Badger Meter PFA User Manual

Ellipse® Pitot Tube Meter
PFA Fire Pump System
2000
1500
1000
2500
3000
GPM
M
F
APPROVED
PFA-XXX
X inch
X/XX
S/N AXXXXXXX
3500
4000
M
F
APPROVED
FLOW M ETERS
DEBITM ETERS
MEDIDO R DE F LUJO
PTT-UM-00523-EN-02 (April 2014)
User Manual
Ellipse® Pitot Tube Meter, PFA Fire Pump System
CONTENTS
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Specications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Pipe Orientation and Sensor Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Installation Instructions, Single Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Installation Instructions, Double Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Gage Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Location Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Gage Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Gage Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Page ii April 2014

INTRODUCTION

The Preso Model PFA Fire Pump System is FM-approved and features the Preso Ellipse primary flow sensor. The Preso patented elliptical design outperforms and provides greater accuracy than traditional differential pressure flow measurement devices. This differential pressure flow meter is designed with a series of ports facing the upstream velocity pressures, as well as flow sensing ports strategically located ahead of the trailing edge flow separation.
The multi-ported, self-averaging flow element consists of an elliptical shape with two independent flow sensing chambers. The impact velocity sensing holes (high pressure) are located along the leading edge and the true static sensing holes (low pressure) are on the exterior probe side. Model PFA Fire Pump System comes with instrument shutoff valves with provisions to accept a direct indicating meter.

SPECIFICATIONS

User Manual
True static sensing holes
Impact velocity sensing holes
Figure 1: PFA pressure sensing holes
Applications Liquids
Pipe Sizes 2…16 in. (5…406.4 mm)
Pressure 400 psi (2758 kPa) maximum
Temperature Gage 180° F (80° C) maximum
PFA Velocity Sensor 250° F (121° C) maximum
Accuracy ±1.75% of reading
Turndown Ratio 17:1 with no vacuum effect
Standard Components Y-type head, brass
Compression fitting;
2…5 in., brass
6…16 in., CS with SS ferrule
CS 3000 lb weld fitting, ASTM A105
316/316L SS Ellipse sensor
Instrument valves (2 per sensor), 1/4" male SAE flare brass ball
Polycarbonate ID tag with wire
Direct reading gage, brass body, 270° arc
Reynolds Number Greater than 75,000 maintains most accurate flow measurements
Less than 75,000 consult factory for estimated results
Double Support Double support required for the following Systems
Pipe Size Pump Ratings
4" 400 and 450 gpm
8" > 2000 gpm 10" > 2500 gpm 12" > 3000 gpm 16" > 5000 gpm
Table 1: PFA specifications
Page 3 April 2014