Badger Meter Turbine Flow Meters User Manual

Activa, Ultima, Classic and Quad
Turbine Flow Sensors
Installation & Operating Instructions
8635 Washington Avenue Racine, WI 53406
Tel: 800-433-5263 or 262-639-6770
Fax: 800-245-3569 or 262-639-2267
E-Mail: info@o-tech.com
www.o-tech.com
Table of Contents
Introduction .................................................................................................................................................................................. 4
Operating Principle ....................................................................................................................................................................5
Specications
Activa™ and Ultima Sensor Arrays ..............................................................................................................................6
Classic Flow Sensors ........................................................................................................................................................... 7
Quad Flow Sensors .............................................................................................................................................................. 8
Installation
Mechanical .............................................................................................................................................................................. 9
Electrical
Standard Magnetic Pick-up ...................................................................................................................................10
IFC (Intelligent Frequency Converter) ..............................................................................................................11
Optional Pressure and Temperature Sensors ...............................................................................................13
Operation ......................................................................................................................................................................................14
Maintenance ................................................................................................................................................................................14
Troubleshooting ........................................................................................................................................................................15
Appendix
Dimensions ...........................................................................................................................................................................16
Flow vs Pressure Drop Charts ......................................................................................................................................17
Returned Goods Authorization ..................................................................................................................................18
Waste and Electronic Equipment (WEEE) Directive ..........................................................................................18
Warranty ........................................................................................................................................................................................19
03/12 Form No. 05-TUR-UM-00194 Page 3
Installation & Operating Instructions
I. INTRODUCTION
Flo-tech turbine ow sensors measure the ow rate of hydraulic uid and compatible liquids. Built to withstand rigorous hydraulic applications, these ow sensors are available in anodized aluminum and zinc plated Stressproof® steel bodies. Port types vary by body material, but include a choice of SAE, BSPP, Code 61 and Code 62, 4-bolt anged options.
Typical applications for the turbine ow sensors include:
• Fluid characteristic measurement on test stands
• Stationary hydraulic system monitoring
• Feedback for hydraulic system control
• Advance warning of impending component failure
• Mobile hydraulic system diagnosis
Flo-tech oers four dierent ow sensor models. Each of these models is available in a wide selection of ow ranges and port sizes.
Activa™ Sensor Array
Features:
• Four ow ranges
• Four port sizes
• Accuracy of ±1% reading @ 32 cSt
• Pressures up to 5800 PSI (400 Bar)
• Temperatures up to 300 °F (150 °C)
• 4-20 mA or 0-5 VDC output for ow
• 4-20 mA output for pressure and temperature
Ultima Sensor Array
Features:
• Four ow ranges
• Four port sizes
• Accuracy of ±1% full scale
• Pressures up to 5800 PSI (400 Bar)
• Temperatures up to 300 °F (150 °C)
• Frequency output for ow
• 4-20 mA output for pressure and temperature
Classic Flow Sensor
Features:
• Eight ow ranges
• Eight port sizes
• Accuracy of ±1% full scale
• Pressures up to 6000 PSI (414 Bar)
• Temperatures up to 300 °F (150 °C)
• Frequency output for ow
Quad Flow Sensor
Features:
• Four ow ranges
• Two port sizes
• Accuracy of ±1% full scale
• Pressures up to 6000 PSI (414 Bar)
• Temperatures up to 300 °F (150 °C)
• Frequency output for ow
Page 4 03/12 Form No. 05-TUR-UM-00194
II. OPERATING PRINCIPLE
1 – Housing 2 – Turbine Rotor 3 – Rotor Supports 4 – Lock Nut 5 – Magnetic Pick-up (frequency output)
Turbine ow sensors measure the ow rate of hydraulic uid and compatible liquids. As uid ows through the sensor it turns the turbine rotor, and as the turbine blades pass the magnetic pick-up a frequency signal is generated. This frequency signal is proportional to the ow rate and can be transmitted to Flo­tech’s digital displays or converted to an analog output. Optional sensors allow measurement of pressure and temperature.
