Autonics SRH2, SRH3 Specifications

Page 1
SR2/SR3 Series
3-Phase, Detachable/Integrated Heatsink Type SSR

Features

Two mounting hole types and sizes
● Alarm function (overheat prevention) : Alarm indicator (red LED), disconnect standard output, alarm output
Dielectric strength: 4000VAC (also 2,500VAC model) High heat dissipation e󰀩ciency with ceramic PCB and integrated heatsink Zero cross turn-on, random turn-on models available Input indicator (green LED) Various mounting methods (DIN rail, panel) - SRH2/SRH3 series
*DIN rail mount not available for 50 A, 75 A load current models
Please read “Safety Considerations” in the instruction manual before using.

Ordering Information

Detachable Heatsink Integrated Heatsink
SR
H 3
Type
Item
Model Rated input voltage Rated load current Rated load voltage Function
SR(H)2-1215
SR(H)3-1215
SR(H)2-4215
SR(H)3-4215
SR(H)2-1230
SR(H)3-1230
SR(H)2-4230
SR(H)3-4230
SR(H)2-1250
SR(H)3-1250
SR(H)2-4250
SR(H)3-4250
SR(H)2-1275
SR(H)3-1275
SR(H)2-4275
SR(H)3-4275
1
-
Rated input voltage
Control phase
4-30VDC
90-240VAC
4-30VDC
90-240VAC
4-30VDC
90-240VAC
4-30VDC
90-240VAC
15 R
4
Rate load current (Resistive load)
Rated load voltage
ᜡ
ᜠ
ᜡ
ᜠ
ᜡ
ᜠ
ᜡ
ᜠ
Function
15A
30A
50A
75A
No mark R
15 30 40 50 75
2 4
1 2 4
2 3
No mark H
SR
24-240VAC
Zero cross turn-on Random turn-on
15A 30A 40A 50A 75A
24-240VAC 48-480VAC
4-30VDC 24VAC 90-240VAC
3-phase (2-pole) 3-phase (3-pole)
Detachable heatsink type Integrated heat sink type
Solid State Relay
ᜠ
Zero cross turn-on
K-32 K-33
Page 2
3-Phase, Detachable/Integrated Heatsink Type SSR
Model Rated input voltage Rated load current Rated load voltage Function
SR(H)2-1415
SR(H)3-1415
SR(H)2-1415R
SR(H)3-1415R
SR(H)2-2415
SR(H)3-2415
SR(H)2-4415
SR(H)3-4415
SR(H)2-1430
SR(H)3-1430
SR(H)2-1430R
SR(H)3-1430R
SR(H)2-2430
SR(H)3-2430
SR(H)2-4430
SR(H)3-4430
SR(H)2-1440
SR(H)3-1440
SR(H)2-1440R
SR(H)3-1440R
SR(H)2-2440
SR(H)3-2440
SR(H)2-4440
SR(H)3-4440
SR(H)2-1450
SR(H)3-1450
SR(H)2-1450R
SR(H)3-1450R
SR(H)2-2450
SR(H)3-2450
SR(H)2-4450
SR(H)3-4450
SR(H)2-1475
SR(H)3-1475
SR(H)2-1475R
SR(H)3-1475R
SR(H)2-2475
SR(H)3-2475
SR(H)2-4475
SR(H)3-4475
4-30VDC
24VAC
ᜠ
90-240VAC
4-30VDC
24VAC
ᜠ
90-240VAC
4-30VDC
24VAC
ᜠ
90-240VAC
4-30VDC
24VAC
ᜠ
90-240VAC
4-30VDC
24VAC
ᜠ
90-240VAC
ᜡ
15A
ᜠ
ᜡ
30A
ᜠ
ᜡ
40A
48-480VAC
ᜠ
ᜠ
ᜡ
50A
ᜠ
ᜡ
75A
ᜠ
Zero cross turn-on
Random turn-on
Zero cross turn-on
Zero cross turn-on
Zero cross turn-on
Random turn-on
Zero cross turn-on
Zero cross turn-on
Zero cross turn-on
Random turn-on
Zero cross turn-on
Zero cross turn-on
Zero cross turn-on
Random turn-on
Zero cross turn-on
Zero cross turn-on
Zero cross turn-on
Random turn-on
Zero cross turn-on
Zero cross turn-on
SENSORS
CONTROLLERS
MOTION DEVICES
SOFTWARE
(J) Temperature Controllers
(K) SSRs
(L) Power Controllers
(M) Counters
(N) Timers
(O) Digital Panel Meters
(P) Indicators
(Q) Converters
(R) Digital Display Units
(S) Sensor Controllers
(T) Switching Mode Power Supplies
Specications
Input
Rated input voltage range
Input voltage range 4-32VDC
4-30VDC
ᜡ
ᜡ
Max. input current 25mA 15mA 25mA
Pick-up voltage Min. 4VDC
Drop-out voltage Max. 1VDC
Zero cross turn-on
Turn-on
time
Random turn-on Max. 1ms
Turn-o󰀨 time
Max. 0.5 cycle of load source + 1ms Max. 1.5 cycle of load source + 1ms Max. 1.5 cycle of load source + 1ms
Max. 0.5 cycle of load source + 1ms Max. 1.5 cycle of load source + 1ms Max. 1.5 cycle of load source + 1ms
ᜡ
ᜡ
24VACrmsᜠ (50/60Hz) 90-240VACrmsᜠ (50/60Hz)
19-26.4VACrmsᜠ (50/60Hz) 85-264VACrmsᜠ (50/60Hz)
