Ideal for Chillers, Grocery Stores, Mechanical Rooms
Physical Plants, Refrigeration Racks, Walk-In Freezers
Features & Benets:
• Proprietary infrared sensing technology virtually
eliminates false alarms and extends sensor life
• No calibration required
• Low detection limits enable leaks to be
found early reducing energy and refrigerant
consumption
• Fastest sampling rate with the longest
sampling distance in the industry at 1,200 feet
-
M
a
Z
k
▪
M
C
o
O
n
2
-
i
t
o
r
M
Z
• Large Graphic LCD for easy set-up and
real-time monitoring
Bacharach’s Multi-Zone Gas Leak Monitors offer superior performance, exibility and functionality for low level
continuous monitoring of refrigerant gases used in most commercial systems including: Chlorouorocarbons
(CFC), Hydrochlorouorocarbons (HCFC), Hydrouorocarbons (HFC), Ammonia (NH
These state-of-the-art xed gas monitors lead the industry in performance, integration capabilities, initial cost
and cost of ownership. Capable of detecting more than 38 refrigerant gases, the Multi-Zone system is compliant
with ASHRAE standard 15-2007, is ETL Energy Saving Listed, meets California Code Regulations for Refrigerant
Monitors and is EN 14624 and CE certied.
) and Carbon Dioxide (CO2).
3
Critical Protection with Flexible Configuration
Bacharach Multi-Zone Monitors provide continuous detection of refrigerant gas levels in up to 16 separate test
zones and can be tted with an optional two channel 4-20 mA current loop board for connection to remote
monitoring equipment. Multi-Zone monitors retain a log of previous readings that can be easily accessed for
analysis. Four relay contacts are provided that can be programmed to trigger external alarm devices in the
event of a system fault, or if a leak (small), spill (medium) or evacuation (large) level of gas is detected, while
audible and visual front panel indicators show alarm and fault conditions. With only minor periodic maintenance,
such as the occasional replacement of lters, and active diagnostics that continuously check the system for
proper operation, Multi-Zone monitors help maintain your equipment efciency, promote safety and protect the
environment.
1-800-736-4666 | 724-334-5000 | www.MyBacharach.com | help@MyBacharach.com
Multi-Zone Specifications
Product Type: The Multi-Zone Gas Leak Monitor is a multiple area monitoring system for low
level continuous monitoring of refrigerant gases used in most commercial
systems including: CFC, HCFC, HFC, Ammonia and Carbon Dioxide. System
design supports compliance to the gas monitoring requirements of
ANSI/BSR ASHRAE 15-2007.
Coverage: 4 Point Standard, Expandable to 16 Points in 4 Point Increments
Detector Type: Single-Pass, Non-Dispersive (NDIR)
Gas Library:
HGM-MZ: CFC: R11, R12, R113, R114, R502, HFP
HFC: R404A (HP62), R407A, R407C (AC9000), R134A, R410A (AZ20),
HFC: R507 (AZ50)
HCFC: R21, R22, R23, R123, R124, R227, R500, R503, R401A (MP39),
R402A (HP80), R402 (HP81), R408A, R409A, R508B (SUVA95),
R236FA, R125, R245FA, R422A, R422D, R427A
Halon: H1301, H2402, H1211
Other: FA188, FC72, N1230, HFO1234YF, R424A, R426A, R427A, R438A
AGM-MZ: Ammonia (NH
-MZ: Carbon Dioxide (CO2), R744
CO
2
Measuring Range:
HGM-MZ: All gases 0 to 10,000 ppm
AGM-MZ: Ammonia 25 to 10,000 ppm
CO
-MZ: Carbon Dioxide 0 to 8,000 ppm
2
Accuracy:
HGM-MZ: ±1 ppm ±10% of reading from 0-1,000 ppm (R11, R22, R13: ±10 ppm
±15% of reading 0-1,000 ppm)
AGM-MZ: ±10 ppm ±10% of reading from 0-1,000 ppm
-MZ: ±5 ppm ±5% of reading from 0-1,000 ppm, ±10% of reading from 1,000
CO
2
to 4,000 ppm, ±15% of reading 4,000 to 8,000 ppm
Temperature Drift:
HGM-MZ: ±0.8% (R134A) of reading per Degrees C between purge cycles
AGM-MZ: 1.5 ppm per Degrees C between purge cycles
-MZ: Less than 1 ppm per Degrees C between purge cycles
CO
2
Display Resolution: 1 ppm
Dimensions: 12.23” x 13.7” x 4.96” (31.0642 cm x 34.798 cm x 12.5984 cm)
Weight: 15 lbs (6.80kg)
User Interface: Front panel w/3 indicator lights: Green - Power On, Normal; Yellow - Fault;
Yellow Flashing - System Fault; Red/Flashing - point has exceeded alarm set.
