Badger Meter Preso Gemini Cone User Manual

Page 1
Dierential Pressure Flow Meter
Gemini Cone
DPM-UM-00206-EN-03 (June 2018)
User Manual
Page 2
Dierential Pressure Flow Meter, Gemini Cone
Page ii June 2018DPM-UM-00206-EN-03
Page 3
User Manual
CONTENTS
Scope of This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Unpacking and Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Valve Manifolds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Shuto Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Dierential Pressure Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Straight Pipe Run Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Mounting Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Meter Orientation and Transmitter Position . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Pressure Tap Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Line Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Dierential Pressure Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Transmitter Connection Tubing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Full Port Block Valves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Impulse Tubing Size Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Impulse Tubing Length and Conguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Meter Installation for Liquid Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Installation Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Horizontal Meter Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Bubble Pot Installation (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Vertical Meter Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Page iii June 2018 DPM-UM-00206-EN-03
Page 4
Dierential Pressure Flow Meter, Gemini Cone
Transmitter Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Meter Installation for Gas Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Installation Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Horizontal Meter Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Condensate Chamber (Drip Pot) (Optional for Wet Gas) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Vertical Meter Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Transmitter Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Meter Installation for Steam Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Installation Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Horizontal Meter Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Vertical Meter Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Transmitter Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
System Modications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Square Root Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Gauge Line Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Elevation and Temperature Eects in Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Part Number Construction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Wafer Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Threaded and Socket Weld Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Flanged Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Butt Weld Mount . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Page iv June 2018DPM-UM-00206-EN-03
Page 5

Scope of This Manual

SCOPE OF THIS MANUAL
This manual contains instructions for installing and operating the Preso® Gemini Cone Differential Pressure Flow Meter.
MPORTANTI
Read this manual carefully before attempting any installation or operation. Keep the manual accessible for future reference.

SAFETY

Terminology and Symbols

Indicates a hazardous situation, which, if not avoided, is estimated to be capable of causing death or serious personal injury.
Indicates a hazardous situation, which, if not avoided, could result in severe personal injury or death.
Indicates a hazardous situation, which, if not avoided, is estimated to be capable of causing minor or moderate personal injury or damage to property.

Considerations

WARNING
NEVER OPEN A MANIFOLD VALVE OR FLANGE UNLESS YOU HAVE FIRST VERIFIED THAT THE SYSTEM IS COMPLETELY DEPRESSURIZED. DURING LIQUID OR WET GAS SERVICE, OPEN VALVES VERY SLOWLY TO AVOID SLUGGING IN THE METER RUN.
WARNING
SECURE ALL CONNECTIONS PROPERLY BEFORE STARTING UP A SYSTEM. KEEP A SAFE DISTANCE AWAY FROM THE PROCESS UPON STARTUP.
WARNING
BE MINDFUL OF STATIC ELECTRICITY GENERATED BY INSULATED FOOTWEAR ETC., AND ALWAYS GROUND YOURSELF BEFORE TOUCHING PIPES IN THE HAZARDOUS AREA WHERE FLAMMABLE GAS IS BEING METERED OR MAY BE PRESENT.

UNPACKING AND INSPECTION

Upon opening the shipping container, visually inspect the product and applicable accessories for any physical damage such as scratches, loose or broken parts, or any other sign of damage that may have occurred during shipment.
OTE:N If damage is found, request an inspection by the carrier’s agent within 48 hours of delivery and file a claim with the
carrier. A claim for equipment damage in transit is the sole responsibility of the purchaser.
WARNING
ALWAYS USE PROPER PROCEDURES AND EQUIPMENT FOR LIFTING AND MOVING THE GEMINI CONE METER TO AVOID RISK OF INJURY.
Page 5 June 2018 DPM-UM-00206-EN-03
Page 6

Introduction

INTRODUCTION
The Preso Gemini Cone meter is a differential pressure device that combines excellent performance with many benefits including low maintenance, low head loss and a unique ability to have none/minimum straight pipe runs in front of the meter. The Gemini Cone meter produces a pressure differential across a pair of pressure measurement ports. The movement of a fluid around the cone-shaped element creates a pressure differential between an upstream and a downstream pressure port, which is processed by a differential pressure transmitter to provide the flow rate. The conical shape of the element also causes the flow meter to act as a flow straightener, pre-conditioning the flow and making the Gemini Cone meter a versatile measuring instrument for many applications. Badger Meter takes pride in designing an optimized differential pressure metering solution for your system.

Theory of Operation

The Preso Gemini Cone meter creates a differential pressure that is proportional to the rate fluid flow. A transmitter measures the differential pressure and outputs an integrated electronic signal, typically via Modbus or a 4…20 mA output, to a flow computer or other process controller for interpretation and readout. For compressible fluids, line pressure and temperature measurements are required for accurate flow rate calculations as well as compensation for the adiabatic change in the expansion factor. As fluid flowing through the pipe flows around the cone, a pressure drop occurs. The static line pressure (P1) is measured via a wall tap located just upstream of the cone. Pressure is also measured via a sensing tap that is connected to the cone and measures pressure at a point immediately downstream of the cone (P2). The fluid flow rate is calculated from the difference between the two pressures using variations of the Bernoulli flow principles and equations.
High Pressure
Port (P1)
∆P
Low Pressure
Port (P2)
Flow
Support and Cone
Assembly
Figure 1: Principles of operation
Meter Body

Applications

The Gemini Cone meter is designed to work in unprocessed and processed applications, and is ideal for applications that present a wide range of measurement challenges. The Gemini Cone meter is a great solution for steam and boilers, coke oven gas, multiphase (non-homogeneous) fluids, biogas and industrial gas management.
Page 6 June 2018DPM-UM-00206-EN-03
Page 7
Introduction

