Ideal for Chillers, Grocery Stores, Mechanical Rooms Physical Plants, Refrigeration Racks, Walk-In Freezers
Features & Benets:
• Proprietary infrared sensing technology virtually eliminates false alarms and extends sensor life
• No calibration required
• Low detection limits enable leaks to be found early reducing energy and refrigerant
consumption
• Fastest sampling rate with the longest sampling distance in the industry at 1,200 feet
-
M
a
Z
k
M
C
o
O
n
2
-
i
t
o
r
M
Z
• Large Graphic LCD for easy set-up and real-time monitoring
Bacharach’s Multi-Zone Gas Leak Monitors offer superior performance, exibility and functionality for low level continuous monitoring of refrigerant gases used in most commercial systems including: Chlorouorocarbons (CFC), Hydrochlorouorocarbons (HCFC), Hydrouorocarbons (HFC), Ammonia (NH These state-of-the-art xed gas monitors lead the industry in performance, integration capabilities, initial cost and cost of ownership. Capable of detecting more than 38 refrigerant gases, the Multi-Zone system is compliant with ASHRAE standard 15-2007, is ETL Energy Saving Listed, meets California Code Regulations for Refrigerant Monitors and is EN 14624 and CE certied.
) and Carbon Dioxide (CO2).
3
Critical Protection with Flexible Configuration
Bacharach Multi-Zone Monitors provide continuous detection of refrigerant gas levels in up to 16 separate test zones and can be tted with an optional two channel 4-20 mA current loop board for connection to remote monitoring equipment. Multi-Zone monitors retain a log of previous readings that can be easily accessed for analysis. Four relay contacts are provided that can be programmed to trigger external alarm devices in the event of a system fault, or if a leak (small), spill (medium) or evacuation (large) level of gas is detected, while audible and visual front panel indicators show alarm and fault conditions. With only minor periodic maintenance, such as the occasional replacement of lters, and active diagnostics that continuously check the system for proper operation, Multi-Zone monitors help maintain your equipment efciency, promote safety and protect the environment.
1-800-736-4666 | 724-334-5000 | www.MyBacharach.com | help@MyBacharach.com
Multi-Zone Specifications
Product Type: The Multi-Zone Gas Leak Monitor is a multiple area monitoring system for low level continuous monitoring of refrigerant gases used in most commercial systems including: CFC, HCFC, HFC, Ammonia and Carbon Dioxide. System design supports compliance to the gas monitoring requirements of ANSI/BSR ASHRAE 15-2007.
Coverage: 4 Point Standard, Expandable to 16 Points in 4 Point Increments Detector Type: Single-Pass, Non-Dispersive (NDIR)
Gas Library:
HGM-MZ: CFC: R11, R12, R113, R114, R502, HFP
HFC: R404A (HP62), R407A, R407C (AC9000), R134A, R410A (AZ20), HFC: R507 (AZ50) HCFC: R21, R22, R23, R123, R124, R227, R500, R503, R401A (MP39), R402A (HP80), R402 (HP81), R408A, R409A, R508B (SUVA95), R236FA, R125, R245FA, R422A, R422D, R427A Halon: H1301, H2402, H1211 Other: FA188, FC72, N1230, HFO1234YF, R424A, R426A, R427A, R438A
AGM-MZ: Ammonia (NH
-MZ: Carbon Dioxide (CO2), R744
CO
2
Measuring Range:
HGM-MZ: All gases 0 to 10,000 ppm AGM-MZ: Ammonia 25 to 10,000 ppm CO
-MZ: Carbon Dioxide 0 to 8,000 ppm
2
Accuracy:
HGM-MZ: ±1 ppm ±10% of reading from 0-1,000 ppm (R11, R22, R13: ±10 ppm ±15% of reading 0-1,000 ppm)
AGM-MZ: ±10 ppm ±10% of reading from 0-1,000 ppm
-MZ: ±5 ppm ±5% of reading from 0-1,000 ppm, ±10% of reading from 1,000
CO
2
to 4,000 ppm, ±15% of reading 4,000 to 8,000 ppm
Temperature Drift:
HGM-MZ: ±0.8% (R134A) of reading per Degrees C between purge cycles AGM-MZ: 1.5 ppm per Degrees C between purge cycles
-MZ: Less than 1 ppm per Degrees C between purge cycles
CO
2
Display Resolution: 1 ppm Dimensions: 12.23” x 13.7” x 4.96” (31.0642 cm x 34.798 cm x 12.5984 cm) Weight: 15 lbs (6.80kg) User Interface: Front panel w/3 indicator lights: Green - Power On, Normal; Yellow - Fault;
Yellow Flashing - System Fault; Red/Flashing - point has exceeded alarm set. Communications: Full 2-way communication with MZ-RD display module or building manage-
ment system via RS-485 Serial Interface. RS-232C Comm. Port Standard. Alarms: Four SPDT alarm contacts are provided rated 2A at 250 VAC (Inductive),
5A at 250 VAC (Resistive). Three assigned to ppm level alarms. One assigned to system faults.
