
DRW160912AC
Single-Phase, Detachable Type SSR
SR1 SERIES
I N S T R U C T I O N M A N U A L
Thank you for choosing our Autonics product.
Please read the following safety considerations before use.
Safety Considerations
Please observe all safety considerations for safe and proper product operation to avoid
※
hazards.
symbol represents caution due to special circumstances in which hazards may occur.
※
Failure to follow these instructions may result in serious injury or death.
Warning
Caution
Warning
1. Fail-safe device must be installed when using the unit with machinery that may
cause serious injury or substantial economic loss. (e.g. nuclear power control,
medical equipment, ships, vehicles, railways, aircraft, combustion apparatus, safety
equipment, crime/disaster prevention devices, etc.)
Failure to follow this instruction may result in re, personal injury, or economic loss.
2. Install on a device panel to use.
Failure to follow this instruction may result in electric shock or re.
3. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock or re.
4. Check 'Connections' before wiring.
Failure to follow this instruction may result in re.
5. Do not disassemble or modify the unit.
Failure to follow this instruction may result in electric shock or re.
Caution
1. Use the unit within the rated specications.
Failure to follow this instruction may result in re or product damage.
2. Use dry cloth to clean the unit, and do not use water or organic solvent.
Failure to follow this instruction may result in electric shock or re.
3. Do not use the unit in the place where ammable/explosive/corrosive gas, humidity,
direct sunlight, radiant heat, vibration, impact, or salinity may be present.
Failure to follow this instruction may result in re or explosion.
4. Keep metal chip, dust, and wire residue from owing into the unit.
Failure to follow this instruction may result in re or product damage.
5. Since leakage current still ows right after turning off the power or in the output OFF
status, do not touch the load terminal.
Failure to follow this instruction may result in electric shock.
Dimensions
Input indicator
(green)
※
When installing multiple SSRs, please keep space between SSRs for heat radiation.
When installing SSRs horizontally (input part and output part on the same height), please
supply less than 50% of the rated load current.
※
The above specifications are subject to change and some models may be discontinued
without notice.
※
Be sure to follow cautions written in the instruction manual and the technical descriptions
(catalog, homepage).
Failure to follow these instructions may result in personal injury or product damage.
(unit: mm)
Panel cut-out
4.5
Ø4.5
47.5
2-M4
58
※
Screw tightening torque
for mounting: 1.8 to 2.5N.m
47.5
44 28.3
Model
Model Rated input voltage Rated load current Rated load voltage Function
SR1-1210-N 4-30VDC
SR1-4210-N 90-240VAC
SR1-1215-N 4-30VDC
SR1-4215-N 90-240VAC
SR1-1220-N 4-30VDC
SR1-4220-N 90-240VAC
SR1-1225-N 4-30VDC
SR1-4225-N 90-240VAC
SR1-1230-N 4-30VDC
SR1-4230-N 90-240VAC
SR1-1240-N 4-30VDC
SR1-4240-N 90-240VAC
SR1-1250-N 4-30VDC
SR1-4250-N 90-240VAC
SR1-1275-N 4-30VDC
SR1-4275-N 90-240VAC
SR1-1410-N
SR1-1410R-N Random turn-on
4-30VDC
10A
15A
20A
25A
24-240VAC Zero cross turn-on
30A
40A
50A
75A
Zero cross turn-on
10A
SR1-4410-N 90-240VAC Zero cross turn-on
SR1-1415-N
SR1-1415R-N Random turn-on
4-30VDC
15A
Zero cross turn-on
SR1-4415-N 90-240VAC Zero cross turn-on
SR1-1420-N
SR1-1420R-N Random turn-on
4-30VDC
20A
Zero cross turn-on
SR1-4420-N 90-240VAC Zero cross turn-on
SR1-1425-N
SR1-1425R-N Random turn-on
SR1-4425-N 90-240VAC Zero cross turn-on
SR1-1430-N
SR1-1430R-N Random turn-on
4-30VDC
4-30VDC
25A
48-480VAC
30A
Zero cross turn-on
Zero cross turn-on
SR1-4430-N 90-240VAC Zero cross turn-on
SR1-1440-N
SR1-1440R-N Random turn-on
4-30VDC
40A
Zero cross turn-on
SR1-4440-N 90-240VAC Zero cross turn-on
SR1-1450-N
SR1-1450R-N Random turn-on
4-30VDC
50A
Zero cross turn-on
SR1-4450-N 90-240VAC Zero cross turn-on
SR1-1475-N
SR1-1475R-N Random turn-on
4-30VDC
75A
Zero cross turn-on
SR1-4475-N 90-240VAC Zero cross turn-on
Cautions during Use
1. Follow instructions in 'Cautions during Use'. Otherwise, it may cause unexpected accidents.
2. 4-30VDC signal input should be insulated and limited voltage/current or Class 2, SELV
power supply device.
