Autonics SRS1 Series Catalog Page

SRS1 Series
Single-Phase, Socket Type SSR
Features
● Socket type for easier installation and maintenance
- SRS1-A: Autonics socket SK-G05 (AC, DC, AC/DC)
- SRS1-B: Universal LY2 sockets (AC)
- SRS1-C: Universal MY4 sockets (AC, DC, AC/DC)
● Zero cross turn-on, random turn-on models available
● Input indicator (red LED)
Please read “Safety Considerations” in the instruction manual before using.
Ordering Information
SRS1-A SRS1-B
SRS1-C
SRS 21 1B 2 02 R
Item
1: In case of SRS1-C1D102-1, SRS1-C1X201-1, rated input voltage is 4-24VDC.
- -
Rated load current (resistive load)
Rated load voltage
Rated input voltage
Socket
Control phase
Number of output circuits
Function
SRS1-A
SRS1-B
SRS1-C
SRS1-A
SRS1-B, SRS1-C
1 1
2 2
No mark Zero cross turn-on
R Random turn-on
01 1A
02 2A
03 3A
05 5A
2 24-240VAC
D1 5-100VDC
D2 5-200VDC
X2 5-240VAC/5-200VDC (universal)
2 90-240VAC
2 90-240VAC
D1 5-100VDC
X2 5-240VAC/5-200VDC (universal)
1 4-24VDC
1 4-30VDC
A
B Universal LY2 socket
C Universal MY4 socket
1 Single-phase
SRS Solid State Relay (socket type)
Autonics socket (Model: SK-G05)
1
K-40 K-41
Single-Phase, Socket Type SSR
Model Rated input voltage Rated load current Rated load voltage Function
SRS1-A
SRS1-B
SRS1-C
SRS1-A1202
SRS1-A1202R Random turn-on
SRS1-A1203
SRS1-A1203R Random turn-on
SRS1-A1205
SRS1-A1205R Random turn-on
4-24VDC
SRS1-A1D101 1A
SRS1-A1D102 2A
SRS1-A1D201
SRS1-A1X201 5-240VACᜠ/5-200VDC
SRS1-B1202-2
SRS1-B1202R-2 Random turn-on
SRS1-B1203-1
SRS1-B1203R-1 Random turn-on
4-30VDCᜡ
SRS1-B1205-1
SRS1-B1205R-1 Random turn-on
SRS1-C1202-2
SRS1-C1202R-2 Random turn-on
SRS1-C1203-1
SRS1-C1203R-1 Random turn-on
4-30VDC
SRS1-C1205-1
SRS1-C1205R-1 Random turn-on
SRS1-C1D102-1
SRS1-C1X201-1 1A 5-240VACᜠ/5-200VDC
4-24VDC
2A
3A
24-240VAC
5A
5-100VDC
1A
5-200VDC
2A (consists of 2 circuits)
3A
90-240VAC
5A
2A (consists of 2 circuits)
3A
90-240VACᜠ
5A
2A 5-100VDC
Zero cross turn-on
Zero cross turn-on
Zero cross turn-on
-
Zero cross turn-on
Zero cross turn-on
Zero cross turn-on
Zero cross turn-on
Zero cross turn-on
Zero cross turn-on
-
SENSORS
CONTROLLERS
MOTION DEVICES
SOFTWARE
(J) Temperature Controllers
(K) SSRs
(L) Power Controllers
(M) Counters
Specications
Input
Series
SRS1-A SRS1-B
SRS1-C1203(R)-1/ SRS1-C1205(R)-1
SRS1-C1202(R)-2/
Rated input voltage range 4-24VDC
Allowable input voltage range 4-26.4VDC
4-30VDC
4-32VDC
ᜡ ᜡ
4-30VDC
4-32VDC
Max. input current 15mA (Random turn-on) 13mA (Random turn-on) 13mA (Random turn-on) 15mA
Pick-up voltage Min. 4VDC
Drop-out voltage Max. 1VDC
Output (AC)
Model
SRS1-A1202(R) SRS1-A1203(R) SRS1-A1205(R)
Rated load voltage range 24-240VACrmsᜠ (50/60Hz) 90-240VACrmsᜠ (50/60Hz)
Allowable load voltage range 24-264VACrmsᜠ (50/60Hz) 90-264VACrmsᜠ (50/60Hz)
Rated load current
Resistive load
1
(AC-51)
2Arms 3Arms 5Arms 2Arms 3Arms 5Arms
Min. load current 0.15Arms 0.2Arms 0.15Arms
Max. 1cycle surge current (60Hz)
Max. non-repetitive surge current (I2t, t=8.3ms)
126A 250A 126A 250A
65A2s 400A2s 65A2s 220A2s
Peak voltage (non-repetitive) 600V
Leakage current (Ta=25℃) Max. 2mArms (240VACᜠ/60Hz)
Output on voltage drop[Vpk] (max. load current)
Static o󰀨-state dv/dt 500V/
Turn-on time
Zero cross turn-on
Random turn-on
Turn-o󰀨 time
1: AC-51 is utilization category at IEC 60947-4-3.