6 – Signal Converter (analog output) 7 – Pressure Port Adapter 8 – Temperature Port Adapter 9 – Retaining Rings
03/12 Form No. 05-TUR-UM-00194 Page 5
Installation & Operating Instructions
III. SPECIFICATIONS
Activa™ and Ultima Sensor Arrays
Material
Housing: 6013-T651 Anodized aluminum Turbine Rotor: T416 Stainless steel Rotor Supports: 6061-T6 Aluminum, C360 Brass for ¼" models Rotor Shaft: T303 Stainless steel Ball Bearings: 440 C Stainless steel Hub Cones: 6061-T6 Aluminum alloy Retaining Rings: 6061-T6 Aluminum alloy Adapters/Plugs: 6061-T6 Anodized aluminum Seals: Buna N standard Viton® and EPR optional Magnetic Pick-up: Body T303 Stainless Steel Nut T303 Stainless Steel IFC (Intelligent Frequency Converter), Activa only: Body 6061-T6 Aluminum, nickel plate Connector Brass, nickel plate
Temperature Probe: 12L14 Steel, electroless nickel nish Pressure Sensor: Case 300 Series stainless steel Diaphragm 17-4 PH stainless steel
Ports: SAE Straight thread O-ring boss, female, J1926/1; ISO1179 (BSPP)
Dimensions See Appendix, page 16
Model Number Information
Performance
Flow Accuracy: Activa ±1% of reading @ 32 cSt Ultima ±1% of full scale Repeatability: ±0.2% Pressure Rating: 5800 PSI (400 Bar) maximum, 5000 PSI (345 Bar) maximum for 1-¼" models Pressure Drop: See ∆ P charts on page 17 Turbine Response: ≤200 ms Fluid Temperature: -4 to +300 °F (-20 to +150 °C) Ambient Temperature: -4 to +131 °F (-20 to +55 °C)
Electrical
Activa 4-20 mA 0-5 VDC
Power: Loop-powered, 6V 10-26 VDC
insertion loss max 10-30 VDC supply
Inputs: Mag pick-up Mag pick-up
Frequency 0-3500 Hz 0-3500 Hz Trigger Sensitivity 30 mV p-p 30 mV p-p
Freq Meas Accuracy ±1% ±1%
Analog Out: 4-20 mA current loop 0-5 VDC
Resolution 1:4000 1:4000 Temp Drift 50 ppm/°C max 50 ppm/°C max
Environmental: Ambient Temp -22 to +158 °F -22 to +158 °F
(-30 to +70 °C) (-30 to +70 °C) Humidity 0-90% 0-90%
non-condensing non-condensing
Ultima
Magnetic Pick-up: Self-generating alternating pulse;
100 mV RMS (100 Hz) minimum. F6202 & F6222 only 10 mV RMS (200Hz) minimum
Calibration
Flow sensors are calibrated with 0.876 specic gravity, 140 SUS (32 cSt) hydraulic oil. Standard calibration is done using 3-points and is traceable to NIST, ISO 9001/ANSI Z540-1 & MIL­STD 45662A.
Nominal Port Size
SAE 8 0.4 - 7 GPM F6202
SAE 12 2 - 40 GPM F6204
SAE 16 4 - 80 GPM F6206
SAE 20 8 - 160 GPM F6208
G ¼ 1.5 - 26 LPM F6222
G ¾ 7.5 - 151 LPM F6224
G 1 15 - 302 LPM F6226
G 1-¼ 30 - 605 LPM F6228
Examples: F6204-AIB-T6 = SAE 12 ports, 2-40 GPM ow range Buna N seals, Temperature sensor 6000 PSI (414 Bar) pressure sensor
Flow Rate Model
IFC
or Mag Pick-up
Activa Models:
AI 4-20 mA Out AV 0-5 VDC Out
Ultima Models:
F Frequency Out
Converter
Seals
B Buna N V Viton E EPR
F6208-FV-TN = SAE 20 ports, 8-160 GPM ow range
Viton seals, Temperature sensor 1/4 NPT (F) plugged pressure port
Temperature Pressure
T with Sensor N ¼ NPT(F)
Plugged
S SAE 2 Plugged G G ¼ Plugged D SAE 4 Plugged
Sensor Ports
1 1000 PSI 3 3000 PSI 5 5000 PSI 6 6000 PSI * N ¼ NPT(F)
Plugged
S SAE 2 Plugged F G ¼ Plugged
* Not available with
Models F6208 or F6228
Page 6 03/12 Form No. 05-TUR-UM-00194
Classic Flow Sensors
Material
