Bacharach MGS Operating Manual

Multi-Channel Input
Single and Dual Alarm
Controllers
Installation and Operation Manual
Instruction 6709-9000
Product Leadership Training Service Reliability
MGS Series Controller Manual
WARRANTY POLICY
BACHARACH, INC. WARRANTS THIS INSTRUMENT, EXCLUDING SENSORS, TO BE FREE FROM DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF PURCHASE BY THE ORIGINAL OWNER. THE SENSORS HAVE A WARRANTY PERIOD OF ONE YEAR FROM THE DATE OF PURCHASE. IF THE PRODUCT SHOULD BECOME DEFECTIVE WITHIN THIS WARRANTY PERIOD, WE WILL REPAIR OR REPLACE IT AT OUR DISCRETION.
THE WARRANTY STATUS MAY BE AFFECTED IF THE INSTRUMENT HAS NOT BEEN USED AND MAINTAINED PER THE INSTRUCTIONS IN THIS MANUAL OR HAS BEEN ABUSED, DAMAGED, OR MODIFIED IN ANY WAY. THIS INSTRUMENT IS ONLY TO BE USED FOR PURPOSES STATED HEREIN. THE MANUFACTURER IS NOT LIABLE FOR AUXILIARY INTERFACED EQUIPMENT OR CONSEQUENTIAL DAMAGE.
DUE TO ONGOING RESEARCH, DEVELOPMENT, AND PRODUCT TESTING, THE MANUFACTURER RESERVES THE RIGHT TO CHANGE SPECIFICATIONS WITHOUT NOTICE. THE INFORMATION CONTAINED HEREIN IS BASED ON DATA CONSIDERED ACCURATE. HOWEVER, NO WARRANTY IS EXPRESSED OR IMPLIED REGARDING THE ACCURACY OF THIS DATA.
ALL GOODS MUST BE SHIPPED TO THE MANUFACTURER BY PREPAID FREIGHT. ALL RETURNED GOODS MUST BE PRE-AUTHORIZED BY OBTAINING A RETURN MERCHANDISE AUTHORIZATION (RMA) NUMBER. CONTACT THE MANUFACTURER FOR A NUMBER AND PROCEDURES REQUIRED FOR PRODUCT TRANSPORT.
SERVICE POLICY
BACHARACH, INC. MAINTAINS AN INSTRUMENT SERVICE FACILITY AT THE FACTORY. SOME BACHARACH DISTRIBUTORS / AGENTS MAY ALSO HAVE REPAIR FACILITIES, HOWEVER, BACHARACH ASSUMES NO LIABILITY FOR SERVICE PERFORMED BY ANYONE OTHER THAN BACHARACH PERSONNEL. REPAIRS ARE WARRANTED FOR 90 DAYS AFTER DATE OF SHIPMENT (SENSORS, PUMPS, FILTERS AND BATTERIES HAVE INDIVIDUAL WARRANTIES). SHOULD YOUR INSTRUMENT REQUIRE NON-WARRANTY REPAIR, YOU MAY CONTACT THE DISTRIBUTOR FROM WHOM IT WAS PURCHASED OR YOU MAY CONTACT BACHARACH DIRECTLY.
IF BACHARACH IS TO DO THE REPAIR WORK, SEND THE INSTRUMENT, PREPAID, TO BACHARACH, INC. AT THE FOLLOWING ADDRESS.
BACHARACH, INC. 621 HUNT VALLEY CIRCLE NEW KENSINGTON, PA 15068 ATTENTION: SERVICE DEPARTMENT
ALWAYS INCLUDE YOUR RMA #, ADDRESS, TELEPHONE NUMBER, CONTACT NAME, SHIPPING/BILLING INFORMATION AND A DESCRIPTION OF THE DEFECT AS YOU PERCEIVE IT. YOU WILL BE CONTACTED WITH A COST ESTIMATE FOR EXPECTED REPAIRS PRIOR TO THE PERFORMANCE OF ANY SERVICE WORK. FOR LIABILITY REASONS, BACHARACH HAS A POLICY OF PERFORMING ALL NEEDED REPAIRS TO RESTORE THE INSTRUMENT TO FULL OPERATING CONDITION.
2 6709-9000 Rev 2
PRIOR TO SHIPPING EQUIPMENT TO BACHARACH, CONTACT OUR OFFICE FOR AN RMA # (RETURNED MERCHANDISE AUTHORIZATION). ALL RETURNED GOODS MUST BE ACCOMPANIED WITH AN RMA NUMBER.
PACK THE EQUIPMENT WELL (IN ITS ORIGINAL PACKING IF POSSIBLE), AS BACHARACH CANNOT BE HELD RESPONSIBLE FOR ANY DAMAGE INCURRED DURING SHIPPING TO OUR FACILITY.