Min. 19VACrmsᜠ Min. 85VACrmsᜠ
Max. 4VACrmsᜠ Max. 10VACrmsᜠ
- -
(U) Recorders
(V) HMIs
(W) Panel PC
(X) Field Network Devices
Page 3
SR2/SR3 Series
Specications
O
utput
Rated load voltage range
Load voltage range 24-264VACrmsᜠ (50/60Hz) 48-528VACrmsᜠ (50/60Hz)
Rated load current
Min. load current 0.15Arms 0.2Arms 0.5Arms 0.5Arms
Max. 1 cycle surge current (60Hz)
Max. non-repetitive surge current (I2t, t=8.3ms)
Peak voltage (non-repetitive)
Leakage current (Ta=25℃) Max. 10mArms (240VACᜠ/60Hz) Max. 10mArms (480VACᜠ/60Hz)
Output on voltage drop [Vpk] (max. load current)
Static o󰀨-state dv/dt 500V/
※
1: AC-51 is utilization category at IEC 60947-4-3.
Alarm output (overheat prevention)
Rated input voltage range
Load input voltage
Load input current
Turn-o󰀨 time Max. 20ms Max. 40ms Max. 40ms
※
Overheat prevention function: When SSR internal temperature is overheated, the load output is cut o󰀨 to prevent internal device damage.
※
To clear alarm, cut OFF the input signal during over alarm output return time at the rated ambient temperature.
G
Dielectric strength (Vrms)
Insulation resistance Over 100MΩ (at 500VDC megger) (input-output, input/output-case)
Indicator Input indicator: Green LED / Alarm indicator: Red LED
Vibration
Shock
Environ-
ment
Input terminal connection, alarm output terminal connection
Output terminal connection
Input terminal xed torque 0.75 to 0.95N·m
Output terminal xed torque 1.6 to 2.2N·m
Approval
Weight
※1: The weight includes packaging. The weight in parenthesis is for unit only. ※
Environment resistance is rated at no freezing or condensation.
※
For wiring the terminal, round terminal must be used.
Resistive load (AC-51)
eneral specications
Mechanical 0.75mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 1 hour
Malfunction 0.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 10 min
Mechanical 300m/s² (approx. 30G) in each X, Y, Z direction for 3 times
Malfunction 100m/s² (approx. 30G) in each X, Y, Z direction for 3 times
Ambient temperature
Ambient humidity 45 to 85%RH, Storage: 45 to 85%RH
※1
24-240VACrmsᜠ (50/60Hz) 48-480VACrmsᜠ (50/60Hz)
15Arms 30Arms 50Arms 75Arms 15Arms 30Arms 40Arms 50Arms 75Arms
1
※
250A 400A 1000A 300A 500A 1000A
340A2S 1000A2S 4000A2S 350A2S 1000A2S 4000A2S
600V 1200V (Zero cross turn-on), 1000V (Random turn-on)
Max. 1.6V
㎲
4-30VDC
ᜡ
Max. 30VDC
Max. 100mA Max. 50mA Max. 50mA
The alarm indicator turns ON and alarm output turns ON.
24-240VACᜠ rated load current 15A/30A
: 2500VAC 50/60Hz 1 min (input-output, input/output-case)
24-240VACᜠ rated load current 50A/75A
48-480VACᜠ rated load current 15A/30A/40A/50A/75A
: 4000VAC 50/60Hz 1 min (input-output, input/output-case)
-30 to 80℃ (in case of the rated input voltage 90-240VACᜠ: -30 to 70℃), storage: -30 to 100 ( The rated load current capacity is di󰀨erent depending on ambient temperature.
Refer to ' SSR Derating Curve'.)
Min. 1×0.5mm2 (1×AWG 20), max. 1×1.5mm2 (1×AWG 16) or 2×1.5mm2 (2×AWG 16)
Min. 1×1.5mm2 (1×AWG 16), max. 1×16mm2 (1×AWG 6) or 2×6mm2 (2×AWG 10)
※
Use wires compliant with load current capacity to connect to the terminal.
Detachable heatsink type: approx. 365g (approx. 275g) Integrated heat sink type - Rated load current 15A/30A/40A: approx. 896g (approx. 686g)
ᜡ
24VACrmsᜠ (50/60Hz) 90-240VACrmsᜠ (50/60Hz)
Max. 30VDC
Rated load current 50A: approx. 1508g (approx. 1268g) Rated load current 75A: approx. 2354g (approx. 2064g)
ᜡ
Max. 30VDC
ᜡ
℃
K-34 K-35
Page 4
3-Phase, Detachable/Integrated Heatsink Type SSR