Max. 1.6V
Max. 0.5 cycle of load source + 1ms
Max. 1ms
Max. 0.5 cycle of load source + 1ms
SRS1-B1202(R)-2/ SRS1-C1202(R)-2
SRS1-C1D102-1/ SRS1-C1X201-1
4-24VDC
4-26.4VDC
SRS1-B1203(R)-1/ SRS1-C1203(R)-1
SRS1-B1205(R)-1/ SRS1-C1205(R)-1
(N) Timers
(O) Digital Panel Meters
(P) Indicators
(Q) Converters
(R) Digital Display Units
(S) Sensor Controllers
(T) Switching Mode Power Supplies
(U) Recorders
(V) HMIs
(W) Panel PC
(X) Field Network Devices
SRS1 Series
Specications
Output (DC, AC/DC)
Model
Rated load voltage range 5-100VDC
Allowable load voltage range 3-120VDC
Rated load current
Min. load current 10mA 10mA
Max. surge current (t=10ms) 5A 10A 4A 10A 4A
Leakage current Max. 100μA Max. 2mArms
Output on voltage drop[Vpk] (max. load current)
Static o󰀨-state dv/dt 500V/
Turn-on time Max. 1ms Max. 2ms Max. 1ms Max. 1ms Max. 2ms Max. 1ms
Turn-o󰀨 time Max. 1ms
1: AC-51 is utilization category at IEC60947-4-3.
Resistive load (AC-51)
General specifications
Series
Dielectric strength (Vrms) 2,500VAC 50/60Hz 1 min (input-output, input/output-case)
Insulation resistance Over 100MΩ (at 500VDC megger)
Indicator Input indicator: red LED
Ambient temperature
Environ
-ment Ambient humidity 45 to 85%RH, storage: 45 to 85%RH
Protection
Approval
1
Weight
1: The weight is per 10 units with packing and the weight of parenthesis is per 1 unit.
Environment resistance is rated at no freezing or condensation.
SRS1-A1D101 SRS1-A1D102 SRS1-A1D201 SRS1-C1D102-1 SRS1-A1X201 SRS1-C1X201-1
1Adc 2Adc 1Adc 2Adc 1Arms/1Adc
1
Max. 1.1V Max. 2.2V
SRS1-A SRS1-B SRS1-C
-20 to 70℃, storage: -30 to 100℃-20 to 80℃, storage: -30 to 100
(The rated load current capacity is di󰀨erent depending on ambient temperature. Refer to ‘ SSR Derating Curve’.)
IP10 (Protection structure of socket, SK-G05)
ᜢ ᜧ
Max. 3A: approx. 270g
(approx. 17g)
5A: approx. 380g (approx. 28g)
5-200VDC
3-220VDC
According to protection of the universal LY2 socket
Approx. 400g (approx. 30g) Approx. 400g (approx. 30g)
5-100VDC
3-120VDC
-
5-240VACrmsᜠ (50/60Hz) /
5-200VDC
3-264VACrmsᜠ (50/60Hz) /
3-220VDC
500V/
According to protection of the universal MY4 socket
-
Max. 2mArms (240VACᜠ/60Hz)
-
Dimensions
SRS1-A
L
Input indicator
(red)
K-42 K-43
5.4
13
4-0.5
4-5
4-Ø3
Max. 3A 5A
L 28 38
(unit: mm)
29
Single-Phase, Socket Type SSR
Dedicated socket for SRS1-A: SK-G05 (sold separately)
82.2
73.5
17.6
54.7
35mm DIN rail
SRS1-B
34.5
Input indicator
(red)
Panel cut-out
6.5
8-0.5
8-5
90.2
82.4
82.4
SENSORS
CONTROLLERS
MOTION DEVICES
2-Ø4.5
SOFTWARE
(J) Temperature Controllers
(K) SSRs
(L) Power Controllers
21
27
(M) Counters
(N) Timers
(O) Digital Panel Meters
SRS1-C
Input indicator
(red)
(P) Indicators
8-Ø3
(Q) Converters
(R)
34.5
6.5
21
8-0.5
27
Digital Display Units
(S) Sensor Controllers
(T) Switching Mode Power Supplies
(U) Recorders
(V) HMIs
(W) Panel PC
(X) Field Network Devices
8-R0.68-2.6
SRS1 Series
