Bacharach MVR-300 Specifications

REFRIGERANT SAFETY COMPLIANCE
MVR-300™ VRF Refrigerant Leak Detector
For VRF Systems in Occupied Spaces
DESCRIPTION
The MVR-300 gas detector is specically designed to provide continuous monitoring for refrigerants associated with high-eciency, high volume refrigerant cooling and heating systems, such as VRF / VRV (Variable Refrigerant Flow / Variable Refrigerant Volume) sytems. Typical applications include hotels, dormitories, hospitals, oce buildings and apartment buildings.
The MVR-300 audible and visual alarms alert occupants and simultaneously communicate to Building Management Systems / Building Automation Systems (BMS / BAS). Two on-board relays can be used to close valves, activate alarm devices and exhaust fans or initiate emergency calls to building management.
The on-board Modbus RTU interface provides real-time information about refrigerant concentrations, status and settings. It also enables custom conguration of the MVR-300 to any application specic requirements using multiple Modbus registers. The MVR-300 is designed for easy installation and simple maintenance.
The MVR-300 is compatible with the Bacharach MVR-SC Controller.
FEATURES BENEFITS
Fits in standard electrical boxes
Low prole/Flush mount Aesthetically non-intrusive appearance
Two relays and Modbus Communications
Alarm options including: LED, buzzer, two levels, congurable delay and fail-
safe
Refrigerant specic sensor Enhances safety
Self diagnostics and simple eld calibration
Unique plug-in eld replaceable pre-calibrated sensor
Easy to install
Notify building management & initiate counter measures
Alert occupants and remotely inform building management of alarm location for rapid response as required
1
and minimizes refrigerant loss
Easy to maintain
Low cost of ownership
HOW TO CONTACT US:
US Customer Service: +1 724 334 5000 EU Customer Service: +353 1 284 6388 CAN Customer Service: +1 905 882 8985
mybacharach.com
1
Important Note: Large refrigerant leaks into occupied spaces can reach concentrations that pose a suocation
risk to the occupants. The MVR-300 is not designed to be used as the sole safety device for this risk. Safety of the occupants also must take a system designed approach that includes things such as ventilation, detection, early warning, mitigation and design redundancy.
FOR MORE INFO:
Scan the QR code to learn more about the MVR-300 and other Bacharach products.
MVR-300 is a trademark of Bacharach, Inc.
SPECIFICATIONS DESCRIPTION
Detectable Gases R-410A, R-407C, R-404A, R-32
Measuring Ranges 2,500 ppm, 5,000 ppm, 10,000 ppm
Housing Flush mount, white ABS, Fits in most 3-gang electrical back boxes
Size (L × W × D, approx.) 6″ × 4.1″ × 1.75″ (150 × 105 × 45 mm) including bezel
Protection Indoor: IP40, NEMA 1
Weight (approx.) 8 oz (230 g)
Power 100 to 240 VAC, 50/60 Hz, 4 W max
Indicator Tri-color LED: green, amber, red
Buzzer 80 dB at 12″ (30 cm)
Relay Two SPDT: low alarm and high alarm / fault, normal or fail-safe, congurable
Alarm Delay 0 to 15 minutes, congurable 0, 5, 10, 15
2
Wiring Power: 3-core cable, 14 to 20 AWG (0.5 to 2.0 mm
Relay: 3-core cable, 18 to 20 AWG (0.5 to 1.0 mm
Modbus: 2-core twisted pair shielded cable 18 to 24 AWG
Modbus RTU Baud Rate: 9,600 or 19,200, congurable
Environmental Conditions Operating Temperature: 32 to 120 ºF (0 to 50 ºC)
Storage Temperature: 5 to 100 ºF (-20 to 40 ºC)
Humidity: 5 to 90% RH, non-condensing
Pressure: 23.6 to 32.5 inch of Hg (800 to 1,100 hPa)
Elevation 0 to 6,560′ (2,000 m) altitude
Sensor Life 2 year minimum life with recommended 6 month testing and / or recalibration
Approvals CE, UL/SCA/IEC/EN 61010-1
)
2
)
REFRIGERANT P/N LOW ALARM* HIGH ALARM* RANGE
6203-0001
R-410A
R-407C
R-404A
R-32
6203-0002 6203-0003
6203 -0 011 6203-0012 6203-0013
6203-0021 6203-0022 6203-0023
6203-0041 6203-0042 6203-0043
*Factory default; can be changed through Modbus. Recommended 6 month testing / recalibration
500 ppm 1,000 ppm 2,000 ppm
500 ppm 1,000 ppm 2,000 ppm
500 ppm 1,000 ppm 2,000 ppm
500 ppm 1,000 ppm 2,000 ppm
2,000 ppm 2,000 ppm 4,000 ppm
2,000 ppm 2,000 ppm 4,000 ppm
2,000 ppm 2,000 ppm 4,000 ppm
2,000 ppm 2,000 ppm 4,000 ppm
2,500 ppm 5,000 ppm
10,000 ppm
2,500 ppm 5,000 ppm
10,000 ppm
2,500 ppm 5,000 ppm
10,000 ppm
2,500 ppm 5,000 ppm
10,000 ppm
THE MVR-SC CONTROLLER
The MVR-SC Refrigerant Leak Monitor provides centralized monitoring and alarming for multi­occupant applications utilizing the MVR-300™ VRF Refrigerant Leak Detector. The MVR-SC continuously monitors all connected gas detectors for alarm and fault conditions, and will provide alerts via the integrated color touchscreen display, integrated buzzer, and on-board relay outputs.
MKTG 000 04 | Rev 2 | Marketing Communic ations | Subject to m odications | © Bacharach Inc
Pittsburgh, PA USA | Dublin, IRE | Stanardsville, VA USA | Toronto, CAN mybacharach.com | help@mybacharach.com
Loading...