Housing: FSC, FSB 6013-T651 Anodized aluminum FSD Stressproof® steel, zinc plated Turbine Rotor: T416 Stainless steel Rotor Supports: FSC-375, 500, 750 C360 Brass FSC-1000, 1005 6061-T6 Aluminum FSD Tungsten carbide Rotor Shaft: FSC, FSB T303 Stainless steel FSD Tungsten carbide Bearings: FSC, FSB 440 C Stainless steel ball bearings FSD Tungsten carbide Hub Cones: FSC, FSB 6061-T6 Aluminum alloy Retaining Rings: FSC T303 Stainless steel FSC-500, 750, 1000, 1005; FSB; FSD Steel, zinc plate Adapters/Plugs: 6061-T6 Anodized aluminum Seals: Buna N standard Viton® and EPR optional Magnetic Pick-up: Body T303 Stainless Steel Nut T303 Stainless Steel IFC (Intelligent Frequency Converter): Body 6061-T6 Aluminum, nickel plate Connector Brass, nickel plate
Ports: SAE Straight thread O-ring boss, female, J1926/1; Code 61 and Code 62: SAE J518
Dimensions See Appendix, page 16
Performance
Flow Accuracy: Standard Magnetic Pick-up ±1% of full scale IFC Converter Option ±1% of reading @ 32 cSt Repeatability: ±0.2% Pressure Rating: FSC, FSB 5000 PSI (345 Bar) maximum, FSD 6000 PSI (414 Bar) maximum Pressure Drop: See ∆ P charts on page 17 Turbine Response: ≤200 ms Fluid Temperature: -4 to +300 °F (-20 to +150 °C) Ambient Temperature: -4 to +131 °F (-20 to +55 °C)
Electrical
Magnetic Pick-up: Self-generating alternating pulse;
100 mV RMS (100 Hz) minimum. FSC-375 only 10 mV RMS (200 Hz) minimum
IFC Converter: 4-20 mA 0-5 VDC
Power: Loop-powered, 6V 10-26 VDC
insertion loss max 10-30 VDC supply
Inputs: Mag pick-up Mag pick-up
Frequency 0-3500 Hz 0-3500 Hz Trigger Sensitivity 30 mV p-p 30 mV p-p
Freq Meas Accuracy ±1% ±1%
Analog Out: 4-20 mA current loop 0-5 VDC
Resolution 1:4000 1:4000 Temp Drift 50 ppm/°C max 50 ppm/°C max
Environmental: Ambient Temp -22 to +158 °F -22 to +158 °F
(-30 to +70 °C) (-30 to +70 °C) Humidity 0-90% 0-90% non-condensing non-condensing
Calibration
Flow sensors are calibrated with 0.876 specic gravity, 140 SUS (32 cSt) hydraulic oil. Standard calibration is done using 3-points and is traceable to NIST, ISO 9001/ANSI Z540-1 & MIL­STD 45662A.
Model Number Information
Nominal Port Size
SAE 8 0.4 - 7 GPM FSC-375 F2945-ASCM F2945-ASCI F2945-ASCV
SAE 12 1 - 15 GPM FSC-500 F2082-ASCM F2082-ASCI F2082-ASCV
SAE 12 2 - 25 GPM FSC-750 F2083-ASCM F2083-ASCI F2083-ASCV
SAE 16 3 - 60 GPM FSC-1000 F2084-ASCM F2084-ASCI F2084-ASCV
SAE 16 4 - 85 GPM FSC-1005 F2084-ASCM8 F2084-ASCI8 F2084-ASCV8
SAE 20, Code 61 5 - 100 GPM FSB-1250 F2085-ASBM F2085-ASBI F2085-ASBV
SAE 24, Code 61 7 - 200 GPM FSB-1500 F2086-ASBM F2086-ASBI F2086-ASBV
SAE 20, Code 62 5 - 100 GPM FSD-1250 F2085-SCDM F2085-SCDI F2085-SCDV
SAE 24, Code 62 7 - 200 GPM FSD-1500 F2086-SDCM F2086-SCDI F2086-SCDV
SAE 32, Code 62 10 - 350 GPM FSD-2000 F2998-SCDM F2998-SCDI F2998-SCDV
Flow Rate Series
03/12 Form No. 05-TUR-UM-00194 Page 7
Model
with Frequency Out
Model
with 4 - 20 mA Out
Model
with 0 - 5 Vdc Out
Installation & Operating Instructions
Quad Flow Sensors
Material
Housing: 6013-T651 Anodized aluminum Turbine Rotor: T416 Stainless steel Rotor Supports: 6061-T6 Aluminum Rotor Shaft: T303 Stainless steel Bearings: 440 C Stainless steel ball bearings Hub Cones: 6061-T6 Aluminum alloy Retaining Rings: Steel, zinc plate Seals: Buna N standard Viton® and EPR optional Magnetic Pick-up: Body T303 Stainless Steel Nut T303 Stainless Steel
Ports: SAE Straight thread O-ring boss, female, J1926/1;
Dimensions See Appendix, page 16
Model Number Information
Performance
Flow Accuracy: ±1% of full scale Repeatability: ±0.2% Pressure Rating: 5000 PSI (345 Bar) maximum, Pressure Drop: See ∆ P charts on page 17 Turbine Response: ≤200 ms Fluid Temperature: -4 to +300 °F (-20 to +150 °C) Ambient Temperature: -4 to +131 °F (-20 to +55 °C)
Electrical
Magnetic Pick-up: Self-generating alternating pulse;
100 mV RMS (100 Hz) minimum.
