Pickup
Setting Range ............................ 0.5 to 15.9 Aac
Setting Increment ....................... 0.1 Aac
Accuracy .................................... ±2%, ±25 milliamperes at or above 0.5 ampere setting
Dropout
Dropout occurs at 95% of pickup value.
Timing Range
0.0 to 9.9 seconds in 0.1 second steps.
Timing Accuracy
The timing accuracy is the sum of ±1 cycle, ±2%. This accuracy applies to the range of 1.3 to 40 times tap and is for a given measured multiple of tap. The measurement of the multiple of tap has an accuracy that is the sum of ±2%, ±25 milliamperes for 5 ampere units, and ±2%, ±5 milliamperes for 1 ampere units.
Timing Accuracy Example (5 Ampere Unit)
PU setting .................................. 5 amperes
Current Applied .......................... 6.5 amperes
+ Multiple Tolerance .................. 6.655 amperes
– Multiple Tolerance .................. 6.345 amperes
Time Curve ................................ E
Time Dial .................................... 5.0
Minimum time dial
using 6.655 amperes ............... 46.5470 seconds
Maximum time dial
using 6.345 amperes ............... 61.3968 seconds
Curve time using 6.5 amperes ... 53.1800 seconds
Curve Characteristics
Nine inverse time functions and one fixed time function can be selected by the front-panel Curve switch. Characteristic curves for the inverse and definite time functions are defined by the following equation.
Where: TT = time to trip in seconds D = time dial setting M = multiple of pickup setting A, B, C, N, K = constants for the particular curve
1-4 BE1-50/51B General Information 9252000991 Rev R
Time characteristic curve constants are listed in Tables 1-3 and 1-4. Constants have been selected to conform to the characteristics of electromechanical relays over a range of pickup multiples from 1.3 to 40. Values of the constants are provided for use in computer relay setting software. Timing accuracy is ±1 cycle, ±2 percent of time to trip.
Table 1-3. Time Characteristic Curve Constants with SW3-3 Open (Off)
(Series 100 Relays or Series 200 Relays)
Curve Type
BE1 Similar To A B C N K R
S ABB CO-2 A-1 0.2663 0.03393 1.000 1.2969 0.028 0.500
L ABB CO-5 A-2 5.6143 2.18592 1.000 1.000 0.028 15.750
D ABB CO-6 A-3 0.4797 0.21359 1.000 1.5625 0.028 0.875
M ABB CO-7 A-4 0.3022 0.12840 1.000 0.5000 0.028 1.750
I ABB CO-8 A-5 8.9341 0.17966 1.000 2.0938 0.028 9.000
V ABB CO-9 A-6 5.4678 0.10814 1.000 2.0469 0.028 5.500
E ABB CO-11 A-7 7.7624 0.02758 1.000 2.0938 0.028 7.750
B BS142-B ‡ A-8 1.4638 0.00000 1.000 1.0469 0.028 3.250
C BS142-C ‡ A-9 8.2506 0.00000 1.000 2.0469 0.028 8.000
F None § N/A 0.0000 1.00000 0.000 0.0000 0.000 1.000
Table 1-4. Time Characteristic Curve Constants with SW3-3 Closed (On)
Curve Type
BE1 Similar To A B C N K R
S GE IAC 55 A-10 0.0286 0.0208 1.000 0.9844 0.028 0.0940
L GE IAC 66 A-11 2.3955 0.00002 1.000 0.3125 0.028 7.8001
D ABB CO-6 A-3 0.4797 0.21359 1.000 1.5625 0.028 0.8750
M ABB CO-7 A-4 0.3022 0.12840 1.000 0.5000 0.028 1.7500
I GE IAC 51 A-12 0.2747 0.1042 1.000 0.4375 0.028 0.8868
V GE IAC 53 A-13 4.4309 0.0991 1.000 1.9531 0.028 5.8231
E GE IAC 77 A-14 4.9883 0.0129 1.000 2.0469 0.028 4.7742
B BS142-B ‡ A-8 1.4636 0.00000 1.000 1.0469 0.028 3.2500
C
F None § N/A 0.0000 1.00000 0.000 0.0000 0.000 1.0000
BS142-C ‡
Figure
Number
(Series 200 Relays)
Figure
Number
A-9 8.2506 0.00000 1.000 2.0469 0.028 8.0000
Constants
Constants
Notes for Tables 1-3 and 1-4
BE1 Curve Types: S: Short Inverse V: Very Inverse L: Long Inverse E: Extremely Inverse D: Definite Time B: BS142 Very Inverse M: Moderately Inverse C: BS142 Extremely Inverse I: Inverse F: Fixed Time Delay
† Figure numbers refer to the characteristic curves located in Appendix A, Time Characteristic Curves.
‡ Curves B and C are defined in British Standard BS142 and IEC Standard IEC 255-4.
§ Fixed time delay, adjustable from 0.1 to 9.9 seconds.
9252000991 Rev R BE1-50/51B General Information 1-5
Integrating Reset
1
=
2
R
M
RD
T
Where:
M = Current in multiples of PICKUP setting during reset
1.0
10.0
100.0
0.000 0.200 0.400 0.600 0.800 1.000 1.200
Multiple of Pickup
xRD (Seconds)
P0046-11
Vertical axis xRD (Seconds) is applicable for all curves and is derived from multiplying the constant R for the curve selected times D (the Time Dial setting).
Reset begins when the current drops below 95% of pickup and the relay has not timed out. Switch SW3-4 provides selection of either an instantaneous or integrating reset characteristic. Opening SW3-4 forces the instantaneous reset timer to zero when timed dropout occurs. This fast reset characteristic prevents the ratcheting effect that may occur with repeating system faults. Closing SW3-4 selects the integrating reset characteristic. The integrating reset characteristic simulates the disk reset of electromechanical relays. When the integrating reset characteristic is selected on 100 series relays, insure that sufficient input power is available to power up the relay. This is not required on Series 200 relays. Series 200 relays provide the integrating reset function even when input current falls to zero.
Integrating reset characteristics are defined by the following equation and shown in Figure 1-2. Equation constants are provided in Tables 1-3 or 1-4.
Integrating Reset Equation:
TR = Time to reset in seconds R = Constant for the particular curve D = TIME DIAL setting
Figure 1-2. Integrating Reset Characteristic Curve