NOTICES
MGS Series Controller Manual
COPYRIGHTS: THIS MANUAL IS SUBJECT TO COPYRIGHT PROTECTION; ALL RIGHTS ARE RESERVED UNDER INTERNATIONAL AND DOMESTIC COPYRIGHT LAWS. THIS MANUAL MAY NOT BE COPIED OR TRANSLATED, IN WHOLE OR IN PART, IN ANY MANNER OR FORMAT, WITHOUT THE WRITTEN PERMISSION OF BACHARACH, INC.
ALL SOFTWARE WHICH BACHARACH UTILIZES AND/OR DISTRIBUTES, HOLDS A PROPRIETARY INTEREST AND IS ALSO SUBJECT TO COPYRIGHT PROTECTION AND ALL RIGHTS ARE RESERVED. NO PARTY MAY USE OR COPY SUCH SOFTWARE IN ANY MANNER OR FORMAT, EXCEPT TO THE EXTENT THAT BACHARACH GRANTS THEM A LICENSE TO DO SO. IF THIS SOFTWARE IS BEING LOADED ONTO MORE THAN ONE COMPUTER, EXTRA SOFTWARE LICENSES MUST BE PURCHASED.
TECHNICIAN USE ONLY
THIS UNIT MUST BE INSTALLED BY A SUITABLY QUALIFIED TECHNICIAN W HO WILL INSTALL THIS UNIT IN ACCORDANCE WITH THESE INSTRUCTIONS AND THE STANDARDS IN THEIR PARTICULAR INDUSTRY/COUNTRY. OPERATORS OF THE UNIT SHOULD BE AWARE OF THE REGULATIONS AND STANDARDS IN THEIR INDUSTRY/COUNTRY FOR THE OPERATION OF THIS UNIT. THESE NOTES ARE ONLY INTENDED AS A GUIDE AND THE MANUFACTURER BEARS NO RESPONSIBILITY FOR THE INSTALLATION OR OPERATION OF THIS UNIT.
FAILURE TO INSTALL AND OPERATE THE UNIT IN ACCORDANCE WITH THESE INSTRUCTIONS AND WITH INDUSTRY GUIDELINES MAY CAUSE SERIOUS INJURY INCLUDING DEATH AND THE MANUFACTURER WILL NOT BE HELD RESPONSIBLE IN THIS REGARD.
HAZARDOUS AREA WARNING
THIS INSTRUMENT HAS NOT BEEN DESIGNED TO BE INTRINSICALLY SAFE FOR USE IN AREAS CLASSIFIED AS HAZARDOUS LOCATIONS. FOR YOUR SAFETY, DO NOT USE IT IN HAZARDOUS (CLASSIFIED) LOCATIONS.
6709-9000 Rev 2 3
MGS Series Controller Manual
Table of Contents
SECTION 1.
INTRODUCTION ........................................................................ 5
1.1. OVERVIEW .................................................................................................. 5
1.2. 2-CHANNEL AND 6-CHANNEL MODELS ............................................................. 5
1.3. ALARMING .................................................................................................. 5
1.4. COMPONENTS .............................................................................................. 8
1.5. SPECIFICATIONS ............................................................................................ 9
SECTION 2. MOUNTING INSTRUCTIONS .................................................... 10
2.1. INSTALLATION WARNINGS ............................................................................ 10
2.2. LOCATION RECOMMENDATIONS .................................................................... 10
2.3. MOUNTING DIMENSIONS ............................................................................. 11
SECTION 3. WIRING ................................................................................... 14
3.1. 1- AND 2-CHANNEL UNITS (SINGLE- AND DUAL-ALARM) ................................... 14
3.2. 4- AND 6-CHANNEL UNITS (SINGLE- AND DUAL-ALARM) ................................... 15
3.3. EXTERNAL HORN (FOR AUDIBLE ALARMS) ....................................................... 18
SECTION 4. CONFIGURATION AND OPERATION ........................................ 19
4.1. OVERVIEW ................................................................................................ 19
4.2. INTRODUCTION TO CHANGING ALARM LEVEL(S) ............................................... 19
4.3. CHANGING ALARM LEVEL FOR 2-CHANNEL, 1-ALARM UNITS .............................. 20
4.4. CHANGING ALARM LEVEL FOR 2-CHANNEL, 2-ALARM UNITS .............................. 21
4.5. CHANGING ALARM LEVEL FOR 6-CHANNEL, 1-ALARM UNITS .............................. 22
4.6. CHANGING ALARM LEVEL FOR 6-CHANNEL, 2-ALARM UNITS .............................. 23
4.7. OUTPUT DELAYS ......................................................................................... 24
4.8. FAIL SAFE OPERATION ................................................................................. 24
4.9. MUTING THE AUDIBLE ALARM (KEY SWITCH) ................................................... 24
4.10. RESETTING HIGH ALARMS (DUAL-LEVEL UNITS ONLY) ..................................... 25
DECLARATION OF CONFORMITY .................................................................. 27
4 6709-9000 Rev 2
Section 1. Introduction
1.1. Overview
The MGS Series controllers provide local alarm status indications (via multi-colored, per-channel LEDs) as well as single-level or dual-level digital (relay) alarm outputs based on 1, 2, 4, or 6 input signals and 1 or 2 user-definable set-points.
