Bacharach MGS-550 Installation Guide

2: SAFETY INSTRUCTIONS
P/N: 1100-0999
Revision 0
June 5, 2015
IP66-Rated ABS Enclosure with Local
Sensor
CAUTION: DO NOT USE the MGS-550 in oxygen-enriched environments of >21% oxygen. High “off-scale” read­ings may indicate an explosive con­centraon.
WARNING: Strictly follow the instrucons in the User Manual (part number 1100-1000).
Magnec Wand
Flame
Proof/
Explosion
Proof Ex d
Enclosure
with Local
Sensor
USER MANUAL: Before using this equipment, carefully read and strictly follow the User Manual (part number 1100-1000). The user must fully understand and strictly observe the instrucons. Use the equipment only for the purposes listed and under the condions specified in that document.
CODE COMPLIANCE: Comply with all local and naonal laws, rules and regulaons associated with this equipment.
GENUINE PARTS: Use only genuine Bacharach spare parts and accessories, otherwise proper funconing of the equip­ment may be impaired.
FLAME PROOF AND EXPLOSION PROOF JOINTS: Joints of
the flame proof/explosion proof enclosure are not in accor­dance with the relevant minimum or maximum values of EN/IEC 60079-1. The joints are not intended to be re-worked by the user.
EXPLOSIVE DIRECTIVES: As long as no EC-Type Examinaon Cerficate per Annex II, clauses 1.5.5, 1.5.6 and 1.5.7 of Direcve 94/9/EC exists: the measuring funcon of the gas detecon transmier for explosion protecon, according to Annex II, clauses 1.5.5, 1.5.6 and 1.5.7 of Direcve 94/9/EC is not covered.
When using the product in areas subject to explosion hazards, refer to the following:
● Instruments or components for use in explo­sion-hazard areas which have been tested and approved according to naonal, European or internaonal Explosion Protecon Regulaons may only be used under the condions specified in the approval and with consideraon of the relevant legal regulaons.
● The instruments or components may not be modified in any manner. The use of faulty or incomplete parts is forbidden. The appropriate regulaons must be observed at all mes when carrying out repairs on these instruments or
3: MOUNTING
115.0 mm (4.53 in)
Mounng Point (Ex d)
120.6 mm (4.75 in)
FULL-SIZE
MOUNTING
TEMPLATES --
DO NOT
RESCALE
Mounng Point (ABS)
Mounng
Point
(Ex d)
144.1 mm (5.67 in)
1: OPERATING AREA AND CONDITIONS
The Bacharach MGS-550 is an instrument for the
connuous monitoring of toxic and combusble gases, oxygen and refrigerants in ambient air. The instrument is housed in a rugged ABS or aluminum enclosure for indoor and outdoor applicaons. The instrument can be connected to a Bacharach monitoring system or a Programmable Logic Controller (PLC). With the inte­grated alarm relay configuraon, the instrument can be operated as a stand-alone unit (with addional local alarm signaling). The instrument is designed to be installed in non-classified, non-hazardous, perma­nent locaons.
The instrument is powered by 19.5 to 28.5 VDC or 24 VAC (± 20%). The measured gas concentraon is converted to a 4 to 20 mA, 0 to 5 V, 0 to 10 V, 1 to 5 V, 2 to 10 V analog and digital Modbus RTU output signal. The instrument accepts wire sizes of 16 to 24 AWG (0.2 to 1.5 mm
2
).
ENVIRONMENTAL CONSIDERATIONS: Carefully consider the full range of environmental condions to which the instru­ments will be exposed.
TARGET GAS CONSIDERATIONS: The physical data of the gas or vapor to be detected must be observed.
APPLICATION CONSIDERATIONS: The specifics of the appli­caon (for example, possible leaks, air movement/dra, etc.) must be observed.
ACCESSIBILITY CONSIDERATIONS: The degree of accessibili­ty required for maintenance purposes must be granted.
ACCESSORY CONSIDERATIONS: The types of oponal and accessory equipment that will be used with the system must be kept in mind.
SENSOR POSITIONING: When installing the instrument or the remote sensor, the sensor opening should always be poinng downward.
SUN SHIELD CONSIDERATIONS: If the instrument is exposed to direct sunlight, the use of a sunshield is recommended.