Dimensions

Detachable heatsink type
109
97
4-Ø5.2
92
4-5.2
Alarm indicator
4-R2.6
(red)
Integrated heatsink (rated load current 15A/30A/40A)
130
2-Ø4.5
3.5 3.5
103
Input indicator
(green)
32
75.5
47.6
Input indicator
76
32.2
(green)
90
100
Panel cut-out
97
92
※
Detachable heatsink type screw tightening torque for mounting
8-M5
32
47.6
: 2.5N.m to 3N.m
112.7
32.2
35mm DIN rail
(unit: mm)
SENSORS
CONTROLLERS
MOTION DEVICES
SOFTWARE
(J) Temperature Controllers
(K) SSRs
(L) Power Controllers
(M) Counters
(N) Timers
4.5
Alarm indicator
(red)
3.5
Cooling fan mounting hole (
rated load current
30A/40A)
71.5
4.5
3.5
4-Ø3.2
71.5
DIN rail bracket
※
DIN rail must be grounded.
Panel cut-out
103
4-M4
90
7 7
※
Integrated heatsink type screw tightening torque for mounting: 1.35N.m
※
When installing multiple SSRs, please keep space between SSRs for heat radiation. When installing SSRs horizontally (input part and output part on the same height), please supply less than 50% of the rated load current.
(O) Digital Panel Meters
(P) Indicators
(Q) Converters
(R) Digital Display Units
(S) Sensor Controllers
(T) Switching Mode Power Supplies
(U) Recorders
(V) HMIs
(W) Panel PC
(X) Field Network Devices
Page 5
SR2/SR3 Series
Integrated heat sink (rated load current 50A)
144
132
Alarm indicator (red)
Cooling fan mounting hole
Input indicator (green)
2-Ø4.5
80
65
2-2
2-4.5
4-Ø3.4
Panel cut-out
132.2
※
132 4-M4
Bolts for grounding must be
grounded.
82.5
82.5
Integrated heat sink (rated load current 75A)
144
132
Alarm indicator (red)
Cooling fan mounting hole
Input indicator (green)
2-Ø4.5
130
115
2-2
2-4.5
4-Ø3.4
Panel cut-out
65
132.2
※
Bolts for grounding must be
grounded.
132 4-M4
High temperature caution
82.5
82.5
※
Integrated heatsink type screw tightening torque for mounting:1.35N.m
※
When installing multiple SSRs, please keep space between SSRs for heat radiation. When installing SSRs horizontally (input part and output part on the same height), please supply less than 50% of the rated load current.
While supplying power to the
115
load or right after turning o󰀨 the power of the load, do not touch the body and heat sink. Failure to follow this instruction may result in a burn due to the high temperature.
K-36 K-37
Page 6
3-Phase, Detachable/Integrated Heatsink Type SSR

