Bacharach MGD-100 Quick Start Guide

GAS DETECTOR and CONTROLLER
QUICK INSTALLATION GUIDE
Revision 0
January 13, 2016
Standard
IP41 Sensor
Housing
1-2 Sensor Controller Housing
CAUTION: DO NOT MOUNT the
MGD-100 in an area that may contain flammable liquids or vapors. Operaon of electrical equipment in such an area cons­tutes a safety hazard.
WARNING: Strictly follow the instrucons in the User Manual (part number 6109-9000) available at www.MyBacharach.com.
1: OPERATING AREA AND CONDITIONS
The Bacharach MGD-100 is an instrument for the
connuous monitoring of refrigerant, combusble, and toxic gases. The system is available with one or two levels of alarm, and consists of 1 to 6 remote gas sensors connected to and powered by a controller.
The controller is powered by 12 VDC or 100-230 VAC 50-60 Hz (specified at me of order).
2: SAFETY INSTRUCTIONS
USER MANUAL: Before using this equipment,
carefully read and strictly follow the User Manual (part number 6109-9000). The user must fully understand and strictly observe the instrucons. Use the equipment only for the purposes listed and under the condions specified in that document.
CODE COMPLIANCE: Comply with all local and naonal laws, rules and regulaons associated with this equipment.
GENUINE PARTS: Use only genuine Bacharach spare parts and accessories, otherwise proper funconing of the equipment may be impaired.
TECHNICIAN USE ONLY: This unit must be installed by a suitably qualified technician who will install this unit in accordance with these instrucons and the standards in their parcular industry/country. Opera­tors of the unit should be aware of the regulaons and standards in their industry/country for the operaon of this unit. These notes are only intended as a guide and the manufacturer bears no responsi­bility for the installaon or operaon of this unit.
Failure to install and operate the unit in accordance with these instrucons and with industry guidelines may cause serious injury including death and the manufacturer will not be held responsible in this regard.
SAFE MOUNTING: This monitor must be connected by a marked, suitably located and easily reached switch or circuit-breaker as means of disconnecon.
3: WEIGHTS AND DIMENSIONS
Type/Enclosure Dimensions Weights
IP41
IP66
IP66 w/ Splash Guard
IP66 w/ Remote Sensor
IP66 w/ Ex d Remote Head
IP66 w/ PRV Sensor Head
IP66 Airflow/ Duct (See Table)
Ex d (Enclosure)
3.35” x 5.59” x 2.09” 86 x 142 x 53 mm
6.89” x 6.5” x 3.29” 175 x 165 x 82 mm
6.89” x 8.9” x 3.29” 175 x 225 x 82 mm
6.89” x 6.1” x 3.29” 175 x 155 x 82 mm
6.89” x 6.1” x 3.29” 175 x 155 x 82 mm
6.89” x 6.1” x 3.29” 175 x 155 x 82 mm
6.89” x 4.9” x 3.29” 175 x 125 x 82 mm
5.12” x 6.3” x 3.54” 130 x 160 x 90 mm
Supported CFM & Duct Sizes for Duct Mount Housing
Units
Inches
Feet
Area (ft2)
12 x 12 12 x 24 18 x 18 24 x 24 24 round
1 x 1
1 2 2.25 4 3.14
Duct Size
1 x 2 1.5 x 1.5 2 x 2 Pi x 1 x 1
6.3 oz 180 g
1 lb 6 oz 629 g
1 lb 9 oz 700 g
1 lb 11 oz 790 g
2 lb 10 oz 1185 g
2 lb 0.3 oz 916 g
1 lb 4 oz 578 g
9 lb 4 oz 4200 g
3.39 in (86.0 mm)
Standard IP41 Housing
4: MOUNTING
ENVIRONMENTAL CONSIDERATIONS: Care-
0.28 in
(7.0 mm)
1.69 in (43.0 mm)
0.18 in
(4.50 mm)
2.09 in (53 mm)
fully consider the full range of environmental condions to which the instruments will be exposed.
0.35 in
(9.0 mm)
TARGET GAS CONSIDERATIONS: The physical data of the gas or vapor to be detected must be observed.
APPLICATION CONSIDERATIONS: The specifics of the applicaon (for example, possible leaks, air movement/dra, etc.) must be observed.
ACCESSIBILITY CONSIDERATIONS: The degree of accessibility required for maintenance purposes must be granted.
4.07 in (103.50 mm)
018 in
(4.50 mm)
4.72 in (120 mm)
ACCESSORY CONSIDERATIONS: The types of oponal and accessory equipment that will be used with the system must be kept in mind.