Instantaneous Overcurrent (50) Element

Setting the INST PICKUP control to the minimum pickup setting (0.2 on the 1 ampere unit and 1.0 on the 5 ampere unit), places the relay in the most sensitive state and may be used as a safety setting.
1 Ampere Unit Pickup
Setting Range ............................ 0.2 to 19.8 Aac
Setting Increment ....................... 0.2 Aac
Accuracy .................................... ±2%, ±5 milliamperes at or above 0.2 ampere setting
1-6 BE1-50/51B General Information 9252000991 Rev R
5 Ampere Unit Pickup
Setting Range ............................ 1 to 99 Aac
Setting Increment....................... 1 Aac
Accuracy .................................... ±2%, ±25 milliamperes at or above 1.0 ampere setting
Dropout
Dropout occurs at 95% of pickup value.
Curve Characteristics
BE1-50/51B instantaneous characteristic curves are similar to standard electromechanical instantaneous units. However, the time to trip for ground applications is slightly longer than that for phase applications to allow time to power up the relay. Longer trip time for ground applications is beneficial because it helps to avoid nuisance trips.
For phase applications, the maximum time to trip is 3.5 cycles at a pickup multiple of 1.0, and 1.5 cycles at a pickup multiple of 3.0. The corresponding times for ground applications are 4.5 and 1.75 cycles. Figure 1-3 shows the instantaneous characteristic curves for maximum time to trip.
On 100 series relays, additional delays of 0.1, 0.2, or 0.3 seconds may be added with internal switches SW3-2 and SW3-3. These delays apply to both phase and ground applications. Closing switch SW3-2 provides an additional delay of 0.1 second. Closing switch SW3-3 provides an additional delay of 0.2 second. Closing both switches SW3-2 and SW3-3 provides an additional delay of 0.3 second. Section 2 illustrates the location of SW3.
On 200 series relays, an additional delay of 0.1 second may be added with internal switch SW3-2. This delay applies to both phase and ground applications. Closing switch SW3-2 provides the additional delay of 0.1 second.
Figure 1-3. Instantaneous Characteristic Curves
9252000991 Rev R BE1-50/51B General Information 1-7