1.2. 2-Channel and 6-Channel Models
MGS Controllers support multiple input sensors/transmitters (1, 2, 4, or 6 channels) based on the model of the controller. Inputs are standard 4-20 mA signals from MGS-series sensors or any standard, linear, 4-20 mA transmitter.
NOTE: The smaller MGS Controller supports up to two input channels (see Figure 1). The larger controller supports up to six channels (see Figure 2). The number of alarm LEDs on your controller will vary based on the flavor of device that is ordered.
MGS Series Controller Manual
IMPORTANT: If you are NOT using the maximum number of available channels (2 for the smaller controller, and 6 for the larger controller), you must connect a 3300 Ω resistor across pins 1 and 2 for each unused input channel.
1.3. Alarming
Regardless of the number of channels supported, each controller contains either 1 or 2 adjustable potentiometers (pots) for setting the alarm value(s). Single-level alarm controllers contain one pot which sets the controller’s alarm threshold. Dual-level alarm controllers contain two pots which are used to set the low-level and high-level alarm thresholds.
As an individual channel’s input signal exceed the controller’s alarm threshold (set by the programmable pot(s)), the corresponding channel’s alarm LED is illuminated, allowing a technician to visually inspect the controller for any alarm conditions on a channel-by-channel basis.
6709-9000 Rev 2 5
MGS Series Controller Manual
Figure 1. Sample Configurations (1,2-Channel)
6 6709-9000 Rev 2
MGS Series Controller Manual
Figure 2. Sample Configurations (4,6-Channel)
MGS Controllers have either one or two relay outputs: one for single­level alarm controllers (“Alarm”), and 2 for dual-level alarm controllers (“Alarm High” and “Alarm Low”). Unlike the alarm LEDs that provide a channel-by-channel alarm status of each incoming transmitter’s signal, the relay output “trips” or “energizes” if any of the inputs exceed the alarm threshold set by the pot (that is, if any of the alarm LEDs is energized). Alarm relays can be used to activate warning lights, sirens, ventilation fans, etc.
6709-9000 Rev 2 7
MGS Series Controller Manual
For dual-alarm configurations, the Alarm Low relay output “trips” or “energizes” if any of the inputs exceed the alarm threshold set by the low alarm pot. Similarly, the Alarm High relay output “trips” or “energizes” if any of the inputs exceed the alarm threshold set by the high alarm pot.
All controllers have a green power LED that is on when the unit has power. The 4- and 6-channel 2-level units have a fault relay which “trips” or “energizes” if the controller experiences a fault condition. Like the alarm relays, the fault relay can be use to activate warning lights, sirens, ventilation fans, etc.
1.4. Components
The following is a summary of the MGS Controller’s hardware components. Note that features vary based on model and features (e.g., 1-2 channel units vs. 4-6 channel units, single-level alarms vs. dual-level alarms, etc.).
Components Descriptions
Power input Provides power to the MGS Controller
Power LED Power status indicator
Channels (max) 1-2 Channel Units 4-6 Channel Units
Sensor input(s) max 2 max 6 max
Alarm levels Single Dual Single Dual
Set point POT(s) 1 2 1 2
Alarm relay output(s) 1 2 1 2
Alarm LED(s) (max) 2 4 6 12
Fault relay output N/A N/A N/A 1
NOTE: For single-alarm configurations, the Low Alarm LEDs are not present.
8 6709-9000 Rev 2
1.5. Specifications
Specification 1-2 Channel 4-6 Channel
MGS Series Controller Manual
Product Type 1-2 channel alarm
controller
Max Channels 2 6
Inputs 4-20 mA 4-20 mA
Display LED alarm indicators LED alarm indicators
Ambient
-20 to +50 degrees C -20 to +50 degrees C Temperature Range
Power Supply 100V-230V AC (50-60Hz)
or 12V DC (Specify at time of order)
Max Power 15 W Max 25 W Max
Audible Alarm Integrated 12 VDC
Alarm Set points
User selectable. Common to all channels. Alarm level set point is based on 4-20 mA input signal.
Alarm Relays One 10-A 30 VDC or 250
VAC resistive Form C relay. Two for dual-alarm configurations. Common low alarm and high alarm across channels.
Housing NEMA 1 wall mount NEMA 1 wall mount
Approvals UL/CSA/IEC/EN 61010-1
CE
4-6 channel alarm controller
100V-230V AC (50-60Hz) or 12V DC (Specify at time of order)
User selectable. Common to all channels. Alarm level set point is based on 4-20 mA input signal.
One 10-A 30 VDC or 250 VAC resistive Form C relay. Two for dual-alarm configurations. Common low alarm and high alarm across channels.
Common fault relay on dual-level alarm configurations.
UL/CSA/IEC/EN 61010-1 CE
NOTE: If replacement of either main power fuse is required, use only a 2A 250V slow fuse (0.79 in/20mm) T2AL250V.
6709-9000 Rev 2 9