Meter Components

The meter comprises three primary elements, as shown in Figure 1 on page 6:
• A meter body or tube with various available end connections.
• A cone assembly, either fabricated or machined from a solid piece of metal, positioned in the center of the meter tube.
• A pair of pressure taps—a wall tap upstream and an integral sensing tap downstream—for reading the differential pressure across the center of the meter tube. (Alternately a downstream tap may be used under certain process measurement conditions.)
The meter can be manufactured from various materials (carbon and stainless steels are standard, but more exotic materials such as duplex stainless steel or nickel-based alloys are also available upon request) to meet the specific requirements for metering steam, air, natural gas, digester gas, nitrogen, ethanol, and a host of media from crude oil to industrial gases.
Preso Gemini Cone meters are differential pressure flow devices providing highly accurate and repeatable measurements of liquids, gases and steam. The meter design provides longer lasting accuracy and lower permanent pressure loss than orifice type meters, reducing maintenance and operating costs. The Gemini Cone can be built to meet the highest pressure and temperature specifications often limited in other flow meter technologies. All models can also be supplied with RTD's and transmitters to provide an economical mass flow measurement solution.

System Components

Valve Manifolds

A 3-way or 5-way valve manifold isolates the transmitter from the process lines. A manifold allows the operator to calibrate the transmitter without removing it from the impulse tubing, draining the transmitter and impulse tubing or venting it to atmosphere. Valve manifolds must be oriented according to the manufacturer’s instructions to prevent trapping air or liquid.

Shutoff Valves

Choose a blocking valve that is rated for the operating pressure of the pipe in which it will be installed. Where dangerous or corrosive fluids or gases like oxygen are likely, the blocking valve and packing must provide ample protection. The valves must not affect the transmission of the differential pressure signal.
Install blocking valves next to the Gemini Cone meter pressure taps.

Differential Pressure Transmitter

A differential pressure transmitter interprets the differential pressures generated by the cone within the meter body and provides an analog or serial output to a flow computer or data control system. Select a transmitter that is rated for accuracy and safety for your particular operating conditions.
Differential pressure devices must be zeroed following installation. The procedure varies somewhat for liquid, gas, and steam applications and by manufacturer. See the manufacturer’s literature for complete procedures on zeroing the transmitter.

Meter Nameplate

This name plate identifies the proper specifications associated with the meter designed for the defined application. The direction of the flow is also indicated on each tag.
Figure 2: Nameplate
Page 7 June 2018 DPM-UM-00206-EN-03
Page 8

Straight Pipe Run Requirements

STRAIGHT PIPE RUN REQUIREMENTS
With most flow elements, proper operation and performance is dependent on the required lengths of unrestricted upstream and downstream piping. One of the advantages of the Gemini Cone meter is that a fully developed symmetrical flow profile is achieved with relatively short upstream and downstream lengths, so it needs minimal if any upstream and downstream straight pipe runs. We recommend that the Gemini Cone meter be installed with zero to five pipe diameters and zero to three pipe diameters downstream.
0.4 0.5 0.6 0.7 0.8
BA
A
Flow
0 0 0 1 1
1½ - 3 D
≤ 2D
1 - 2 D
≥ ½ D
Two Plane
Changes
Flow
Single Elbow
Flow
Two Elbows In-Plane
Flow
Two Elbows Out of Plane
A
Flow
Pipe Reduction
A
B
BA
A
B
BA
A
B
B
A
B
B
A
0 0 0 1 1
0 0 0 1 1
0 0 0 1 1
0 0 0 1 1
0 0 0 1 1
1 1 1 2 2
1 1 1 2 2
1 1 1 2 2
Pipe Enlargement
D A B
B
A
Flow
Pipe With Tee
A B
Flow
B
A
B
A
Gate/Globe Valve Fully Open/Partially Open
Page 8 June 2018DPM-UM-00206-EN-03
B
1 1 1 2 2
0 0 0 1 1
0 0 0 1 1
3 3 3 4 4
0 0 0 1 1
3 3 3 4 4
3 3 3 4 4
Page 9

Installation

INSTALLATION

Installation Basics

Here are the basic steps for installing a Gemini Cone meter system:
1. Install the meter in the meter run in accordance with the ow run requirements. See “Straight Pipe Run Requirements” on
page8.
2. Secure the manifold to the meter taps.
3. Connect the differential pressure transmitter to the manifold, following the guidelines in “Mounting Location” on
page10.
4. Connect the transmitter to the flow computer according to instructions in the transmitter user manual.
5. Zero the transmitter.
NEVER USE EXCESSIVE PRESSURE OR FORCE WHEN CONNECTING TUBING TO A DIFFERENTIAL PRESSURE TRANSMITTER.
IF HIGH-TEMPERATURE FLUIDS ARE LIKELY TO BE ENCOUNTERED, MAKE SURE THE CONNECTION TUBING IS RATED FOR THE ANTICIPATED TEMPERATURE RANGE.

Installation Checkpoints for the Transmitter

Before putting the Gemini Cone meter into service, verify that the transmitter is installed properly by reviewing the following checkpoints:
• Is the transmitter full scale correct?
• Has the transmitter zero been checked and/or adjusted?
• Are the transmitter and flow computer set to the appropriate modes—linear or square root?
• Have the transmission lines to the transmitter been purged?
• Are there any leaks in the transmission lines?
• Is the manifold bypass valve closed?
• Is the Gemini Cone meter's high pressure port located upstream of the low pressure port?
Page 9 June 2018 DPM-UM-00206-EN-03
Page 10
Straight Pipe Run Requirements

Mounting Location

The Gemini Cone meter should be installed with zero to five pipe diameters of straight run upstream of the meter and zero to three pipe diameters downstream (see “Straight Pipe Run Requirements” on page8) . The meter can be used in pipelines that are slightly larger than the meter tube; however, if the meter tube is larger than the pipeline, operators should contact Badger Meter or installation requirements. This is usually determined before supply according to application and the degree of accuracy and performance required.