Calibration
Flow sensors are calibrated with 0.876 specic gravity, 140 SUS (32 cSt) hydraulic oil. Standard calibration is done using 3-points and is traceable to NIST, ISO 9001/ANSI Z540-1 & MIL­STD 45662A.
Nominal Port Size
SAE 12 1 - 15 GPM FSC-2005 F2082-ASCQ4
SAE 12 2 - 25 GPM FSC-2075 F2083-ASCQ4
SAE 16 3 - 60 GPM FSC-2100 F2084-ASCQ4
SAE 16 4 - 85 GPM FSC-2150 F2085-ASCQ4
Flow Rate Series Model
Page 8 03/12 Form No. 05-TUR-UM-00194
IV. INSTALLATION
CAUTION
This product should be installed and serviced by technically qualied personnel trained in maintaining industrial class ow instrumentation and processing equipment.
CAUTION
Read instructions thoroughly before installing the ow sensor. If you have any questions regarding product installation or maintenance, call your local supplier or the factory for more information.
WARNING
Do not use male pipe threads (NPT) into SAE straight thread ports. Using male pipe threads (NPTF) with a ow sensor possessing SAE straight thread O-ring ports will not create a proper seal and is potentially dangerous. Pipe threads inserted into an SAE straight thread port only allow the engagement of one or two threads. No amount of tightening or thread seal will stop the leaking or make the installation safe. Failure to follow these instructions could result in serious personal injury or death and/or damage to the equipment.
Installation Recommendations
The in-line ow sensor is a simple device to install. However, the following measures are recommended for reliable, trouble-free operation:
DO - Provide at least 10 port diameters of upstream straight pipe with no obstructions to the ow sensor and at least 5 diameters of downstream pipe. The pipe should be of the same diameter as the nominal port size.
Example: An FSC-1000 has a one inch (25.4 mm) port. The unobstructed upstream length should be at least 10 inches (254 mm) and the downstream length should be at least 5 inches (127 mm).
1" PORT
(25.4 mm)
END VIEW
10 PORT DIAMETERS
10" (254 mm)
Upstream and Downstream Pipe Diameters
03/12 Form No. 05-TUR-UM-00194 Page 9
IN
FIGURE 1
5 PORT DIAMETERS
5" (127 mm)
Installation & Operating Instructions
DO - Choose a position for the ow sensor that will not be at the lowest level in the system. Placing the
ow sensor at a higher elevation in the system will avoid collection of debris, sediment and dirt in the ow sensor.
DO - Use a lter. All applications should be ltered to at least 40 micron.
DON’T - Locate a ow sensor directly in-line with the outlet of a pump, as pressure pulsations can react
with the turbine. Locate the sensor after another component, observing the 10 port diameter rule.
DON’T - Adjust the magnetic pick-up on the ow sensor. This is calibrated at the factory. Further adjustment will cause a decrease in performance or damage to the sensor.
DON’T - Exceed the working temperature range of –4 °F to +300 °F (–20 °C to +150 °C). Higher temperatures will damage the magnetic pick-up and lower temperatures will limit the rotation of the turbine.
Electrical Connections - Standard Magnetic Pick-up
A
B
Magnetic Pick-up
Male Connector
2
1
3
A - (RED) B - (BLACK) -
Standard Magnetic Pick-up with Frequency Output – 2-pin Connector
1 - (WHITE) N.C. 2 - (BLACK) ­3 - (RED) +
+
B A
Top of
F2832 Cable
2
3
1
FIGURE 2
Cable Assembly F2832-6 6 Ft. F2832-15 15 Ft.
Cable Assembly F6234-6 6 Ft. F6234-15 15 Ft.
(BLACK) -
(RED)
+
(WHITE) N.C.
(BLACK) -
(RED)
+
(WHITE) N.C.