Communications: Full 2-way communication with MZ-RD display module or building manage-
ment system via RS-485 Serial Interface. RS-232C Comm. Port Standard.
Alarms: Four SPDT alarm contacts are provided rated 2A at 250 VAC (Inductive),
5A at 250 VAC (Resistive). Three assigned to ppm level alarms. One assigned
to system faults.
Conditioned Signal: Optional Dual 4-20 mA DC isolated outputs. Channel 1=zone area,
Channel 2=ppm
System Noise: Less than 40dB at 10 Ft. (3m)
Response Time: 5 to 315 seconds per zone – Depending on air line length and number of zones
Sampling Mode: Automatic or Manual (Hold)
Re-Zero: Every 5 minutes or on 0.5 Degree C internal temperature change
Monitoring Distance: 1,200 ft. max. (500 ft. for NH
tubing (each zone)
Power Safety Mode: Fully automatic system reset. All programmed parameters retained
Operating Temp: 32° to 122° F (0 to 50° C)
Ambient Humidity: 5% to 90% RH Non-condensing
Altitude Limit: 6,562 Ft. (2,000 m)
Power: 100 to 240 VAC, 50/60 Hz, 20 W
Approvals:
UL 61010-1, CAN/CSA 22.2 No. 61010-1; EN61010-1, EN61326, EN14624; CE Mark
Distributed By:
), R717
3
) for combined length of sample and exhaust
3
MZ-RD Remote Display
The MZ-RD Remote Display is a Multi-Zone
accessory that is placed in an alternate
location for the Multi-Zone with access to the
diagnostics, communications and control of the
unit. The MZ-RD can connect up to four
Multi-Zone monitors, expanding zone coverage
to 64 separate test zones.
Multi-Zone Ordering Information
Multi-Zone Monitors
3015-5043 HGM-MZ Halogen Gas Monitor - 4 Zone
3015-5044 HGM-MZ Halogen Gas Monitor - 8 Zone
3015-5045 HGM-MZ Halogen Gas Monitor - 12 Zone
3015-5046 HGM-MZ Halogen Gas Monitor - 16 Zone
3015-5047 AGM-MZ Ammonia Gas Monitor - 4 Zone
3015-5048 AGM-MZ Ammonia Gas Monitor - 8 Zone
3015-5049 AGM-MZ Ammonia Gas Monitor - 12 Zone
3015-5050 AGM-MZ Ammonia Gas Monitor - 16 Zone
3015-5356 CO
3015-5357 CO
3015-5358 CO
3015-5359 CO
3015-5138 MZ-RD Remote Display
Multi-Zone Kits
3015-5330 HGM-MZ 4 Zone Monitor with Remote Display
3015-5331 HGM-MZ 8 Zone Monitor with Remote Display
3015-5332 HGM-MZ 12 Zone Monitor with Remote Display
3015-5333 HGM-MZ 16 Zone Monitor with Remote Display
3015-5334 AGM-MZ 4 Zone Monitor with Remote Display
3015-5335 AGM-MZ 8 Zone Monitor with Remote Display
3015-5336 AGM-MZ 12 Zone Monitor with Remote Display
3015-5337 AGM-MZ 16 Zone Monitor with Remote Display
3015-5531 CO
3015-5532 CO
3015-5533 CO
3015-5534 CO
Multi-Zone Annual Maintenance Kits
3015-5525
-MZ Carbon Dioxide Gas Monitor - 4 Zone
2
-MZ Carbon Dioxide Gas Monitor - 8 Zone
2
-MZ Carbon Dioxide Gas Monitor - 12 Zone
2
-MZ Carbon Dioxide Gas Monitor - 16 Zone
2
-MZ 4 Zone Monitor with Remote Display
2
-MZ 8 Zone Monitor with Remote Display
2
-MZ 12 Zone Monitor with Remote Display
2
-MZ 16 Zone Monitor with Remote Display
2
MADE IN THE USA
3015-5526
3015-5527
3015-5528
Multi-Zone Replacement Parts
3015-2906 Multi-Zone End-of-Line Replacement Filter Only
3015-5512 Multi-Zone End-of-Line Water Stop Replacement
Bacharach® is a registered trademark of Bacharach, Inc.
©Product Bulletin 5001 2010, Bacharach, Inc., all rights reserved. All information is subject to verification.
November 2010 – Rev. 2 Printed in U.S.A.
Filter