Meter Orientation and Transmitter Position

The location of the transmitter with respect to the meter should be based on the properties of the fluid being measured and the direction of flow through the pipeline. The direction of flow is clearly labeled on the body of every Gemini Cone meter. The meter must be installed so that the high pressure tap (labeled P1 in Figure 1 on page 6) is always upstream of the low pressure tap labeled P2.
Vertical installations measuring liquids may introduce a slight hydrostatic head effect, which must be considered when zeroing a transmitter. With liquid applications, the meter should be installed so flow is moving UP to ensure a full pipe. Use of a 3-valve manifold for zeroing a transmitter. Before installation of any Gemini Cone meter, inspect the meter for damage, particularly at the sealing surfaces. Any damage should be reported to Badger Meter as soon as possible. Each flow element has an arrow indicating the required direction of flow. Failure to properly orient the meter according to the direction of flow will cause improper results and potentially damage the meter.
For vertical installations, the location of differential pressure taps is unrestricted, as long as the static pressure tap is upstream of the lower-pressure tap.
WARNING
NEVER EXCEED THE MAXIMUM PRESSURE OR TEMPERATURE RECOMMENDED FOR THE MEASURED PROCESS. EXCEEDING PROPER PRESSURE OR TEMPERATURE RATINGS CAN LEAD TO PERSONAL INJURY OR EQUIPMENT DAMAGE. THE PROCESS PIPING FLANGES SHOULD BE IDENTICAL TO THOSE ON THE GEMINI CONE BOTH IN PRESSURE CLASS AND INSIDE DIAMETER. THE PROCESS TEMPERATURE AND PRESSURE SHOULD NEVER EXCEED THOSE FOR WHICH THE ELEMENT HAS BEEN DESIGNED.
IF HIGH-TEMPERATURE FLUIDS ARE LIKELY TO BE ENCOUNTERED, MAKE SURE THE CONNECTION FITTINGS VALVES AND TUBING ARE RATED FOR THE ANTICIPATED TEMPERATURE RANGE.

Pressure Tap Location

Location of the pressure taps will vary with the product flowing through the pipeline (liquid, gas, or steam) and the orientation of the meter (vertical or horizontal).
For horizontal installations, the following installation guidelines apply:
• For measuring liquid, differential pressure taps should be located in the bottom half of the pipeline, between 4 o’clock and 5 o’clock positions, or between 7 o’clock and 8 o’clock positions.
• For measuring gas, differential pressure taps should be located in the top half of the pipeline. For wet gas, taps should be located between the 10 o’clock and 2 o’clock positions to allow proper drainage of condensate.
• For steam, differential pressure taps should be located in the side of the pipeline at 3 o’clock or 9 o’clock.
Liquid
120…150° or −120…−150°
Page 10 June 2018DPM-UM-00206-EN-03
Figure 3: Typical piping configurations for liquid, gas, and steam
Wet Gases 60… −60°
Dry Gases 90… −90°
Steam
90…−90° Only
Page 11
Straight Pipe Run Requirements

Line Installation

All flanged Gemini Cone meters require a gasket between the flange on the process line and the mating flange on the meter itself. Select gaskets that match the pressure and temperature ratings of the Gemini Cone flanges and resist corrosive properties of the process fluid.
Before completing the bolting process, make sure that the gaskets are properly centered so that protrusion into the pipe opening is minimized. Misalignment may cause added flow turbulence which can affect meter performance, although such effects are typically minimal (depending upon the application). Bolt the element in line with suitable hardware using recommended bolt torques for the type and class rating of the flanges.
TORQUE ALL MODELS PER ANSI FLANGE RATINGS.
DO NOT EXCEED SPECIFIED TORQUE.
OTE:N Tighten the flange bolts in a progressive star pattern to avoid localized stress on the gaskets.
Dierential Pressure Connections
The high pressure connection is always on the upstream side of the flow direction arrow and the low pressure connection on the downstream side. Fittings used must be able to withstand the process temperature and pressure conditions, as well as provide proper corrosion resistance. See the appropriate secondary instrument instructions for connections to the secondary instrument high and low ports. Coat all fitting threads with a process compliant thread sealant prior to tightening. Once tightened, torque mark all fittings for future reference.

Transmitter Connection Tubing

Before connecting the Gemini Cone meter to the transmitter, consider the following tips for optimizing your system’s measurement accuracy. In a well-designed installation, fluids will drain freely from the process lines and gases will vent to the atmosphere.

Full Port Block Valves

Adding block valves to the pressure taps of the meter will simplify any type of calibration or maintenance to any upstream components. Select valves that are compatible to the pressures, temperatures and system media.

