Bacharach MGS-150 Owner's Manual

Multi-Channel Input
Single- and Dual-Alarm
Controllers
Installation and Operation Manual
Instruction 6709-9000
Product Leadership Training Service Reliability
MGS Series Controller Manual
WARRANTY POLICY
BACHARACH, I NC. WARRANTS THIS INSTRUMENT, E XCLUDING SENSORS, TO BE FREE FROM DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF PURCHASE BY THE ORIGINA L OWNE R. THE SE NSORS HAVE A WARRANTY PERIOD OF ONE YEAR FROM THE DATE OF PURCHASE. IF THE PRODUCT SHOULD BECOME DEFECTIVE WITHIN THIS WARRANTY PERIOD, WE WILL REPAIR O R REPLACE IT AT OUR DISCRETION.
THE WARRANTY S TATUS MAY BE AFFECTED IF THE INSTRUMENT HAS NOT BEEN USED AND MAINTAINED PER THE INSTRUCTIONS IN THIS MANUAL OR HAS BEEN ABUSED, DAMAGED, OR MODIFIED IN ANY WAY. THIS INSTRUMENT IS ONLY TO BE USED FOR PURPOSES STATED HEREIN. THE MANUFACTURER IS NOT LIABLE FOR AUXILIARY INTER FACED EQUIPMENT OR CONSEQUENTIAL DAMAGE.
DUE TO ONGOING RESEARCH, DEVELOPMENT, AND PRODUCT TESTING, THE MANUFACTURER RESERVES THE RI GHT TO CHANGE SPECIFICATIONS WITHOUT NOTICE. THE INFORMATIO N CONTAINED HEREIN IS BASED ON DATA CONSIDERED ACCURATE. HOWEVER, NO WARRANTY IS EXPRESSED OR IMPLIED REGARDING THE ACCURACY OF THIS DATA.
ALL GOODS MUST BE SHIPPED TO THE MANUFA CTURER BY PREPAID FREIGHT. ALL RETURNED GOODS MUST BE PRE-AUTHORIZED BY OBTAINING A RETURN MERCHANDISE AUTHORIZATION (RMA) NUMBE R. CONTACT THE MANUFACTURER FOR A NUMBER AND PROCEDURES REQUIRED FOR PRODUCT TRANSPORT.
SERVICE POLICY
BACHARACH, INC. MAINTAINS AN INSTRUMENT SERVICE FACILITY AT THE FACTORY. SOME BACHARACH DIS TRIBUTORS / AGENTS MAY ALSO HAVE REPAIR FACILITIES, HOWEVER, BACHARACH ASSUMES NO LIABILITY FOR SERVICE PERFORMED BY ANYONE OTHER THAN BACHARACH PERSONNEL. REPAIRS ARE WARRANTED FOR 90 DAYS AFTER DATE OF SHIPMENT (SENSORS, PUMPS, FILTERS AND BATTERIES HAVE INDIVIDUAL WARRANTIES). SHOULD YOUR INSTRUMENT REQUIRE NON-WARRANTY REPAIR, YOU MAY CONTACT THE DISTRIBUTOR FROM WHOM IT WAS PURCHASED OR YOU MAY CONTACT BACHARACH DIRECTLY.
IF BACHARACH IS TO DO THE REPAIR WORK, SEND THE INSTRUMENT, PREPAID, TO BACHARACH, INC. AT THE FOLLOWING ADDRESS.
BACHARACH, INC. 621 HUNT VALLEY CIRCLE NEW KENSINGTON, PA 15068 ATTENTION: SERVICE DEPARTMENT
ALWAYS INCLUDE YOUR RMA #, ADDRESS, TELEPHONE NUMBER, CONTACT NAME, SHIPPING/BILLING INFORMATION AND A DESCRIPTION OF THE DEFECT AS YOU PERCEIVE IT. YOU WILL BE CONTACTED WITH A COST ESTIMATE FOR EXPECTED REPAIRS PRIOR TO THE PERFORMANCE OF ANY SERVICE WORK. FOR LIABILITY REASONS, BACHARACH HAS A POLICY OF PERFORMING ALL NEEDED REPAIRS TO REST ORE THE INSTRUMENT TO FULL OPERATING CONDITION.
2 6709-9000 Rev 1
PRIOR TO SHIPPING EQUIP MENT TO B ACHA RACH, CONT ACT OUR OFF ICE FOR AN RMA # (RETURNED MERCHANDISE AUTHORIZATION). ALL RETURNED GOODS MUST BE ACCOMPANIED WITH AN RMA NUMBER.
PACK THE EQUIPMENT WELL (IN ITS ORIGINAL PACKING IF POSSIBLE), AS BACHARACH CANNOT BE HELD RESPONSIBLE FOR ANY DAMAGE INCURRED DURING SHIPPING TO OUR FACILITY.
NOTICES
MGS Series Controller Manual
COPYRIGHTS: THIS MANUAL IS SUBJECT TO COPYRIGHT PROTECTION; ALL RIGHTS ARE RESERVED UNDER INTERNATIONAL AND DOMESTIC COPYRIGHT LAWS. THIS MANUAL MAY NOT BE COPIED OR TRANSLATED, IN WHO LE OR IN PART, IN ANY MANNER OR FORMAT, WITHOUT THE WRITTEN PERMISSION OF BACHARACH, INC.
ALL SOFTWARE WHICH BACHARACH UTILIZES AND/OR DISTRIBUTES, HOLDS A PROPRIETARY INTEREST AND IS ALSO SUBJECT TO COPYRIGHT PROTECTION AND ALL RIGHTS ARE RESERVED. NO PARTY MAY USE OR COPY SUCH SOFTWARE IN ANY MANNER OR FORMAT, EXCEPT TO THE EXTENT THAT BACHARACH GRANTS THEM A LICENSE TO DO SO. IF THIS SOFTWARE IS BEING LOADED ONTO MORE THAN ONE COMPUTER, EXTRA SOFTWARE LICENSES MUST BE PURCHASED.
TECHNICIAN USE ONLY