Magnetic Pick-up
Male Connector
Top of
F6234 Cable
FIGURE 3
Standard Magnetic Pick-up with Frequency Output – 3-pin Connector
Page 10 03/12 Form No. 05-TUR-UM-00194
Electrical Connections - IFC (Intelligent Frequency Converter)
3
4
5
F to I Converter Male Connector
2
1
+ 4 - 20 mA
- 4 - 20 mA N.C. N.C. N.C.
PIN 1 PIN 2 PIN 3 PIN 4 PIN 5
RED BLACK WHITE
FIGURE 4
IFC with 4-20 mA Output (F to I) – 5-pin Connector
The 4-20 mA output can drive auxiliary devices (resistive loads) such as displays, recorders and computers, provided that the voltage supplied by the power supply is adequate. Devices must be wired in series with the F to I converter and power supply. The voltage drop across the load(s) and the 6 Vdc minimum needed to drive the F to I converter determine the minimum voltage required from the power supply.
Determine the necessary voltage required to adequately drive the F to I converter and auxiliary device(s).
The F to I converter acts as a current controlling device. Thus, the current output remains the same even if the power supply voltage uctuates or the load resistance changes. The current varies only with respect to the ow rate from the turbine ow sensor, as long as the voltage drop across the F to I converter is at least 6 Vdc.
The load(s) in the circuit will generally have some electrical resistance, 100 Ohms for this example. The 4-20 mA loop current will produce a voltage drop across each load. The maximum voltage drop across a load(s) will exist when the loop current is 20 mA. The power supply must provide enough voltage for the load(s) plus the 6 Vdc minimum insertion loss of the F to I converter.
+ 4 - 20 mA (Sink)
- 4 - 20 mA (Source) No Connection
Cable Assembly F6557-6 6 Ft. F6557-15 15 Ft.
At 20 mA loop current, the voltage drop across the load(s)
Subtract 6 volts from the 24 volt source to determine that 18 volts is available to power the F to I converter. The 18 volts is within the specified 10 to 30 volt range and is sufficient to power the F to I converter.
At 20 mA loop current, the voltage drop across the load(s)
Subtract 20 volts from the 24 volt source to determine that 4 volts is available to power the F to I converter. The 4 volts is below the specified 10 to 30 volt range and is not adequate to power the F to I converter. If for example, the power supply voltage was 30 volts instead of 24 volts, the voltage available to power the F to I converter would be 10 volts and within the specified range.
3
2
1
Cable
Connector
4
5
(RED)
Loop
+
(BLACK) - Loop
(WHITE) N.C.
Example 1
Sufficient Power Supply Voltage
F to I
Converter
Total Load Resistance = 300 Ohms
300 Ohms × 20 mA = 6,000 mV or 6 volts
4 - 20 mA
150
Ohms
is 6 volts:
100
Ohms50Ohms
24 VDC
Power Supply
Example 2
Insufficient Power Supply Voltage
F to I
Converter
Total Load Resistance = 1000 Ohms
1000 Ohms × 20 mA = 20,000 mV or 20 volts
4 - 20 mA
1000 Ohms
is 14 volts:
24 VDC
Power Supply
FIGURE 5
Power Supply Voltage Examples
03/12 Form No. 05-TUR-UM-00194 Page 11
1400
1200
1000
800
600
400
Loop Load (Ohm's)
200
10 12 14 16 18 20 22 24
Operate in the
Shaded Region
Supply Voltage (VDC)
FIGURE 6
Loop Resistance Chart
Installation & Operating Instructions
28 30
26
4
5
F to V Converter
Male Connector
3
2
2
+10 - 26 VDC
1
SIGNAL GND N.C.
N.C.
N.C.
N.C.
PIN 1 PIN 2 PIN 3 PIN 4 PIN 5
RED BLACK WHITE
+10 to 26 VDC
SIGNAL 0 V
1
Connector
Cable Assembly F6557-6 6 Ft. F6557-15 15 Ft.
3
4
5
Cable
(RED) 10 - 26 VDC (BLACK) SIGNAL
(WHITE) 0 V
FIGURE 7
IFC with 0-5 Vdc Output (F to V) – 5-pin Connector
Page 12 03/12 Form No. 05-TUR-UM-00194
Electrical Connections - Optional Pressure and Temperature Sensors
Cable Assembly F6234-6 6 Ft.
2
3
2 - - Signal Output (BLACK)
1
3 - + Voltage (RED)
1 - N/C (WHITE)
2
3
1
F6234-15 15 Ft.
(BLACK) -
(RED)
+
(WHITE) N.C.