Impulse Tubing Size Selection

Transmitter connection tubing, the tubing that connects the Gemini Cone meter taps to the transmitter, can vary in diameter for different applications. A minimum diameter of 3/8 inch (10 mm) for the internal diameter (ID) of the tubing is recommended, and as a general rule it should be no smaller than 1/4 inch (6 mm). The tubing ID must not exceed 1 inch (25 mm) at the maximum.
In most applications, the primary concern is measurement reliability. If the pressure taps or the connecting tubes become plugged, the reliability of the flow measurement is lost creating a safety risk. High reliability is required for any flow signals used to manage safety processes. A minimum tubing ID of 5/8 inch (16 mm) is recommended in industrial applications.
For steam applications, the ID should be 3/8… 1 in. (10…25 mm).
Page 11 June 2018 DPM-UM-00206-EN-03
Page 12
Straight Pipe Run Requirements

Impulse Tubing Length and Configuration

Impulse tubing is used to connect the sensing taps of the cone meter to the manifold connected to the differential pressure transmitter. One section of tubing should connect the high-pressure tap to the high-pressure side of the differential pressure transmitter; another section of tubing should connect the low-pressure tap to the low-pressure side of the differential pressure transmitter.
• Impulse tubing should be installed with a gradient of 1:12 at a minimum to help prevent undesirable fluids from being transferred to the differential pressure transmitter.
• If tubing is installed in a horizontal orientation, install a gas/liquid separator device.
• Avoid abrupt bends in impulse tubing.
• If impulse tubing sections are long, use mounting brackets to support them.
• Tubing length must be short enough for a high degree of accuracy, and long enough for proper cooling of high-temperature fluids before they reach the transmitter.
• Make sure the installation permits access to the connection tubes, valves, valve manifolds and transmitters for maintenance.
• Limit the number of fittings and avoid long tubing sections that can impair measurement accuracy and increase the risk of plugging.
• Avoid changes in tubing elevation. Differences in elevation will cause a difference in the hydrostatic pressure of the liquid column in the process lines, which can result in inaccurate differential pressure measurements. Fasten the process lines together, if possible, to keep their relative elevations consistent.
• Install process lines so that they slope in only one direction (up or down). If piping must slope in more than one direction, do not allow more than one bend. Install a liquid or gas trap at the lowest point in a gas service installation. Install gas trap at the highest point in a liquid service installation.
Page 12 June 2018DPM-UM-00206-EN-03
Page 13
Top View
2. Minimize all lead line lengths.

Meter Installation for Liquid Service

METER INSTALLATION FOR LIQUID SERVICE

Installation Options

• Meter Orientation—Gemini Cone meters can be installed in a horizontal or vertical position. Horizontal is the standard
orientation, however where space is very limited, a vertical position may prove to be the best option.
• Pipe Orientation—The orientation of piping is dictated by the position of the meter, the type of product being measured, and for vertical meter installations, the direction of flow. When a vertical piping system is used, the operator must give special consideration to the piping configuration to prevent gas from being trapped in liquid differential pressure lines.

Horizontal Meter Installation

For horizontal installations, pressure taps must be positioned 30…60° below the horizontal centerline (4…5 o'clock or 7…8 o'clock). Taps at the bottom of the pipe may become plugged with solids from the liquid; taps above the centerline can accumulate air or non-condensing gases. In liquid service, the connecting lines from the meter shall slope downward to the transmitter with no upturns or pockets. The minimum recommended slope for self-venting is 1:12.

Bubble Pot Installation (Optional)

In liquid applications where the transmitter must be mounted above the metering line, gas or vapor in the liquid can collect at the highest point in the instrument tubing and give a false differential pressure reading. Bubble pots may be the only effective solution for such installations. The piping from the meter connects to the bubble pot anywhere between the 10 o’clock and 2 o’clock positions on a horizontal plane.
Flow
HI
LO
DP Transmitter
or
Direct Read Gage
3-Valve Manifold
ø
Flow
HI LO
Side View
Notes:
1. ø = 1 in/ft (80 mm/m) for water; 2…4 in/ft (160…320 mm/m) for more viscous uids.
Figure 4: Typical horizontal installation for liquids
ø
Up to –45°
Front View
Page 13 June 2018 DPM-UM-00206-EN-03
Page 14
Direct Read Gage
Meter Installation for Liquid Service

Vertical Meter Installation

In most process applications, some level of gas or vapor exists in a liquid service, even if the liquid is water. As a result, the piping configuration must be designed so gas can rise back into the flow stream. The process piping should be extended horizontally a very short distance from the downstream tap and then sloped at a nominal 1:12 angle to the top of the manifold block. Mount the manifold block horizontally below the upstream tap so that piping from the upstream tap to the manifold slopes downward also.
WHEN THE PROCESS IS TURNED OFF, PARTICULATES MAY SETTLE IN THE LOW-PRESSURE PORT. FLUSH THE LOW-PRESSURE PORT WITH AN INERT FLUID BEFORE STARTING THE METER.
OTE:N Do not use downward flow piping configurations that use the standard upstream and downstream pressure ports for
liquid applications due to the risk of trapping gas.

Transmitter Calibration

Calibrate transmitters (differential pressure and/or multi-variable) according to the manufacturer’s recommendations, appropriate national or company standards and contractually agreed methodology. Consider the process conditions in which the Gemini Cone meter and transmitter are installed and operated.
LO
HI
Flow
Front View
3-Valve Manifold
3-Valve Manifold
DP Transmitter
or
Direct Read Gage
DP Transmitter
or
Figure 5: Typical vertical installation for liquids
LO
HI
Flow
Side View
Page 14 June 2018DPM-UM-00206-EN-03
Page 15

Meter Installation for Gas Service

METER INSTALLATION FOR GAS SERVICE

Installation Options

• Meter Orientation—Gemini Cone meters can be installed in a horizontal or vertical position. Horizontal is the standard
orientation, however where space is very limited, a vertical position may be the best option.
• Connection Tube Orientation—The orientation of connection tubing is dictated by the position of the meter, the type of product being measured and, for vertical meter installations, the direction of flow. When a vertically oriented metering system is used, give special consideration to the tubing configuration to prevent liquid being trapped in gas differential pressure lines.