THIS UNIT MUST B E INSTALLED BY A SUITABLY QUALIFIED TECHNICIAN WHO WILL INSTALL THIS UNIT IN ACCORDANCE WITH THESE INSTRUCTIONS AND THE STANDARDS IN THEIR PARTICULAR INDUSTRY/COUNTRY. OPERATORS OF THE UNIT SHOULD BE AWARE OF THE REGULATIONS AND STANDARDS IN THEIR INDUSTRY/COUNTRY FOR THE OPERATION OF THIS UNIT. THESE NOTES ARE ONLY INTENDED AS A GUIDE AND THE MANUFACTURER BEARS NO RESPONSIBILITY FOR THE INSTALLATION OR OPERATION OF THIS UNIT.
FAILURE TO INSTALL AND OPERATE THE UNIT IN ACCORDANCE WITH THESE INSTRUCTIONS AND W ITH INDUSTRY GUIDELINES MAY CAUSE SERIOUS INJURY INCLUDING DEATH AND THE MANUF ACTURER WILL NOT BE HELD RESPONSIBLE IN THIS REGARD.
HAZARDOUS AREA WARNING
THIS INSTRUMENT HAS NOT BEEN DESIGNED TO BE INTRINSICALLY SAFE FOR USE IN AREAS CLASSIFIED AS HAZARDOUS LOCATIONS. FOR YOUR SAFETY, DO NOT USE IT IN HAZARDOUS (CLASSIFIED) LOCATIONS.
6709-9000 Rev 1 3
MGS Series Controller Manual
Table of Contents
SECTION 1.
INTRODUCTION ........................................................................ 5
1.1. OVERVIEW .................................................................................................. 5
1.2. 2-CHANNEL AND 6-CHANNEL MODELS ............................................................. 5
1.3. ALARMING .................................................................................................. 5
1.4. COMPONENTS .............................................................................................. 8
1.5. SPECIFICATIONS .......................................................................................... 11
SECTION 2. MOUNTING INSTRUCTIONS .................................................... 12
2.1. INSTALLATION WARNINGS ............................................................................ 12
2.2. LOCATION RECOMMENDATIONS .................................................................... 12
2.3. MOUNTING DIMENSIONS ............................................................................. 13
SECTION 3. WIRING ................................................................................... 16
3.1. 1- AND 2-CHANNEL UNITS (SINGLE- AND DUAL-ALARM) ................................... 16
3.2. 4- AND 6-CHANNEL UNITS (SINGLE- AND DUAL-ALARM) ................................... 17
3.3. EXTERNAL HORN (FOR AUDIBLE ALARMS) ....................................................... 20
SECTION 4. CONFIGURATION AND OPERATION ........................................ 21
4.1. OVERVIEW ................................................................................................ 21
4.2. INTRODUCTION TO CHANGING ALARM LEVEL(S) ............................................... 21
4.3. CHANGING ALARM LEVEL FOR 2-CHANNEL, 1-ALARM UNITS .............................. 23
4.4. CHANGING ALARM LEVEL FOR 2-CHANNEL, 2-ALARM UNITS .............................. 24
4.5. CHANGING ALARM LEVEL FOR 6-CHANNEL, 1-ALARM UNITS .............................. 25
4.6. CHANGING ALARM LEVEL FOR 6-CHANNEL, 2-ALARM UNITS .............................. 26
4.7. OUTPUT DELAYS ......................................................................................... 27
4.8. FAIL SAFE OPERATION ................................................................................. 28
4.9. MUTING THE AUDIBLE ALARM (KEY SWITCH) ................................................... 29
4.10. RESETTING HIGH ALARMS (DUAL-LEVEL UNITS ONLY) ..................................... 29
DECLARATION OF CONFORMITY .................................................................. 30
4 6709-9000 Rev 1

Section 1. Introduction

1.1. Overview

The MGS Series controllers provide local alarm status indications (via multi-colored, per-channel LEDs) as well as single-level or dual-level digital (relay) alarm outputs based on 1, 2, 4, or 6 inp ut signals and 1 or 2 user-definable set-points.