Connections

3-phase (2-pole)
R S T
Rapid
fuse
1/L1
2/T1
3/L2
4/T2
5/L3
6/T3
Input
circuit
Over
heating
detection
circuit
7/A1+
8/A2-
9/AL+
10/AL-
(AC, DC)
+
-
LOAD
Alarm out (NPN open collector output)
Load
※
For DC signal input models, 8 and 10 terminals are connected inside.
※
For AC signal input models, 8 and 10 terminals are insulated inside.
※
Use terminals of size specied below.
Terminal type
a
<Round>
Input
a Min. 3.5mm Min. 5.0mm
b
b Max. 7.0mm Max. 12.0mm
3-phase (3-pole) delta connection ( -connection)
R S T
Power
supply
1/L1
3/L2
5/L3
+
-
2/T1
4/T2
6/T3
Output
Rapid
Load
fuse
Input
circuit
Over
heating
detection
circuit
7/A1+
8/A2-
9/AL+
10/AL-
+
-
LOAD
Alarm out (NPN open collector output)
3-phase (3-pole) star connection (Y-connection)
R S T
Power
supply
(AC, DC)
1/L1
3/L2
+
2/T1
-
4/T2
5/L3
6/T3
Rapid
Load
fuse
Input
circuit
Over
heating
detection
circuit
7/A1+
8/A2-
9/AL+
10/AL-
Power
supply
(AC, DC)
+
-
LOAD
+
-
Alarm out (NPN open collector output)
SENSORS
CONTROLLERS
MOTION DEVICES
SOFTWARE
(J) Temperature Controllers
(K) SSRs
(L) Power Controllers