Pressure Sensor
Male Connector
2
1
3
Temperature Sensor
Male Connector
Pressure Sensor, Optional – 3-pin Connector
1 - Case Ground (WHITE) 2 - - Signal Output (BLACK) 3 - + Voltage (RED)
Temperature Sensor, Optional – 3-pin Connector
Top of
F6234 Cable
2
3
1
Top of
F6234 Cable
FIGURE 8
FIGURE 9
Cable Assembly F6234-6 6 Ft. F6234-15 15 Ft.
(BLACK) -
(RED)
+
(WHITE) N.C.
03/12 Form No. 05-TUR-UM-00194 Page 13
Installation & Operating Instructions
V. OPERATION
General
WARNING
Do not exceed allowable pressure ratings. Pressure in excess of the maximum allowable ratings may cause the turbine body to fail. Failure to follow these instructions could result in serious personal injury or death and/or damage to the equipment.
DO - Allow uids to warm to operating temperatures before critical measurements are taken.
DO - Maintain a ooded condition in the ow sensor at all times. Air and turbulence will result in erroneous
readings.
DON’T - Exceed the working temperature range of –4 °F to +300 °F (–20 °C to +150 °C). Higher temperatures will damage the magnetic pick-up and lower temperatures will limit the rotation of the turbine.
Flow Sensors with IFC Option
As soon as power is applied, the IFC will begin to output an analog value representative of the measured frequency from the turbine meter.
Refer to the wiring diagram that corresponds to the IFC being utilized. See pages 11 and 12.
VI. MAINTENANCE
WARNING
Always disconnect the primary power source before inspection or service. Failure to follow these instructions could result in serious personal injury or death and/or damage to the equipment.
1. A schedule for maintenance checks should be determined based upon environmental conditions and frequency of use. Inspect at least once a year.
2. Perform visual, electrical and mechanical checks on all components.
a. Visually check for undue heating evidenced by discoloration of wires or other components,
damaged or worn parts, or excessive corrosion of the device.
b. Electrically check to make sure that all connections are clean and tight and that the device is
operating properly.
Page 14 03/12 Form No. 05-TUR-UM-00194
VII. TROUBLESHOOTING
TROUBLE POSSIBLE CAUSE REMEDY
Sensor indicates higher than actual ow rate
• Cavitation
• Debris on straightening section
• Build-up of foreign material on sensor
bore
• Gas in liquid
• Increase back pressure
• Clean sensor
• Clean sensor
• Install gas eliminator ahead of sensor
Sensor indicates lower than actual ow rate
Erratic indications on readout
Readout shows ow when pumps are not running
No ow indication at any ow rate
Erratic indications at low ows, but good indications at high ows
System works except readings are lower than expected
No current output • Low or missing supply voltage
Analog output reads a constant reading all the time
Analog output is not stable
• Debris on turbine
• Worn bearing
• Any of the above
• Ground loop problem
• Turbulence in uid stream
• Mechanical vibration or pump dither
causes turbine to oscillate even though there is no ow
• Foreign material stopping turbine rotation
• Damaged turbine and/or bearing
• Magnetic pick-up stopping turbine
rotation
• Magnetic pick-up shorted or open
• Foreign material wrapped around
turbine
• Flow is being bypassed
• System has a leak
• Broken / disconnected wires
• Incorrect wiring polarity
• Electrical noise in vicinity
• Damaged electronics
• Electrical noise in vicinity
• Entrained gas in liquid
• Damaged meter rotor
• Foreign matter lodged in turbine
• Clean sensor and add lter
• Have sensor serviced and add lter
• Any of the above
• Be sure only one system ground is
present. Reroute cables away from electrical noise
• Redo plumbing per instructions
• Isolate ow sensor
• Clean sensor and add lter
• Have sensor serviced
• Readjust magnetic pick-up away from
turbine
• Have magnetic pick-up replaced
• Clean sensor and add lter
• Repair or replace faulty valves
• Find and repair any system leaks
• Check polarity of the current loop
connections for proper orientation
• Make sure receiving device is congured to provide loop current
• Make sure there is ow in the system
• Verify that the rotor inside the turbine
meter turns freely
• Check shield
• Remove noise producing device
• External noise is being picked up by
the sensor. Keep all AC wires separate from DC wires.
• Check for radio antenna in close proximity. This usually indicates a weak signal.