1.2. 2-Channel and 6-Channel Models

MGS Controllers s upport m ult iple input se nsor s/trans mitters (1, 2, 4, or 6 channels) based on the model of the controller. Inputs are standard 4-20 mA signals from MGS-series sensors or an y standard, line ar, 4-20 mA transmitter.
NOTE: The smaller MGS Controller supports up to t wo input channels (see Figure 1). The larger contr oller suppor ts up to six channels (see Figure 2). The number of alarm LEDs on your controller will vary based on the flavor of device that is ordered (see Figure 3).
MGS Series Controller Manual
IMPOR TANT: If you ar e N O T us ing th e maximum number of available channels (2 f or the smaller controller , and 6 for the larger controller), you must connect a 3300 Ω resistor across pins 1 and 2 for each unused input channel.

1.3. Alarming

Regardless of the number of channels supported, each controller contains either 1 or 2 adjustable potentiometers (pots) for setting the alarm value(s). Single-l evel alarm controllers c ontain one pot which sets the controller’s alar m threshold. D ual-level a larm controller s contain two pots which are used to set the low-level and high-level alarm thresholds.
As an individual channel’s input signal exceed the controller’s alarm threshold (set by the programm able pot(s)), the cor responding ch annel’s alarm LED is illuminated, allowing a technician to visually inspect the controller for an y alarm c onditions on a c hannel-by-channel basis. Refer to Figure 3.
6709-9000 Rev 1 5
MGS Series Controller Manual
Figure 1. Sample Configurations (1,2-Channel)
6 6709-9000 Rev 1
MGS Series Controller Manual
Figure 2. Sample Configurations (4,6-Channel)
MGS Controllers have either one or two relay outputs: one for single­level alarm controllers (“Alarm”), and 2 for dual-level alarm controllers (“Alarm High” and “Alarm Low”). Unlike the alarm LEDs that provide a channel-by-channel alarm status of each incoming transmitter’s signal, the relay output “trips” or “energizes” if any of the inputs exceed the alarm threshold set by the pot (that is, if any of the alarm LEDs is energized). Alarm rela ys can be used to activate warning lights, sirens, ventilation fans, etc.
6709-9000 Rev 1 7
MGS Series Controller Manual
Figure 3. Sample Front Panels Showing Status LEDs
For dual-alarm configurations, the Alarm Low relay output “trips” or “energizes” if any of the inputs exceed the alarm threshold s et b y the low alarm pot. Sim ilarly, the Alarm High r elay output “trips” or “energizes” if any of the inputs exceed the alarm threshold set by the high alarm pot.
All controllers have a green power LED that is on when the unit has power. The 4- and 6-channel 2-level units have a fault relay which “trips” or “energizes” if the controller experiences a fault condition. Like the alarm relays, the fault rela y can be use to activate warnin g lights, sirens, ventilation fans, etc.

1.4. Components

The following is a summary of the MGS Controller’s hardware components. Note that f eatures var y based o n m odel and featur es (e.g. , 1-2 channel units vs. 4-6 c hannel un its, sing le-level al arms vs . dual-level alarms, etc.).
8 6709-9000 Rev 1
Components Descriptions
Power input Provides power to the MGS Controller Power LED Power status indicator Channels (max) 1-2 Channel Units 4-6 Channel Units Sensor input(s) max 2 max 6 max Alarm levels Single Dual Single Dual Set point POT(s) 1 2 1 2 Alarm relay output(s) 1 2 1 2 Alarm LED(s) (max) 2 4 6 12 Fault relay output N/A N/A N/A 1
MGS Series Controller Manual
Figure 4. 6-Channel, Dual-Alarm MGS Controller
6709-9000 Rev 1 9
MGS Series Controller Manual
NOTE: Figure 4 sho ws components ass ociated with a dual­alarm configuration. F or si ngle-al arm configur ations, t he Low Alarm LEDs are not present. JP1 on the single-alarm configuration is the delay jumper.
Figure 5. 2-Channel, Dual-Alarm MGS Controller
NOTE: Figure 5 shows components associated with a dual-
alarm configuration. F or si ngle-al arm configur ations, t he Low Alarm LEDs are not present, and the Delay Jumper will be present. The Delay Jumper is not available on dual-alarm configurations, though its location is highlighted above.
10 6709-9000 Rev 1