Mounng
Point (ABS)
4: WEIGHTS AND DIMENSIONS (APPROXIMATE)
WIDTH HEIGHT DEPTH
COMPONENT
General Purpose Enclosure
Explosion Proof Encosure
mm in mm in mm in
210
125
8.3
4.9
225
190
8.9
7.5
85
90
3.4
3.5
WEIGHT
kg
1
1.623.5
lbs
5: WIRING
M20 OPENINGS: The ABS and the
flame proof/explosion proof enclosures provide four M20 openings for cable glands or plugs. These openings can be used for field wiring, direct aachment of a sensor or wiring of a remote sensor. Unused openings must be closed with a suitable plug and gasket, maintaining the IP or Ex d rang.
NOTE: To make wiring connecons, you must first open the MGS-550 housing. The enclosure lid of the IP66 ABS housing has four capve screws. The enclosure lid of the Ex d (flame proof/explosion proof) hous­ing unscrews.
Next, carefully discon­nect the combinaon Display Bezel and Processor Board (which remain connected) from the lower Inter­face Board by unscrew­ing the 3 capve screws. Access the capve screws through holes in the Display Bezel.
Refer to the User Manual (part number 1100-1000)
for detailed instrucons on accessing the internal components for wiring.
WARNING: The MGS-550 must be powered by either (a) a suitable UL 60950/CSA cerfied power supply that is isolated from line voltage by double insulaon, or (b) an appro­priately rated UL listed/CSA Class 2 transformer. Failure to comply can result in personal injury or death.
NOTE: For 24 VDC installaons, the input is protected. If the polarity is reversed, the instru­ment will not power-up.
SHIELD WIRE WARNING: Con­nect the shield of the power wires to the earth ground of the central control system (e.g., chassis, ground bus bar, etc.).
1: Strip 0.2 to 0.25 inches (5 to 7 mm) of wiring insulaon.
2: Connect the wires as indicated.
FUNCTION PIN LABEL
Power
(+24VDC or 24VAC)
1
2
3
+24VDC/AC
PWR GND
ANALOG 1 GND
Analog Output 1
4
ANALOG OUT 1
24VAC
PWR GND
24VAC
PWR GND
24VAC
PWR GND
24VAC
PWR GND
NOTE: For connecons to an external controller such as a Bacharach MGS or GDA, refer to the manual that was included with the controller.
POLARITY WARNING: For 24 VAC installaons in a daisy-chain configuraon, the neutral polari­ty must be maintained for all instruments.
NOTE: Aer wiring is completed, carefully re-as­semble the enclosure and its components, nong the keyed ribbon cable and sensor connectors. Aer installaon is complete, be sure to refer to the User Manual
detailed instrucons on registering the sensors and configuring the MGS-550 for proper operaon.
(part number 1100-1000) for
24VAC
PWR GND
24VAC
PWR GND
4-Wire Power and Output to Central Control System
3-Wire Power and Output to Central Control System
24VAC
PWR GND
A OUT 1
A1 GND
PWR GND
+24VDC
SUPPLY
TRANSFORMER
mA
-
+
AC
POWER
Processor
Board (Middle Layer) with Keyed Ribbon Cable
Internal Display Bezel (Top Layer)
5
ANALOG 2 GND
Analog Output 2
Modbus RTU
6
7
8
9
ANALOG OUT 2
RS-485 GND
A
B
FUNCTION PIN LABEL
RELAY 1 NC
RELAY 1 C
RELAY 1 NO
RELAY 2 NC
RELAY 2 C
RELAY 2 NO
RELAY 3 NC
RELAY 3 C
RELAY 3 NO
Relay 1 Output
Relay 2 Output
Relay 3 Output
10
11
12
13
14
15
16
17
18
PIN 10
PIN 18
Connector Style
May Vary Slightly
from Photo
PIN 9
Interface Board
(Boom Layer)
PIN 1
A OUT 1
mA
PWR GND
+24VDC
World Headquarters
621 Hunt Valley Circle
New Kensington, PA 15068 USA
Phone: 724-334-5000 • Fax: 724-334-5001
Toll Free: 1-800-736-4666
Website: www.MyBacharach.com
E-mail: help@MyBacharach.com
114A Georges Street Lower
Dun Laoghaire • Co Dublin • Ireland
Phone: +353 1 284 6388 • Fax: +353 1 284 6389
-
+
Loading...