Horizontal Meter Installation

The pressure taps on the Gemini Cone meter should be between the horizontal centerline and the top of the pipe (3…12 o'clock or 9…12 o'clock). If the fluid is a wet gas (that is, a gas containing small quantities of liquids or condensate), situate the pressure taps in a vertical position (12 o’clock) to allow all liquids to drain away from the transmitter. If the connecting tubing extending from the cone meter to the transmitter is not installed in a vertical position, it should slope upward (at least 1:12) for proper drainage.
DP Transmitter
or
Direct Read Gage
3-Valve Manifold
Flow
HI
LO
Top View
DP Transmitter
or
Direct Read Gage
3-Valve Manifold
Φ
HI
Flow
Notes:
1. ø = 1 in/ft (80 mm/m)
2. Minimize all lead line lengths.
Figure 6: Typical horizontal installation for gases
HI LO
Side View
LO

Condensate Chamber (Drip Pot) (Optional for Wet Gas)

The condensate chamber is a collection vessel that helps prevent liquid pockets from collecting in gas instrument tubing.
If drip pots are used, they should ideally be mounted immediately following the shutoff valves installed near the upstream and downstream pressure taps of the meter. For wet gas applications, the piping from the meter connects to the condensate chamber in a 3 o'clock or 9 o'clock position on a horizontal plane. The chambers are positioned vertically so that the meter connection and instrument connection points are at the top and drain points are at the bottom of the chambers.
Page 15 June 2018 DPM-UM-00206-EN-03
Page 16
Front View Side View
Meter Installation for Gas Service

Vertical Meter Installation

When installing the meter in a vertical position, make sure that no trap forms in the downstream tap such that gas is trapped in a liquid or liquid is trapped in a gas.
When measuring dry, non-condensing gases, where there is absolutely no risk for liquid being present, extend the piping from the downstream pressure tap of the cone meter horizontally and then angle it upward to connect to the manifold block. Mount the manifold block horizontally. Slope the tubing from the upstream tap of the cone meter 1 in./ft to the same level as the downstream tap piping to connect to the manifold (see Figure 7).
IF THERE IS ANY LIQUID PRESENT IN THE GAS, DO NOT USE THE PIPING ARRANGEMENT SHOWN IN Figure 7. THE "U” CONFIGURATION COULD TRAP LIQUID IN THE CONE, CHANGING THE DOWNSTREAM PRESSURE.

Transmitter Calibration

Calibrate transmitters (differential pressure and/or multi-variable) according to the manufacturer’s recommendations, appropriate national or company standards and contractually agreed methodology. Consider the process conditions in which the Gemini Cone meter and transmitter are installed and operated.
DP Transmitter
or
Direct Read Gage
DP Transmitter
or
Direct Read Gage
3-Valve Manifold
3-Valve Manifold
LO
HI
Flow
Figure 7: Typical vertical installation for gases
LO
HI
Flow
Page 16 June 2018DPM-UM-00206-EN-03
Page 17

Meter Installation for Steam Service

METER INSTALLATION FOR STEAM SERVICE
Steam measurement is one of the most difficult applications for differential pressure transmitter tubing and requires careful consideration during installation. Steam is usually at a high temperature, which will damage the transmitter. In addition, steam can vary between liquid or gaseous phase depending on temperature and pressure. Due to this, the differential pressure impulse tubing must be oriented in such a manner that it can operate with gas liquid, or a combination of the two present.

Installation Options

• Meter Orientation—Gemini Cone meters can be installed in a horizontal or vertical position. Horizontal is the standard
orientation, however where space is very limited, a vertical position may prove to be the best option.
• Connection Tubing Orientation—The orientation of the impulse tubing is dictated by the orientation of the meter, the type quality of the steam being measured, and for vertical meter installations, the direction of flow. When a vertical meter run is used, the operator must give special consideration to the impulse tubing configuration to prevent liquid from being trapped in gas differential pressure lines.
• Condensate Chamber—The condensate chamber is a liquid reservoir that helps prevent steam from entering the differential pressure transmitter. In most cases, a large-diameter tee is all that is required to collect the liquid. However, if the DP measuring instrument is designed with hydraulic/pneumatic bellows (such a Barton 202E chart recorder), a larger volume condensate chamber will be required. Modern DP transmitters have very little diaphragm movement and do not require the large-volume condensate chamber.

Horizontal Meter Installation

Install the pressure taps above the horizontal centerline (9…3 o'clock) of the primary device. In condensing hot vapor service such as steam, the fluid in the impulse lines is liquid that has been condensed from the vapor. The use of a condensate chamber is mandatory to prevent hot process fluid from damaging the transmitter. Slope the impulse tubing upwards from the cone meter to the condensate pots. A condensate pot can be a tubing tee (for low volume DP instruments) or a full-size condensate chamber (for high volume DP instruments). In either case, install the condensate pots at exactly the same level to ensure accurate differential pressure readings. Fill the line from the bottom of the tee to the transmitter mounted below the tee to the point where excess fluid can drain back into the meter.
In many cases, water (steam condensate) is used for the fluid fill. However, in cold weather, the fluid must be protected from freezing. The fluid fill requires careful design with heat tracing and insulation to keep it in the liquid phase and to keep both the high-pressure and low-pressure legs of the tubing at the same temperature (maintaining the liquid fill at the same density). If practical, use a liquid leg fill fluid other than water. Methanol is a possible substitute, but dibutyl phthalate is the recommended fill fluid because it does not mix with water and remains liquid throughout a broad temperature range of, –31…644° F (–35…340° C).
MPORTANTI
Be careful when using dibutyl phthalate. Follow all hazardous material guidelines (CAS No: 87-74-2).
Page 17 June 2018 DPM-UM-00206-EN-03
Page 18
Side View
Front View
Filling Crosses
Instrument Taps Not In the Same Plane
Filling Crosses
Meter Installation for Steam Service
Flow
HI
LO
HI
LO
By-pass
Valve
DP Transmitter or Direct Read Gage
Figure 8: Typical horizontal installation for steam
HI
LO
(Fill with water to same level)
(Fill with water to same level)
Flow
Side View
HI
LO
By-pass
Valve
DP Transmitter or Direct Read Gage
Figure 9: Optional horizontal installation for steam
Front View
Page 18 June 2018DPM-UM-00206-EN-03
Page 19
Side View Front View
Meter Installation for Steam Service