ELECTRONIC CONSIDERATIONS: The system contains sensive electronic components that
0.31 in
(8.0 mm)
1.0 in
(25.00 mm)
1.4 in
(36.00 mm)
1.0 in
(25.00 mm)
can be easily damaged. Do not touch nor disturb any of these components.
Mount the MGD-100 and Controller according to the above consideraons, product dimen­sions (see Secon 3), maximum wiring lengths (see Secon 5), and the corresponding mount-
Screw
0.2 in (5.0 mm)
0.4 in (9.0 mm)
0.6 in (15.5 mm)
2.0 in
(50.0 mm)
ing dimensions shown in the illustraons that follow.
3.5 in
(90 mm)
5.4 in
(138 mm)
2 x Clearance for M6
Mounng Holes
4.8 in
(122 mm)
5.1 in
(130 mm)
Ex d Housing
5.9 in (151 mm)
5.1 in (130 mm)
6.3 in (160 mm)
0.6 in
(15.0 mm)
0.5 in (12.7 mm)
0.4 in (10.0 mm)
1-2 Sensor
Controller
Housing
2.9 in (74.5 mm)
10.26 in (260.50mm)
Mounng
Hole
Screw
0.2 in (4.8 mm)
0.6 in (15.0 mm)
0.5 in (12.7 mm)
5.13 in (130.25 mm)
O 0.20 in (5.10 mm)
IP66 Housing
5.7 in
4.8 in (123 mm)
mounng slots =
0.35 in (9mm) long x
4.0 in
0.24 in (6mm) wide
(101 mm)
Use 3/16-inch screws (5mm - 6mm )
1.7 in
(42 mm)
2.3 in
(59 mm)
5.7 in
(146 mm)
(144 mm)
M42 thread
Exd Remote
Head
PRV/IP66 Vent Pipe
Monitoring 1
in BSP Head
1”BSP thread
9.47 in (240.50 mm)
8.85 in (224.70 mm)
4-6 Sensor
Controller Housing
O 0.18 in (4.60 mm)
9.55 in (242.50 mm)
5: WIRING
CABLE OPENINGS: The metal IP51 controller
housing provides a number of PG7 openings for cable glands or plugs. Each MGD-100 IP41 transmit­ter will have a single opening for an M20 cable gland, as well as an oponal knockout opening. Each MGD-100 IP66 tranmier has 3 openings These openings can be used for field wiring, direct aachment of a sensor or wiring of a remote sensor. Unused openings must be closed with a suitable plug and gasket, maintaining the IP or Ex d rang.
NOTE: To make wiring connecons, you must first open the MGD-100 housing. The enclosure lid of the IP66 housing has four capve screws.
Refer to the User Manual (part number 6109-
9000) at www.MyBacharach.com for detailed instrucons on accessing the internal components for wiring.
WARNING: The mains power supply cable should be of an approved type based on local regulaons. Connec­on to the mains power supply must be made via an approved, readily-accessible, switched and fused plug and socket (or as per local wiring regulaons) which should be within 10 feet (3 meters) of the control unit.
SHIELD WIRE WARNING: Con- nect the shield of the power wires to the earth ground of the central control system (e.g., chassis, ground bus bar, etc.).
1: Strip 0.2 to 0.25 inches (5 to 7 mm) of wiring insulaon. 2: Connect the wires as indicated.
NOTE: Aer wiring is completed, carefully re-assemble the enclosure and its components, nong the keyed ribbon cable and sensor connectors. Aer installaon is complete, be sure to refer to the User Manual (part number 6109-
9000) for detailed instrucons on registering the sensors and configur­ing the MGD-100 for proper opera­on.
Volt Free Alarm Relay
Relay
NC COM NO
HIGH
SAFE
ON
B
m
r
a
l
A
FAIL
u
e
l
KEY
z
z
e
r
A
u
d
b
i
OFF
RED
RED
LED (Opt.)