• Clean meter
• Recalibrate meter
03/12 Form No. 05-TUR-UM-00194 Page 15
VIII. APPENDIX
B
C
Magnetic Pickup
Housing
A
D
E
B A
Magnetic Pickup
Housing
C
D
Pressure Port
Adapter
Temperature Port
Adapter
Dimensions
Installation & Operating Instructions
Activa Series
Signal Converter
Pressure Port
Adapter
Housing
B A
Ultima Series
Classic Series
FSC
Magnetic Pickup
Housing
B
FSB
Magnetic Pickup
Housing
B
FSD
Magnetic Pickup
Temperature Port
Adapter
C
D
C
A
D
C
A
SERIES
WIDTH
IN (mm)
D
F6202 / F6222 1.23 (31.2) 4.72 (120.0) 1.47 (37.3) 5.74 (145.6) 1.60 (0.73)
B LENGTH IN (mm)
C HEIGHT IN (mm)
D
HEIGHT
IN (mm)
WEIGHT
LBS
(KG)
F6204 / F6224 1.48 (37.6) 5.08 (129.0) 1.80 (45.7) 6.04 (153.0) 1.90 (0.86)
F6206 / F6226 1.98 (50.3) 5.87 (149.0) 2.20 (56.0) 6.50 (164.0) 2.80 (1.27)
F6208 / F6228 2.46 (62.5) 6.81 (173.0) 2.48 (63.0) 6.74 (171.0) 4.20 (1.91)
SERIES
A
WIDTH
IN (mm)
B LENGTH IN (mm)
C HEIGHT IN (mm)
D HEIGHT IN (mm)
WEIGHT
LBS
(KG)
F6202 / F6222 1.23 (31.2) 4.72 (120.0) 1.47 (37.3) 5.74 (145.6) 1.60 (0.73)
F6204 / F6224 1.48 (37.6) 5.08 (129.0) 1.80 (45.7) 6.04 (153.0) 1.90 (0.86)
F6206 / F6226 1.98 (50.3) 5.87 (149.0) 2.20 (56.0) 6.50 (164.0) 2.80 (1.27)
F6208 / F6228 2.46 (62.5) 6.81 (173.0) 2.48 (63.0) 6.74 (171.0) 4.20 (1.91)
E
SERIESAWIDTH
IN (mm)
B LENGTH IN (mm)
C
HEIGHT
IN (mm)
D
W/MAG
IN (mm)
E
W/IFC
IN (mm)
WEIGHT
LBS
(KG)
FSC-375 1.25 (32) 5.00 (127) 1.50 (38) 3.91 (99) 5.48 (139) 1.25 (0.57)
FSC-500 2.00 (51) 6.50 (165) 2.00 (51) 4.16 (106) 5.84 (148) 2.75 (1.25)
FSC-750 2.00 (51) 6.50 (165) 2.00 (51) 4.25 (108) 5.93 (151) 2.87 (1.30)
E
FSC-1000 2.50 (64) 6.50 (165) 2.00 (51) 4.34 (110) 5.97 (152) 3.25 (1.48)
FSC-1005 2.50 (64) 6.50 (165) 2.00 (51) 4.34 (110) 5.97 (152) 3.25 (1.48)
FSB-1250 4.00 (102) 7.00 (178) 3.00 (76) 4.94 (126) 6.43 (165) 7.75 (3.52)
A
FSB-1500 4.00 (102) 7.00 (178) 3.00 (76) 5.10 (130) 6.59 (167) 7.40 (3.36)
FSD-1250 2.12 (54) 7.50 (190) 2.125 (54) 4.50 (114) 5.17 (131) 6.12 (2.78)
FSD-1500 2.50 (64) 7.50 (190) 2.500 (64) 4.85 (123) 5.34 (135) 6.75 (3.06)
FSD-2000 3.12 (79) 8.25 (209) 3.125 (79) 5.39 (137) 5.45 (138) 8.55 (3.88)
Page 16 03/12 Form No. 05-TUR-UM-00194
Quad Series
Magnetic Pickup (2)
Housing
B A
B
SERIESAWIDTH
IN (mm)
D
C
FSC-2005 2.00 (51) 6.50 (165) 2.00 (51) 4.16 (106) 4.05 (102) 2.75 (1.25)
FSC-2075 2.00 (51) 6.50 (165) 2.00 (51) 4.25 (108) 4.05 (102) 2.87 (1.30)
LENGTH IN (mm)
C HEIGHT IN (mm)
D
W/MAG
IN (mm)
E
W/MAG
IN (mm)
WEIGHT
LBS
(KG)
FSC-2100 2.50 (64) 6.50 (165) 2.00 (51) 4.34 (110) 4.59 (117) 3.25 (1.47)
E
FSC-2150 2.50 (64) 6.50 (165) 2.00 (51) 4.34 (110) 4.59 (117) 7.75 (3.52)
Flow vs Pressure Drop Charts
Activa and Ultima Series
100
F6202
10
F6204
F6206
F6208
F6222
F6224
F6226
F6228
PRESSURE DROP PSI
1
.1
.1 1 10 100 300
FLOW GPM
PRESSURE DROP BAR
.1 10 100 1000
FLOW LPM
Classic Series
50
FSC-375
FSC-500
10
PRESSURE DROP PSI
.1
.1 10 100 500 10 100 1000 2000
FSC-750
FLOW GPM FLOW LPM
FSC-1000 FSC-1005
FSB-1250 FSD-1005
FSB-1500 FSD-1500
FSD-2000
PRESSURE DROP BAR
0.1
0.07
4
FSC-375
FSC-500
1
FSC-750
FSC-1000 FSC-1005
FSB-1250 FSD-1005
FSB-1500 FSD-1500
FSD-2000
Quad Series
50
FSC-2005
10
FSC-2075
FSC-2100 FSC-2150
PRESSURE DROP PSI
1
1 10 100 500
FLOW GPM
03/12 Form No. 05-TUR-UM-00194 Page 17
PRESSURE DROP BAR
0.1
0.07
4
FSC-2005
1
FSC-2075
10 100 1000 2000
FSC-2100 FSC-2150
FLOW LPM
Installation & Operating Instructions