Vertical Meter Installation

For steam service installations in which the meter is oriented vertically, extend the piping from the upstream pressure tap horizontally to a T-connector. The T-connector enables a plug to be installed at the top for liquid filling purposes to avoid overheating of the differential pressure cell. Position the manifold block directly below, at a distance that keeps the steam at a safe operating temperature when it reaches the differential pressure transmitter. Extend both lines to the T-connectors.
NOT:N This configuration results in a head difference in the differential pressure lines and the differential pressure
transmitter must be zeroed when zero flow has been established in the main line.
When the process is turned off, particulates may settle into the low-pressure port. Flush the low-pressure port with an inert fluid before starting the meter.

Transmitter Calibration

Calibrate the transmitters (differential pressure and/or multi-variable) according to the manufacturer’s recommendations, appropriate national or company standards and contractually agreed methodology. Consider the service in which the Gemini Cone meter and transmitter are installed and operated.
LO
Flow
HI
Flow
Filling Crosses (Fill with water to same level)
LO
HI
DP Transmitter
or
Direct Read Gage
Figure 10: Typical vertical installation for steam
3-Valve Manifold
Page 19 June 2018 DPM-UM-00206-EN-03
Page 20
System Modications

SYSTEM MODIFICATIONS

Square Root Error

Differential pressure measurement is only accurate for steady-state flow. Flow pulsation caused by reciprocating compressors, defective regulators, and like equipment can cause mis-registration of delivered volumes.
Significant errors occur when using differential pressure devices at the discharge of a reciprocating gas compressor where pressure pulses may exceed 10% of static pressure. This causes a condition called square root error, which may be reduced by the use of an acoustic filter.

Gauge Line Error

Gaseous fluids in small-bore pipes may start to oscillate due to an effect called gauge line error. It is a type of acoustic resonance comprising of standing pressure waves, and usually occurs at a maximum of 1/4 wavelengths. A common cause of this phenomenon is the use of impulse lines with a high length to diameter ratio. To help prevent gauge line error, keep impulse lines as short as possible, and use large impulse line diameters where possible. It also helps to keep impulse line diameters constant along their length. The direct mounting of the transmitter to the meter can help reduce or even eliminate the effects of gauge line error. Direct-mount manifolds are available from leading manifold manufacturers.
Elevation and Temperature Eects in Piping
In liquid service, it is important to keep vertical elevation equal between the two impulse lines. If one liquid-filled leg is longer than the other, the hydrostatic head of the lines will vary, resulting in inaccurate differential pressure measurement.
Similarly, if the temperature of liquid in one leg is different from the temperature of liquid in the other leg, the density of the fluid will be different, resulting in inaccurate differential pressure measurement. This most often occurs when one leg of the tubing is in bright sun and the other leg is shaded. To minimize the effects of temperature differences in the vertical legs of impulse lines, shade both of the legs from the sun. The effect of temperature differences is more notable in liquid service installations; gas service is not as prone to DP error due to varying line temperatures.

SPECIFICATIONS

Applications Liquids, steam, air and industrial gases
Wafer 1…4 in. (25…102 mm)
Pipe Sizes
Repeatability ± 0.1% or better Flow Range 10:1 and greater Accuracy ± 0.5% of actual flow Standard Beta Ratio 0.40…0.80 (special betas available) Permanent Pressure Loss Varies with beta ratio and DP
Installation Piping Requirements
Construction Materials 304/304L, 316/316L stainless steel, A106 carbon steel, other materials on request End Fittings Threaded (NPT), flange, wafer, socket, and butt weld, other end connections on request Approvals CRN
Threaded and Socket Weld 1/2…2 in. (12…51 mm) Flanged Mount 1…24 in. (25…609 mm) Butt Weld 1/2…24 in. (12…609 mm)
Typically 0…3 diameters upstream and 0…1 diameters downstream of the cone are required, depending on fittings or valves in the adjacent pipeline (See “Installation” on page9 for the
straight pipe requirements of your application)
Page 20 June 2018DPM-UM-00206-EN-03
Page 21