Burden

Burden is non-linear. Figure 1-4 illustrates the device burden.
1 Ampere Unit
0.1 amperes ............................... Z = 120
1.0 ampere ................................. Z = 5
5 Ampere Unit
0.5 amperes ............................... Z = 4.8
5.0 amperes ............................... Z = 0.2
Figure 1-4. Burden Characteristics

Frequency Response

A change of ±5 Hz from the nominal 50/60 Hz current causes <0.5% change in the current required for pickup.

Transient Response

<10% overreach with system time constants up to 40 ms.

Harmonic Response

Figure 1-5 shows that a relay set for 1 ampere pickup would pick up at 0.96 amperes with a current containing 40% seventh harmonic. This corresponds to a 10:1 rejection ratio. Other conditions may be evaluated in the same manner.
1-8 BE1-50/51B General Information 9252000991 Rev R
Figure 1-5. Harmonic Rejection

Target Indicators

Gravity latched, manually reset targets indicate that current of 0.2 amperes or greater was present in the trip circuit. Target coil resistance is less than 0.1 ohms and operate time is less than one millisecond. See Output Contacts for maximum current rating.

Output Contacts

Output contacts are surge protected and rated as follows:
Resistive Ratings
120/240 Vac ............................... Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 5 amperes.
125/250 Vdc ............................... Make 30 amperes for 0.2 seconds, carry 7 amperes for 2 minutes, 3
amperes continuously, and break 0.3 ampere.
Inductive Ratings
120/240 Vac, 125/250 Vdc ........ Make and carry 30 amperes for 0.2 seconds, carry 7 amperes for 2
minutes, 3 amperes continuously, and break 0.3 ampere. (L/R = 0.04).

AUX Output Contact

The AUX Output contact can be configured in the field using jumpers to select closing on either timed or instantaneous trip. The AUX output contact is surge protected and has the same ratings as the output contacts above.

Type Tests

Isolation ..................................... IEEE C37.90-2005
Transient Surge ......................... IEEE C37.90.1-2004
Radiated Interference ................ IEEE C37.90.2-2004
Electrostatic Discharge .............. IEEE C37.90.3-2006
Vibration ..................................... IEC 255-21-1
Shock and Bump ....................... IEC 255-21-2

Environment

Operating Temperature ............. –40°C to 70°C (–40°F to158°F)
Storage Temperature ................ –50°C to 70°C (–58°F to 158°F).
9252000991 Rev R BE1-50/51B General Information 1-9

Agency Recognition

UL Recognized/CSA Certified
UL Recognized per Standard 508, UL File No. E97033. CSA Certified per Standard CAN/CSA-C22.2 No. 14-M91, CSA File No. LR 23131.
Note: Output contacts are not UL Recognized/CSA Certified for voltages greater than 250 volts.
GOST-R Certification
GOST-R certified per the relevant standards of Gosstandart of Russia.

Patent

Patented in U.S., 1998, U.S. Patent No. 5751532.

Physical

Weight ........................................ 8.6 lb (3.9 kg)
1-10 BE1-50/51B General Information 9252000991 Rev R

SECTION 2 • CONTROLS AND INDICATORS

TABLE OF CONTENTS
SECTION 2 • CONTROLS AND INDICATORS ........................................................................................ 2-1
Introduction ............................................................................................................................................ 2-1
Figures
Figure 2-1. Location of Controls and Indicators ........................................................................................ 2-1
Figure 2-2. Location of SW3 and Auxiliary Output Jumper Terminations
Tables
Table 2-1. BE1-50/51B Controls and Indicators (Refer to Figures 2-1 and 2-2) ....................................... 2-3
................................................. 2-2
9252000991 Rev R BE1-50/51B Controls and Indicators i