SSR Derating Curve

SR(H)2/SR(H)3-1215
With heatsink
15
10
Load current [A]
Without heatsink
4
1.5 0
0 10 20 30 40 50 60 70 80 90
SR(H)2/SR(H)3-4215
With heatsink
15
10
Load current [A]
Without heatsink
4
1.5
0
0 10 20 30 40 50 60 70 80 90
SR(H)2/SR(H)3-1230
With heatsink+Fan
30
20
With heatsink
Load current [A]
15 14
10
Without heatsink
5 4
1.5 0
0 10 20 30 40 50 60 70 80 90
Ambient temperature [℃]
Ambient temperature [℃]
Ambient temperature [℃]
SR(H)2/SR(H)3-1415/1415R/2415
With heatsink
15
10
Load current [A]
Without heatsink
4
1.5 0
0 10 20 30 40 50 60 70 80 90
Ambient temperature [℃]
SR(H)2/SR(H)3-4415
With heatsink
15
10
Load current [A]
Without heatsink
4
1.5
0
0 10 20 30 40 50 60 70 80 90
Ambient temperature [℃]
SR(H)2/SR(H)3-1430/1430R/2430
With heatsink+Fan
30
20
With heatsink
Load current [A]
15
10
Without heatsink
5
1.5 0
0 10 20 30 40 50 60 70 80 90
Ambient temperature [℃]
(M) Counters
(N) Timers
(O) Digital Panel Meters
(P) Indicators
(Q) Converters
(R) Digital Display Units
(S) Sensor Controllers
(T) Switching Mode Power Supplies
(U) Recorders
(V) HMIs
(W) Panel PC
(X) Field Network Devices
Page 7
SR2/SR3 Series
SSR Derating Curve
SR(H)2/SR(H)3-4230
With heatsink+Fan
30
20
With heatsink
Load current [A]
15 14
10
Without heatsink
5 4
1.5 0
0 10 20 30 40 50 60 70 80 90
SR(H)2/SR(H)3-1440/1440R/2440
With heatsink+Fan
40
Load current [A]
With heatsink
19
15
Without heatsink
7 5
0
0 10 20 30 40 50 60 70 80 90
SR(H)2/SR(H)3-1250/1450/1450R/2450
60
With heatsink+Fan
50
40
Load current [A]
With heatsink
23 16
Without heatsink
9
5 0
0 10 20 30 40 50 60 70 80 90
SR(H)2/SR(H)3-1275/1475/1475R/2475
With heatsink+Fan
75
Ambient temperature [℃]
1.5
Ambient temperature [℃]
1.5
Ambient temperature [℃]
SR(H)2/SR(H)3-4430
With heatsink+Fan
30
20
Load current [A]
With heatsink
15
10
Without heatsink
7 5
1.5 0
0 10 20 30 40 50 60 70 80 90
SR(H)2/SR(H)3-4440
With heatsink+Fan
40
Load current [A]
With heatsink
19
15
Without heatsink
7 5
0
0 10 20 30 40 50 60 70 80 90
SR(H)2/SR(H)3-4250/4450
60
With heatsink+Fan
50
40
Load current [A]
With heatsink
23 16
9
Without heatsink
5
0
0 10 20 30 40 50 60 70 80 90
SR(H)2/SR(H)3-4275/4475
With heatsink+Fan
75
Ambient temperature [℃]
Ambient temperature [℃]
Ambient temperature [℃]
1.5
1.5
50
With heatsink
Load current [A]
34
16
Without heatsink
10
5 0
0
10 20 30 40 50 60 70 80 90
※
The heatsink of the curves is dedicated for the SRH2/SRH3.
※
Install SR2/SR3 Series on the metal plate (min. 130mm×120mm).
Since e󰀨ectiveness of the heat radiation is decreased when multiple SSRs are installed closely, please supply less than 50% of the rated load current.
※
Above SSR derating curves obtained approval from the UL certication authority.
Ambient temperature [℃]
1.5
50
Load current [A]
With heatsink
34
16
10
Without heatsink
5 0
0 10 20 30 40 50 60 70 80 90
Ambient temperature [℃]
1.5
Specication of cooling fan
1
Load capacity Cooling fan type Size (mm)
30A/40A
50A/75A
※
1: The cooling fan should be over the rated air ow value.
※
Autonics does not provide or sell a cooling fan. (Please buy a cooling fan separately.)
AC Fan DC Fan 1.25 44.0 AC Fan DC Fan 1.80 63.5
80×80
92×92
Rated air ow
m3/min CFM
0.68 24.0
1.13 40.0
K-38 K-39
※
Page 8
3-Phase, Detachable/Integrated Heatsink Type SSR

Proper Usage

Cautions during use
1. Follow instructions in 'Cautions during Use'. Otherwise, it may cause unexpected accidents.
2. 4-30VDC, 24VAC signal input should be insulated and limited voltage/current or Class 2, SELV power supply device.
3. Attach a heat sink or install the unit in the well ventilated place. To attach the heat sink, use Thermal Grease as below or that of equal specication.
※
Thermal Grease: GE TOSHIBA (YG6111), KANTO-KASEI (FLOIL G-600), SHINETSU (G746)
4. Ground to the heat sink, panel, or DIN rail. Failure to follow this instruction may result in electric shock.
5. While supplying power to the load or right after turning o󰀨 the power of the load, do not touch the body and heat sink. Failure to follow this instruction may result in a burn due to the high temperature.
6. In order to protect the product from the short-circuit current of the load, use rapid fuse of which I2t is under the 1/2 of SSR I2t. When short-circuited, replace the fuse to those of same specication with the used rapid fuse.
7. Install dummy resistance in parallel with the load, to keep the sum of current owing in the load and dummy resistance being over SSR minimum load current.
8. When using random turn-on model for phase control, install noise lter between the load and the power of the load.
9. Do not use near the equipment which generates strong magnetic force or high frequency noise.
10. This unit may be used in the following environments.
①
Indoors (in the environment condition rated in 'Specications')
②
Altitude max. 2,000m
③
Pollution degree 2
④
Installation category III
SENSORS
CONTROLLERS
MOTION DEVICES
SOFTWARE
(J) Temperature Controllers
(K) SSRs
(L) Power Controllers
(M) Counters
(N) Timers
(O) Digital Panel Meters
(P) Indicators
(Q) Converters
(R) Digital Display Units
(S) Sensor Controllers
(T) Switching Mode Power Supplies
(U) Recorders
(V) HMIs
(W) Panel PC
(X) Field Network Devices
Loading...