PART NUMBER CONSTRUCTION

Wafer Mount

Part Number Construction
P G W
Pipe Size
C) 1" Body-Element Instrument Beta Transmitter Material Surface D) 1-1/4" Material Connection Ratio Bracket Certicate Finish E) 1-1/2" 1) CS body-316/ H) 1/4" NPT 4) 0.4 1) SS bracket 1) Material 1) Tungsten F) 2" 316L element (1…3" NPS) 5) 0.5 2) With three certicates Carbide G) 2-1/2" 2) 316/316L I) 1/2" NPT 6) 0.6 valve 2) PMI 2) Chromium
H) 3" body-316/ (3" and up) 7) 0.7 3) With ve 3)
I) 4" 316L element J) 1/2" socket 8) 0.8 valve of one and
X) Other 3) 304/304L weld X) Custom 4) None two above
Pipe Schedule
A) Standard** Process Connection 1) Factory 5) NACE (WMP only)
B) 10 A) RF ange 150# calibration (MR0103) 3) 5 Valve manifold C) 20 B) RF ange 300# Instrument Valve 2) Special X) Other (WMP only)
D) 30 C) RF ange 600# A) 1/4" Needle valve CS calibration* 0) None 4) Mounting
E) 40 D) RF ange 900# B) 1/2" Needle valve CS Z) Not required bracket only
J) 120 X) Other C) 1/4" Needle valve SS Welding X) Other
L) 160 D) 1/2" Needle valve SS Standard 0) None
M
) XH E) 1/2" Gate w/cross CS (steam) A) Standard
N
) XXH F) 1/2" Gate w/cross SS (steam) B) ASME B31.1
O
) 5S X) Other Hydrostatic C) ASME B31.3
P
) 40S Z) Not required Testing X) Other NDE Testing
Q
) 80S 1) Hydro with A) X-ray/Dye Pen 5%
X
) Other certicate X) Other
            
Combination
body-316/ X) Other 316L element
X) Other Transmitter
4) NACE Mounting
Calibration (MR0175) 2) 3 Valve manifold
0) None 0) None
* Standard calibration is performed at Badger Meter with ve data points (0.5 percent accuracy)
** Pipe schedule "Standard" is schedule 40 up to 10 in. and 3.75 in. wall at 12 in. and larger.
Carbide
Page 21 June 2018 DPM-UM-00206-EN-03
Page 22
Part Number Construction

Threaded and Socket Weld Mount

PG
             
Series
T)
Threaded
S)
Socket weld
Pipe Size 316L element (1…3" NPS) 5) 0.5 2) With three certicates Carbide B) 1/2" 2) 316/316L I) 1/2" NPT 6) 0.6 valve 2) PMI C) 1" body-316/ (3" and up) 7) 0.7 3) With ve 3) D) 1-1/4" 316L element J) 1/2" socket 8) 0.8 valve of one and Carbide E) 1-1/2" 3) 304/304L weld X) Custom 4) None two above F) 2" body-316/ X) Other 4) NACE X) Other 316L element (MR0175)
Pipe Schedule
A) Standard** Process Connection A) 1/4" Needle valve CS calibration (WMP only) B) 10 F) NPT C) 1/4" Needle valve SS 2) Special 3) 5 Valve manifold D) 30 G) Socket weld X) Other calibration* (WMP only)
E) 40 X) Other Z) Not required Z) Not required 4) Mounting
G) 80 Welding bracket only
L) 160 Standard X) Other
M
) XH Hydrostatic Testing A) Standard 0) None
N
) XXH 1) Hydro with certicate B) ASME B31.1
O
) 5S 0) None C) ASME B31.3
P
) 40S X) Other NDE Testing
Q
) 80S A) X-ray/Dye Pen 5%
X
) Other X) Other
(NPT)
Body-Element Instrument Beta Transmitter Material Surface Material Connection Ratio Bracket Certicate Finish
1) CS body-316/ H) 1/4" NPT 4) 0.4 1) SS bracket 1) Material 1) Tungsten
Combination
X) Other 5) NACE
Calibration
Instrument Valve 1) Factory 2) 3 Valve manifold
(MR0103)
X) Other
0) None
0) None
2) Chromium
Transmitter Mounting
* Standard calibration is performed at Badger Meter with ve data points (0.5 percent accuracy)
** Pipe schedule "Standard" is schedule 40 up to 10 in. and 3.75 in. wall for 12 in. and larger.
Page 22 June 2018DPM-UM-00206-EN-03
Page 23

Flanged Mount

Part Number Construction
P G F
Pipe Size
C) 1" Body-Element Beta Transmitter Material Surface
D) 1-1/4" Material Ratio Bracket Certicate Finish
E) 1-1/2" 1) CS body-316/ 4) 0.4 1) SS bracket 1) Material 1) Tungsten
F) 2" 316L element 5) 0.5 2) With three certicates Carbide G) 2-1/2" 2) 316/316L 6) 0.6 valve 2) PMI 2) Chromium H) 3" body-316/ 7) 0.7 3) With ve 3)
I) 4" 316L element 8) 0.8 valve of one and
J) 5" 3) 304/304L X) Other 4) None two above
K) 6" body-316/ 4) NACE
L)
8"
M
) 10" X) Other 5) NACE N) 12" (MR0103) O) 14" Calibration X) Other Transmitter
P) 16" Process Connection 1) Factory 0) None Mounting
X) Other A) RF ange 150# calibration 2) 3 Valve manifold
Pipe Schedule D) 1/2" Needle valve SS Standard bracket only
A) Standard** Instrument E) 1/2" Gate w/cross CS (steam) A) Standard X) Other
B) 10 Connection F) 1/2" Gate w/cross SS (steam) B) ASME B31.1 0) None C) 20 A) 2" RF ange 150# X) Other C) ASME B31.3
D) 30 (2" and up) Z) Not required X) Other
E) 40 B) 2" RF ange 300#
F) 60 (2" and up) NDE Testing G) 80 C) 2" RF ange 600# Hydrostatic Testing A) X-ray/Dye Pen 5% H) 100 (2" and up) 1) Hydro with certicate X) Other J) 120 D) 3" RF ange 150# 0) None 0) None K) 140 (3" and up)
L) 160 E) 3" RF ange 300#
M
) XH (3" and up)
N
) XXH F) 3" RF ange 600#
O
) 5S (3" and up)
P
) 40S G) 3” RF ange 900#
Q
) 80S (3" and up)
X
) Other H) 1/4" NPT (1"…3" NPS)
            