Connections
SRS1-A
SRS1-A1202(R)/SRS1-A1203(R)/
SRS1-A1205(R)
3
4
5
INPUT : 4-24VDC
SRS1-A1X201
3
4
5
INPUT : 4-24VDC
SRS1-B
SRS1-B1202(R)-2
2
4
6 8
INPUT : 4-30VDC
SRS1-A1202(R) : 240VAC 2A RESISTIVE LOAD SRS1-A1203(R)
1
: 240VAC 3A RESISTIVE LOAD SRS1-A1205(R) : 240VAC 5A RESISTIVE LOAD
SRS1-A1X201 : 200VDC 1A RESISTIVE LOAD
: 240VAC 1A RESISTIVE LOAD
1
1
SRS1-B1202(R)-2
3
: 240VAC 2A RESISTIVE LOAD
5 7
SRS1-A1D101/SRS1-A1D102/
SRS1-A1D201
3 4
5 1
INPUT : 4-24VDC
SRS1-A1D101 : 100VDC 1A RESISTIVE LOAD SRS1-A1D102 : 100VDC 2A RESISTIVE LOAD SRS1-A1D201 : 200VDC 1A RESISTIVE LOAD
SRS1-B1203(R)-1/SRS1-B1205(R)-1
2
4
6 8
INPUT : 4-30VDC
1
SRS1-B1203(R)-1
3
: 240VAC 3A RESISTIVE LOAD
5
SRS1-B1205(R)-1 : 240VAC 5A RESISTIVE LOAD
7
SRS1-C
SRS1-C1202(R)-2
SRS1-C1202(R)-2
: 240VAC 2A RESISTIVE LOAD
INPUT : 4-30VDC
SRS1-C1D102-1/SRS1-C1X201-1
SRS1-C1D102-1
: 100VDC 2A RESISTIVE LOAD
SRS1-C1X201-1 : 200VDC 1A RESISTIVE LOAD : 240VAC 1A RESISTIVE LOAD
INPUT : 4-24VDC
SRS1-C1203(R)-1/SRS1-C1205(R)-1
SRS1-C1203(R)-1 : 240VAC 3A RESISTIVE LOAD SRS1-C1205(R)-1 : 240VAC 5A RESISTIVE LOAD
INPUT : 4-30VDC
K-44 K-45
Single-Phase, Socket Type SSR
Example of Connection
SRS1-A
AC Load (SRS1-A1202(R)/SRS1-A1203(R)/SRS1-A1205(R))
5/+
4-24VDC
+
Input Output
-
1/-
DC Load (SRS1-A1D101/SRS1-A1D102/SRS1-A1D201)
5/+ 3/+
4-24VDC
+
Input Output
-
AC/DC Load (SRS1-A1X201)
5/+ 3
+
4-24VDC
Input Output
-
SRS1-B
8/+ 6
4-30VDC
+
Input Output
-
7/-
SRS1-C
AC Load (SRS1-C1202(R)-2/SRS1-C1203(R)-1/SRS1-C1205(R)-1
14/+
4-30VDC
+
-
DC Load (SRS1-C1D102-1)
4-24VDC
+
-
Input Output
13/-
14/+
Input Output
13/-
SRS1
SRS1
SRS1
SRS1
SRS1
SRS1
3
4
4/-1/-
41/-
4
8
12
8/+
12/-
Varistor
Varistor
Varistor
Varistor
Varistor
Varistor
1
Rapid fuse
1
Rapid fuse
1
Rapid fuse
1
Rapid fuse
1
Rapid fuse
1
Rapid fuse
Load
CAP
Load
Load
Load
CAP
Load
CAP
Load
SENSORS
Load
2
~
source
(AC)
Load
+
source
-
Load
source
~
(AC)
Load
2
~
source
(AC)
Load
2
~
source
(AC)
+
source
-
1: Must use a Varistor (470V, 0.6W)
2: When connecting capacitor as
above, it is appropriate for EMC. CAP: 1μF/250VAC
1: Must use a Varistor
(SRS1-A1D101/SRS1-A1D102:
(DC)
270V, 0.6W) (SRS1-A1D201: 470V, 0.6W)
-
+
Load
source
(DC)
+
-
1: Must use a Varistor (470V, 0.6W)
1: Must use a Varistor (470V, 0.6W)
2: When connecting capacitor as
above, it is appropriate for EMC. CAP: 1uF/250VAC
1: Must use a Varistor (470V, 0.6W)
2: When connecting capacitor as
above, it is appropriate for EMC. CAP: 1μF/250VAC
Load
(DC)
1: Must use a Varistor (270V, 0.6W)
CONTROLLERS
MOTION DEVICES
SOFTWARE
(J) Temperature Controllers
(K) SSRs
(L) Power Controllers
(M) Counters
(N) Timers
(O) Digital Panel Meters
(P) Indicators
(Q) Converters
(R) Digital Display Units
(S) Sensor Controllers
(T) Switching Mode Power Supplies
(U) Recorders
(V) HMIs
AC/DC Load (SRS1-C1X201-1)
SRS1
4-24VDC
14/+
+
-
Input Output
(W) Panel PC