Chan 2 Alm
SENSOR 2
ON OFF
SENSOR 1
ON OFF
Channel 2
(Oponal)
Channel 1
Chan 1
Alarm LED
GRN
Fuse 2
Fuse 1
Mains
Power
Controller PCB
MAINS
Transformer
12V
2 Channel 1 Alarm
50/60Hz
ON
NC COM NO
High Relay
RED
Chan 4
Alarm LED
Mains
Power
Horn (12 VDC, 200 mA Max)
MAINS
Fuse
12V
PSU
+ 12V -
RED
GRN
Chan 1
Alarm LED
SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4 SENSOR 5 SENSOR 6
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
- SIREN +
Chan 2
Alarm LED
KEY
RED
REPLACE FUSE WITH M205 T2AL250V
OFF
Chan 3
Alarm LED
Fuse
FAIL SAFE
RED
Key Switch
RED
Chan 5
Alarm LED
500  (152 m) max;
22 AWG; Max 8.8Ω/wire
4-conductor cable (stranded);
Fail Safe Jumper Seng:
ON
ON: High Relay Is Normally Energized (De-energized on High Alarm or Mains Failure Condion)
OFF
OFF: High Relay Is Energized On Alarm (Energized on High Alarm Condion)
To Lid
Ground
Connecon
Base Ground
Connecon
RED
Chan 6
Alarm LED
SC
SENSOR
IR Gas Sensor PCB
ON
OFF
ON
OFF
RV1
Jumper Seng:
Fail Safe
ON: High Relay Is Normally Energized (De-energized on High Alarm or Mains Failure Condion)
OFF: High Relay Is Energized On Alarm (Energized on High Alarm Condion)
Relay Output
Sensor Enable
Jumper Sengs:
ON: Sensor is enabled for this channel
OFF: Sensor is disabled for this channel
High Alarm
Relay
(Volt Free)
Low Alarm
Relay
(Volt Free)
Mains
Power
GRN
Relay 2
NC COM NO
HIGH
Relay 1
Fuse 2
Controller PCB
ON
m
r
a
l
NC COM NO
Fuse 1
FAIL SAFE
u
B
A
e
l
LOW
KEY
RESET
SENSOR 2
ON OFF
RED
OFF
z
z
e
r
YEL
A
u
Chan 2 Alm LEDs (Opt.)
d
b
i
RED
SENSOR 1
ON OFF
Channel 2
(Oponal)
Channel 1
YEL
Chan 1 Alarm LEDs
GRN
MAINS
Transformer
12V
2 Channel 2 Alarm
Horn (12 VDC, 200 mA Max)
MAINS
Fuse
12V
PSU
+ 12V -
YEL
RED
Chan 1
Alarm LEDs
SENSOR 1 SENSOR 2 SENSOR 3 SENSOR 4 SENSOR 5 SENSOR 6
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
- SIREN +
YEL
Chan 2
Alarm LEDs
KEY RESET
RED
REPLACE FUSE WITH M205 T2AL250V
YEL
Chan 3
Alarm LEDs
Fuse
OFF
FAIL SAFE
RED
Mains
Power
Key Switch
50/60Hz
ON
NC COM NO
NC COM NO
High Relay Low Relay Fault Relay
YEL
Chan 4
Alarm LEDs
YEL
RED
Chan 5
Alarm LEDs
RED
500  (152 m) max;
22 AWG; Max 8.8Ω/wire
4-conductor cable (stranded);
Fail Safe Jumper Seng:
ON
ON: High Relay Is Normally Energized (De-energized on High Alarm or Mains Failure Condion)
OFF
OFF: High Relay Is Energized On Alarm (Energized on High Alarm Condion)
To Lid
Ground
Connecon
Push
Buon Switch
Base Ground
Connecon
NO COM NC
YEL
RED
Chan 6
Alarm LEDs
SC Gas Sensor PCB
SC
SENSOR
RV1
IR Gas Sensor PCB
ON
OFF
ON
Fail Safe
Jumper Seng:
ON: High Relay Is Normally Energized (De-energized on High Alarm or Mains Failure Condion)
OFF: High Relay Is Energized On Alarm (Energized on High Alarm Condion)
Relay Outputs
Sensor Enable
Jumper Sengs:
ON: Sensor is enabled for this channel
OFF
OFF: Sensor is disabled for this channel
World Headquarters
621 Hunt Valley Circle
New Kensington, PA 15068 USA
Phone: 724-334-5000 • Fax: 724-334-5001
Toll Free: 1-800-736-4666
Website: www.MyBacharach.com
E-mail: help@MyBacharach.com
114A Georges Street Lower
Dun Laoghaire • Co Dublin • Ireland
Phone: +353 1 284 6388 • Fax: +353 1 284 6389
Repeat for sensor
channels 3 through
6 as required.
4-conductor cable (stranded) (6 places max); 500  (152 m) max; 22 AWG; Max 8.8Ω/wire
Ensure that connecons 1 to 4
RV1
on each sensor connect to their
corresponding numbers on the terminal block in the main alarm unit, otherwise the system will not funcon correctly and could be damaged.
RV1
4-conductor cable (stranded) (6 places max); 500  (152 m) max; 22 AWG; Max 8.8Ω/wire
Ensure that connecons 1 to 4
on each sensor connect to their
corresponding numbers on the terminal block in the main alarm unit, otherwise the system will not funcon correctly and could be damaged.
6 Channel 1 Alarm
Repeat for sensor
channels 3 through
6 as required.
6 Channel 2 Alarm