Combination
316L element (MR0175)
B) RF ange 300# Instrument Valve 2) Special (WMP only) C) RF ange 600# A) 1/4" Needle valve CS calibration* 3) 5 Valve manifold D) RF ange 900# B) 1/2" Needle valve CS Z) Not required (WMP only) X) Other C) 1/4" Needle valve SS Welding 4) Mounting
I) 1/2" NPT (>3" NPS)
J) 1/2" socket weld
X) Other
Carbide
* Standard calibration is performed at Badger Meter with ve data points (0.5 percent accuracy)
** Pipe schedule "Standard" is schedule 40 up to 10 in. and 3.75 in. wall at 12 in. and larger.
Page 23 June 2018 DPM-UM-00206-EN-03
Page 24
Dierential Pressure Flow Meter, Gemini Cone

Butt Weld Mount

P G B
Pipe Size
B) 1/2" C) 1" D) 1-1/4" Material Ratio Bracket Certicate Finish
E) 1-1/2" 1) CS body-316/ 4) 0.4 1) SS bracket 1) Material 1) Tungsten
F) 2" 316L element 5) 0.5 2) With three certicates Carbide G) 2-1/2" 2) 316/316L 6) 0.6 valve 2) PMI 2) Chromium H) 3" body-316/ 7) 0.7 3) With ve 3)
I) 4" 316L element 8) 0.8 valve of one and
J) 5" 3) 304/304L X) Custom 4) None two above
K) 6" body-316/ 4) NACE
L) 8" 316L element (MR0175) M) 10" X) Other 5) NACE Transmitter N) 12" (MR0103) Mounting
O) 14"
P) 16" Process Connection 1) Factory 0) None ( WMP only) X) Other E) Butt weld calibration 3) 5 Valve manifold
Pipe Schedule D) 1/2" Needle valve SS Standard 0) None
A) Standard** Instrument E) 1/2" Gate w/cross CS (steam) A) Standard B) 10 Connection F) 1/2" Gate w/cross SS (steam) B) ASME B31.1 C) 20 A) 2" RF ange 150# X) Other C) ASME B31.3 D) 30 (2" and up) Z) Not required X) Other
E) 40 B) 2" RF ange 300# NDE Testing
F) 60 (2" and up) A) X-ray/Dye Pent 5% G) 80 C) 2" RF ange 600# Hydrostatic Testing X) Other H) 100 (2" and up) 1) Hydro with certicate 0) None J) 120 D) 3" RF ange 150# 0) None K) 140 (3" and up)
L) 160 E) 3" RF ange 300# M
) XH (3" and up)
N
) XXH F) 3" RF ange 600#
O
) 5S (3" and up)
P
) 40S G) 3" RF ange 900#
Q
) 80S (3" and up)
X
) Other H) 1/4” NPT (1…3" NPS)
            
Body-Element
X) Other Instrument Valve 2) Special (WMP only)
A) 1/4" Needle valve CS calibration* 4) Mounting B) 1/2" Needle valve CS Z) Not required bracket only C) 1/4" Needle valve SS Welding X) Other
I) 1/2" NPT (>3" NPS)
J) 1/2" socket weld
X) Other
Beta Transmitter Material Surface
Combination
Calibration X) Other 2) 3 Valve manifold
Carbide
* Standard calibration is performed at Badger Meter with ve data points (0.5 percent accuracy)
** Pipe schedule "Standard" is schedule 40 up to 10 in. and 3.75 in. wall at 12 in. and larger.
Control. Manage. Optimize.
Preso is a registered trademark of Badger Meter, Inc. Other trademarks appearing in this document are the property of their respective entities. Due to continuous research, product improvements and enhancements, Badger Meter reserves the right to change product or system specications without notice, except to the extent an outstanding contractual obligation exists. © 2018 Badger Meter, Inc. All rights reserved.
www.badgermeter.com
The Americas | Badger Meter | 4545 West Brown Deer Rd | PO Box 245036 | Milwaukee, WI 53224-9536 | 800-876-3837 | 414-355-0400 México | Badger Meter de las Americas, S.A. de C.V. | Pedro Luis Ogazón N°32 | Esq. Angelina N°24 | Colonia Guadalupe Inn | CP 01050 | México, DF | México | +52-55-5662-0882 Europe, Eastern Europe Branch Oce (for Poland, Latvia, Lithuania, Estonia, Ukraine, Belarus) | Badger M eter Europe | ul. Korfantego 6 | 44-193 Knurów | Poland | +48-32-236-8787 Europe, Middle East and Africa | Badger Meter Europa GmbH | Nurtinger Str 76 | 72639 Neuen | Germany | +49-7025-9208-0 Europe, Middle East Branch Oce | Badger Meter Europe | PO Box 341442 | Dubai Silicon Oasis, Head Quarter Building, Wing C, O ce #C209 | Dubai / UAE | +971-4-371 2503 Slovakia | Badger Meter Slovakia s.r.o. | Raciansk a 109/B | 831 02 Bratislava, Slovakia | +421-2-44 63 83 01 Asia Pacic | Badger Meter | 80 Marine Parade Rd | 21-06 Parkway Parade | Singapore 449269 | +65-63464836 China | Badger Meter | 7-1202 | 99 Hangzhong Road | Minhang District | Shanghai | China 201101 | +86-21-5763 5412 Switzerland | Badger Meter Swiss AG | Mittelholzerstrasse 8 | 3006 Bern | Switzerland | +41-31-932 01 11 Legacy Document Number: 10-DPM-UM-00479-EN
Loading...