Badger Meter R9120-5 Specifications

Wireless Modbus/Pulse Transceiver
ModHopper R9120-5
DESCRIPTION
The ModHopper R9120-5 is a breakthrough mesh technology design that makes connecting Modbus and pulse devices simple and cost effective. Our smart ModHopper transceivers eliminate the need for costly wiring runs, allowing users to capture meter data in the most challenging retrofit and campus environments. Collect meter points in existing buildings with minimum downtime or disruption of day-to-day operations.
Designed specifically for wireless metering
256 Bit AES, FIPS-197 certified, J/F-12 8306
No software or programming required
Devices automatically configure when powered
Wireless mesh network self-healing, self-optimizing
Frequency hopping, spread spectrum (FHSS)
Connect up to 32 Modbus and 2 pulse devices per ModHopper (expandable)
Long distance communication (3000 ft indoor/14 miles LOS)
Visual display of signal strength (LEDs)
Multiple independent network capability
Reliable, constant two-way communication and packet verification
Point to multi-point communication
Field upgradable firmware
Wireless Communication
Badger Meter developed a wireless Modbus/Pulse transceiver to capture remote meter points. Our high-powered radios allow you to easily collect meter data from multiple buildings over long distances. Our unique mesh technology provides optimized routing of communications with no PC or software configuration, meaning the ModHopper works immediately “out of the box.” This self-managed mesh network means that the system functions with high reliability where other wireless systems fail due to short-term or long-term interference. ModHoppers can be used with any Modbus Master or gateway, making them an ideal solution for any project. Ask us about international frequency options.
Partners
Badger Meter's outstanding integration and software partners supplement our products and services so you receive the very best energy monitoring solution.
Compatibility
The ModHopper is compatible with virtually any PLC or Modbus RTU device, allowing customers the flexibility to use the ModHopper in existing Modbus applications. The ModHopper is a smart device that requires no programming. If used with the Badger Meter Model 3700, the ModHopper offers numerous diagnostic tools, including a graphical display of the wireless mesh network.
Applications
Utility submetering (electric, gas, water and other services)
Metering in existing buildings (retrofit)
Metering on campus environments
Government advanced metering projects (256 Bit AES, FIPS-197 certified, J/F-12 8306)
Multi-tenant submetering projects
Industrial/manufacturing facilities
Demand response
Renewable energy—PV projects (inverters, string monitoring)
XMT-DS-00638-EN-02 (June 2016)
Product Data Sheet
Wireless Modbus/Pulse Transceiver, ModHopper R9120-5
SPECIFICATIONS
Processor 60 MHz ARM7 embedded CPU LEDs 3 x RF, 2 x RS-485, 2 x Pulse, Alive, Alarm Power North America: 110…120V AC, 60 Hz, primary, 9…12V DC class 2 power supply included
CE/Europe: 100…240V AC, 50…60 Hz, primary (power supply not included)
Communication
Protocols Modbus RTU, 2-wire
Addressing Modbus address may be set from 1…247 via DIP switch
Baud Rate 9600/19200 baud, N, 8, 1
RF Frequency hopping, spread spectrum (FHSS), ISM band (see table)
Inputs
I/O 2x Pulse, dry contact, standard or KYZ, closure threshold 100 Ω…2.5 Ω user selectable
Pulse Rate User selectable to 10 Hz, 50 Hz, 100 Hz, 250 Hz
Pulse rate option 10 Hz, minimum pulse width 50 ms Pulse rate option 50 Hz, minimum pulse width 10 ms Pulse rate option 100 Hz, minimum pulse width 5 ms Pulse rate option 250 Hz, minimum pulse width 2 ms
Storage Pulse counts stored in non-volatile memory
Modbus Modbus RTU, 2-wire, hard-wire connect up to 32 devices (expandable) Range R9120-5: 900 MHz, 1 W, 3000 ft (900 m) indoor, 14 miles (22 km) line-of-sight Weight 1.25 lb (0.67 kg) Size 6.5 in. × 4.5 in. × 2 in. (260 mm × 64 mm × 45 mm) Environmental North America: 0…50° C, 0…90% RH, non-condensing
CE/Europe: 5…40° C, 0…90% RH, non-condensing
Altitude 2000 m maximum Pollution Degree 2 Codes and Standards
FCC ID FCC ID OUR-9XTEND
IC (Industry Canada) IC 4214A-9XTEND; FCC CFR 47 Part 15, Class A
Encryption 256 Bit AES
Additional Notes
The R9120-5 is not cross-compatible with the Badger Meter 345WT. For use with any Modbus RTU device/server.
As per SIPCO LLC, this product may be used in a system and employ or practice certain features and/or methods of one or more of the following patents: U.S. Patent No. 7,103,511, U.S. Patent No. 6,914,893, U.S. Patent No. 6,891,838, U.S. Patent No. 5,714,931, U.S. Patent No. 6,233,327, U.S. Patent No. 7,397,907, U.S. Patent No. 6,618,578, U.S. Patent No. 7,079,810, U.S. Patent No. 7,295,128, U.S. Patent No. 7,263,073, U.S. Patent No. 7,480,501, U.S. Patent No. 6,437,692, U.S. Patent No. 7,468,661, U.S. Patent No. 7,053,767, U.S. Patent No. 7,650,425, U.S. Patent No. 7,739,378
Control. Manage. Optimize.
Data Industrial is a registered trademark of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specications without notice, except to the extent an outstanding contractual obligation exists. © 2016 Badger Meter, Inc. All rights reserved.
www.badgermeter.com
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400 México | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazón N°32 | Esq. Angelina N°24 | Colonia Guadalupe Inn | CP 01050 | México, DF | México | +52-55-5662-0882 Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuen | Germany | +49-7025-9208-0 Europe, Middle East Branch Oce | Badger Meter Europe | PO Box 341442 | Dubai Silicon Oasis, Head Quarter Building, Wing C, Oce #C209 | Dubai / UAE | +971-4-371 2503 Czech Republic | Badger Meter Czech Republic s.r.o. | Maříkova 2082/26 | 621 00 Brno, Czech Republic | +420-5-41420411 Slovakia | Badger Meter Slovakia s.r.o. | Racianska 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01 Asia Pacic | Badger Meter | 80 Marine Parade Rd | 21-06 Parkway Parade | Singapore 449269 | +65-63464836 China | Badger Meter | 7-1202 | 99 Hangzhong Road | Minhang District | Shanghai | China 201101 | +86-21-5763 5412 Switzerland | Badger Meter Swiss AG | Mittelholzerstrasse 8 | 3006 Bern | Switzerland | +41-31-932 01 11 Legacy Document Number: R9120-5_1