Conditioned Signal: Optional Dual 4-20 mA DC isolated outputs. Channel 1=zone area, Channel 2=ppm
System Noise: Less than 40dB at 10 Ft. (3m) Response Time: 5 to 315 seconds per zone – Depending on air line length and number of zones Sampling Mode: Automatic or Manual (Hold) Re-Zero: Every 5 minutes or on 0.5 Degree C internal temperature change Monitoring Distance: 1,200 ft. max. (500 ft. for NH
tubing (each zone)
Power Safety Mode: Fully automatic system reset. All programmed parameters retained Operating Temp: 32° to 122° F (0 to 50° C) Ambient Humidity: 5% to 90% RH Non-condensing Altitude Limit: 6,562 Ft. (2,000 m) Power: 100 to 240 VAC, 50/60 Hz, 20 W Approvals:
UL 61010-1, CAN/CSA 22.2 No. 61010-1; EN61010-1, EN61326, EN14624; CE Mark
Distributed By:
), R717
3
) for combined length of sample and exhaust
3
MZ-RD Remote Display
The MZ-RD Remote Display is a Multi-Zone accessory that is placed in an alternate location for the Multi-Zone with access to the diagnostics, communications and control of the unit. The MZ-RD can connect up to four Multi-Zone monitors, expanding zone coverage to 64 separate test zones.
Multi-Zone Ordering Information
Multi-Zone Monitors
3015-5043 HGM-MZ Halogen Gas Monitor - 4 Zone 3015-5044 HGM-MZ Halogen Gas Monitor - 8 Zone 3015-5045 HGM-MZ Halogen Gas Monitor - 12 Zone 3015-5046 HGM-MZ Halogen Gas Monitor - 16 Zone 3015-5047 AGM-MZ Ammonia Gas Monitor - 4 Zone 3015-5048 AGM-MZ Ammonia Gas Monitor - 8 Zone 3015-5049 AGM-MZ Ammonia Gas Monitor - 12 Zone 3015-5050 AGM-MZ Ammonia Gas Monitor - 16 Zone 3015-5356 CO 3015-5357 CO 3015-5358 CO 3015-5359 CO 3015-5138 MZ-RD Remote Display
Multi-Zone Kits
3015-5330 HGM-MZ 4 Zone Monitor with Remote Display 3015-5331 HGM-MZ 8 Zone Monitor with Remote Display 3015-5332 HGM-MZ 12 Zone Monitor with Remote Display 3015-5333 HGM-MZ 16 Zone Monitor with Remote Display 3015-5334 AGM-MZ 4 Zone Monitor with Remote Display 3015-5335 AGM-MZ 8 Zone Monitor with Remote Display 3015-5336 AGM-MZ 12 Zone Monitor with Remote Display 3015-5337 AGM-MZ 16 Zone Monitor with Remote Display 3015-5531 CO 3015-5532 CO 3015-5533 CO 3015-5534 CO
Multi-Zone Annual Maintenance Kits
3015-5525
-MZ Carbon Dioxide Gas Monitor - 4 Zone
2
-MZ Carbon Dioxide Gas Monitor - 8 Zone
2
-MZ Carbon Dioxide Gas Monitor - 12 Zone
2
-MZ Carbon Dioxide Gas Monitor - 16 Zone
2
-MZ 4 Zone Monitor with Remote Display
2
-MZ 8 Zone Monitor with Remote Display
2
-MZ 12 Zone Monitor with Remote Display
2
-MZ 16 Zone Monitor with Remote Display
2
MADE IN THE USA
3015-5526
3015-5527
3015-5528
Multi-Zone Replacement Parts
3015-2906 Multi-Zone End-of-Line Replacement Filter Only 3015-5512 Multi-Zone End-of-Line Water Stop Replacement
Bacharach® is a registered trademark of Bacharach, Inc.
©Product Bulletin 5001 2010, Bacharach, Inc., all rights reserved. All information is subject to verification.
November 2010 – Rev. 2 Printed in U.S.A.