Return Goods Authorization
When returning equipment for service, a Returned Goods Authorization (RGA) number must be obtained from our Service Department. Please contact them by phone at 800-433-5263 or 262-639-6770 or by e-mail to info@o-tech.com.
All returns go to the following address and must include the RGA number on the outside of the box:
Flo-tech
Division of Racine Federated Inc.
8635 Washington Avenue
Racine, WI 53406-3738 USA
Attn: RGA # xxx-xxxx
Waste and Electronic Equipment (WEEE) Directive
In the European Union, this label indicates that this product should not be disposed of with household waste. It should be deposited at an appropriate facility to enable recovery and recycling.
For information on how to recycle this product responsibly in your country, please visit:
www.racinefed.com/recycle/
Page 18 03/12 Form No. 05-TUR-UM-00194
Division of Racine Federated Inc.
Limited Warranty and Disclaimer
Flo-tech, Division of Racine Federated Inc. warrants to the end purchaser, for a period of one year from the date of shipment from the factory, that all ow meters manufactured by it are free from defects in materials and workmanship. This warranty does not cover products that have been damaged due to misapplication, abuse, lack of maintenance, or improper installation. Flo-tech’s obligation under this warranty is limited to the repair or replacement of a defective product, at no charge to the end purchaser, if the product is inspected by Flo­tech and found to be defective. Repair or replacement is at Flo-tech’s discretion. A returned goods authorization (RGA) number must be obtained from Flo-tech before any product may be returned for warranty repair or replacement. The product must be thoroughly cleaned and any process chemicals removed before it will be accepted for return.
Flo-tech
The purchaser must determine the applicability of the product for its desired use and assumes all risks in connection therewith. Flo-tech assumes no responsibility or liability for any omissions or errors in connection with the use of its products. Flo-tech will under no circumstances be liable for any incidental, consequential, contingent or special damages or loss to any person or property arising out of the failure of any product, component or accessory.
All expressed or implied warranties, including the implied warranty of merchantability
and the implied warranty of tness for a particular purpose or application are expressly disclaimed and shall not apply to any products sold or services rendered by Flo-tech.
The above warranty supersedes and is in lieu of all other warranties, either expressed or implied and all other obligations or liabilities. No agent or representative has any authority to alter the terms of this warranty in any way.
03/12 Form No. 05-TUR-UM-00194 Page 19
o-tech.com
8635 Washington Avenue  Racine, WI 53406-3738
Tel: 800-433-5263 or 262-639-6770 Fax: 800-245-3569 or 262-639-2267
E-Mail: info@o-tech.com
Flo-tech and Activa are trademarks of Racine Federated Inc. VITON is a registered trademark of DuPont Dow Elastomers. STRESSPROOF is a registered trademark of LaSalle Steel Corporation. UL is a registered trademark of Underwriters Laboratories.
© 2010 Racine Federated Inc., all rights reserved.
Specications are subject to change without notice.
03/12 Form No. 05-TUR-UM-00194
Loading...