(X) Field Network Devices
1
Rapid fuse
Load
Load
source
~
(AC)
+
-
1: Must use a Varistor (470V, 0.6W)
-
+
Load
source
(DC)
8
Varistor
1213/-
SRS1 Series
SSR Derating Curve
SRS1-A
SRS1-A1202(R)/SRS1-A1203(R)/
SRS1-A1205(R)
SRS1-A1205(R)
5
4
SRS1-A1203(R)
3
Load current[A]
SRS1-A1202(R)
2
1
0.7
0.5
0
SRS1-B
5
4
3
Load current[A]
2
1.6
1
0.7
0
10 20 30 40 50 60 70 80
SRS1-B1205(R)-1
SRS1-B1202(R)-2
10 2025 30 40 50 60 70 80 90
Ambient temperature [℃]
Ambient temperature [℃]
SRS1-B1203(R)-1
SRS1-A1D102/SRS1-A1D101/
SRS1-A1D201/SRS1-A1X201
SRS1-A1D102
2
1
Load current[A]
SRS1-A1D201/A1X201
0.6
0.3
0.2
0 10 20 30 40 50 60 70 80
Ambient temperature [℃]
SRS1-A1D101
SRS1-C
SRS1-C1202(R)-2/SRS1-C1203(R)-1/
SRS1-C1205(R)-1
SRS1-C1205(R)-1
5
4
3
Load current[A]
SRS1-C1202(R)-2
2
1.6
1
0.7
0
10 2025 30 40 50 60 70 80 90
Since e󰀨ectiveness of the heat radiation is decreased when multiple SSRs are installed closely, please supply less than 50% of the rated load current.
Above SSR derating curves obtained approval from the UL certication authority.
SRS1-C1203(R)-1
Ambient temperature [℃]
SRS1-C1D102-1/SRS1-C1X201-1
SRS1-CD102-1
2
1
Load current[A]
SRS1-C1X201-1
0.6
0.3
0.2
0 10 20 30 40 50 60 70 80
Ambient temperature [℃]
K-46 K-47
Single-Phase, Socket Type SSR
Proper Usage
Cautions during use
1. Follow instructions in ‘Cautions during Use’. Otherwise, it may cause unexpected accidents.
2. 4-24VDC, 4-30VDC signal input should be insulated and limited voltage/current or Class 2, SELV power supply device.
3. Install the unit in the well ventilated place.
4. While supplying power to the load or right after turning o󰀨 the power of the load, do not touch the body. Failure to follow this instruction may result in a burn due to the high temperature.
5. In order to protect the product from the short-circuit current of the load, use rapid fuse of which I2t is under the 1/2 of SSR I2t. When short-circuited, replace the fuse to those of same specication with the used rapid fuse.
6. Install dummy resistance in parallel with the load, to keep the sum of current owing in the load and dummy resistance being over SSR minimum load current.
7. When using random turn-on model for phase control, install noise lter between the load and the power of the load.
8. Do not use near the equipment which generates strong magnetic force or high frequency noise.
9. This unit may be used in the following environments.
Indoors (in the environment condition rated in ‘Specications’)
Altitude max. 2,000m
Pollution degree 2
Installation category II
SENSORS
CONTROLLERS
MOTION DEVICES
SOFTWARE
(J) Temperature Controllers
(K) SSRs
(L) Power Controllers
(M) Counters
(N) Timers
(O) Digital Panel Meters
(P) Indicators
(Q) Converters
(R) Digital Display Units
(S) Sensor Controllers
(T) Switching Mode Power Supplies
(U) Recorders
(V) HMIs
(W) Panel PC
(X) Field Network Devices
Loading...