Bacharach MGS-408 Specifications

2. Safety Instructions (Continued)
Gas Detection Controller
for Commercial & Industrial Applications
Refrigerant Leak Detection
P/N: 1100-2292 | February 2019 Revision 0
Languages
This quick start guide has been translated into the following languages: Deutsch, Español, Français, Italiano and Nederlands. To download a translated
document, scan here or visit http://bit.ly/2TbbFNb.
1. Introduction
The MGS-408 Gas Detection Controller displays comprehensive information about the status of all connected gas detectors. A maximum of eight (8) gas sensors can be connected to the MGS-408 via Modbus RTU.
Compatible Bacharach gas detectors are the MGS-410, MGS-450, MGS-460, MGS-250 and MGS-550.
Quick Start Guide
WARNING: Extreme care should be exercised when
accessing the product’s interior. Only qualied electrical
maintenance personnel should perform connections and adjustments. Always remove AC power before working inside the MGS-408’s enclosure.
WARNING: Use a DRY CLOTH to clean the outside of this product. DO NOT use soap and water or other detergents. Failure to comply may result in a potential shock hazard.
become impaired if it is used in a manner not specied by the manufacturer. Modications to this instrument, not expressly approved, will void the warranty.
CAUTION: Use ONLY the provided cable glands for electrical and communication wiring. Drilling into the box will void the warranty.
A certied AC power disconnect or circuit breaker should
be mounted near the controller and installed following applicable local and national codes. If a switch is used instead of a circuit breaker, a properly rated CERTIFIED fuse or current limiter is required to be installed as per local or national codes. Markings for positions of the
switch or breaker should state (I) for on and (O) for o.
4. Key Specications
Si ze (H×W×D): 11.0″ × 8.5″ × 3.9″ (280 × 215 × 100
Weight: 2.76 lbs (1250 g)
Indicators: Multi-color Status LED
Alarm Delay: Congurable (0 to 15 minutes)
Inputs: Tactile Switches (×2), Magnetic
Outputs: Analog Output: 4 to 20 mA, 0 to 5V, 0 to
Bluetooth
®
mm)
Internal Alarm Buzzer: 72dB @ 3.9″ (10 cm)
Switches (×2)
10V, 1 to 5V (default) or 2 to 10V
Bluetooth® Low Energy, BLE 4.2
CAUTION: In case of malfunction, DO NOT continue to use
this equipment if there are any symptoms of malfunction
or failure. In the case of such occurrence, de-energize the power supply and contact a qualied repair technician or
the nearest Bacharach Service Center.
CODE COMPLIANCE: Comply with all local and national
laws, rules and regulations associated with this equipment.
Operators should be aware of the regulations and standards in their industry / locality for the operation of the MGS-408.
TECHNICIAN USE ONLY: The MGS-408 must be installed
by a suitably qualied technician who will install this unit in
accordance with these instructions and the standards in their
particular industry / country. This document is only intended as a guide and the manufacturer bears no responsibility for the installation or operation of this unit.
Failure to install and operate the unit in accordance with these instructions and with industry guidelines may cause serious injury or death and the manufacturer will not be held responsible in this regard.
Power Supply: 100 - 240 VAC, 50 / 60 HZ, 80W
(maximum)
Wiring (Power): 2-core cable, 16 to 28 AWG
Wiring (Relays): 2-core cable, 16 to 28 AWG
Wiring (Modbus): Recommended: Belden 3106A (or
equivalent) 3-core, 2 twisted pair + ground, shielded cable with 120 Ω characteristic impedance, 16 to 28 AWG
Enclosure: Material: ABS
Protection: IP66
Temperature: 32 to 113°F (0 to 45°C)
2. Safety Instructions
DANGER: The MGS-408 is NOT certied or approved for operation in oxygen-enriched atmospheres. Failure to comply may result in EXPLOSION.
WARNING: NEVER operate the MGS-408 without connection to a protective ground. Failure to comply may result in a potential shock hazard and is a violation of electrical safety standards.
Modbus: Connection: RS-485 terminal block
Baud Rate: 9,600 (default) or 19,200 Data Bits: 8 Parity: None (default), odd or even Stop Bits: 1 (default) or 2 Retry Time: 500 ms (minimum)
Humidity: 5 to 90% RH, non condensing
Pressure: 23.6 to 32.5″Hg (800 to 1,100 mbar)
Elevation: 0 to 6,560′ (2,000 m) altitude
5.118
5. Mounting Template
FULL-SIZE MOUNTING
TEMPLATE
DO NOT RESCALE
8.996