3. Attach a heat sink or install the unit in the well ventilated place.
To attach the heat sink, use Thermal Grease as below or that of equal specication.
※
Thermal Grease: GE TOSHIBA (YG6111), KANTO-KASEI (FLOIL G-600),
4. Ground to the heat sink, panel, or DIN rail.
Failure to follow this instruction may result in electric shock.
5. While supplying power to the load or right after turning off the power of the load, do not
touch the body and heat sink.
Failure to follow this instruction may result in a burn due to the high temperature.
6. In order to protect the product from the short-circuit current of the load, use rapid fuse of
which I2t is under the 1/2 of SSR I2t. When short-circuited, replace the fuse to those of same
specication with the used rapid fuse.
7. Install dummy resistance in parallel with the load, to keep the sum of current owing in the
load and dummy resistance being over SSR minimum load current.
8. When using random turn-on model for phase control, install noise lter between the load
and the power of the load.
9. Do not use near the equipment which generates strong magnetic force or high frequency
noise.
10. This unit may be used in the following environments.
Indoors (in the environment condition rated in 'Specications')
①
Altitude max. 2,000m
②
Pollution degree 2
③
④ Installation category III
SHINETSU (G746)
Specications
Input
Rated input voltage range
Allowable input voltage range
4-30VDC
ᜡ
4-32VDCᜡ 85-264VACrmsᜠ (50/60Hz)
Max. input current 18mA 18mArms (240VACrmsᜠ)
Pick-up voltage Min. 4VDCᜡ Min. 85VACrmsᜠ
Drop-out voltage Max. 1VDCᜡ Max. 10VACrmsᜠ
Zero cross
turn-on
Turn-on
time
Random
turn-on
Turn-off time
Max. 0.5 cycle of load source + 1ms
Max. 1ms
Max. 0.5 cycle of load source + 1ms
90-240VACrmsᜠ (50/60Hz)
Max. 2 cycle of load source + 1ms
-
Max. 2 cycle of load source + 1ms
Output
Rated load voltage range
Allowable load voltage range
Rated load
current
Resistive load
(AC-51)
Min. load current 0.15Arms 0.2Arms 0.2Arms 0.5Arms
Max. 1 cycle surge
current (60Hz)
Max. non-repetitive surge
current (I2t, t=8.3ms)
Peak voltage
(non-repetitive)
Leakage current (Ta=25℃)
Output on voltage drop
[Vpk] (max. load current)
Static off state dv/dt 500V/
Rated load voltage range
Allowable load voltage range
Rated load
current
Resistive load
(AC-51)
Min. load current 0.5Arms 0.5Arms 0.5Arms 0.5Arms
Max. 1 cycle surge
current (60Hz)
Max. non-repetitive surge
current (I2t, t=8.3ms)
Peak voltage
(non-repetitive)
Leakage current (Ta=25℃)
Output on voltage drop
[Vpk] (max. load current)
Static off state dv/dt 500V/
24-240VACrmsᜠ (50/60Hz)
24-264VACrmsᜠ (50/60Hz)
10Arms 15Arms 20Arms 25Arms 30Arms 40Arms 50Arms 75Arms
※
1
160A 250A 400A 1000A
130A2s 300A2s 910A2s 4000A2s
600V
Max. 10mArms (240VACᜠ/60Hz)
Max. 1.6V
㎲
48-480VACrmsᜠ (50/60Hz)
48-528VACrmsᜠ (50/60Hz)
10Arms 15Arms 20Arms 25Arms 30Arms 40Arms 50Arms 75Arms
※
1
300A 500A 500A 1000A
350A2s 1000A2s 1000A2s 4000A2s
1200V (Zero cross turn-on), 1000V (Random turn-on)
Max. 10mArms (480VACᜠ/60Hz)
Max. 1.6V
㎲
General specications
Dielectric strength (Vrms)
Insulation resistance Over 100MΩ (at 500VDC megger) (input-output, input/output-case)
Indicator Input indicator: green LED
Mechanical
Vibration
Malfunction
Mechanical
Shock
Malfunction
Ambient temp.
Environment
Ambient humi.
Input terminal
connection
Output terminal
connection
Input terminal xed torque
Output terminal xed torque
Approval
※
1
Weight
※
1: The weight includes packaging. The weight in parenthesis is for unit only.
※
Environment resistance is rated at no freezing or condensation.
※
For wiring the terminal, round terminal must be used.
2500VAC 50/60Hz 1 min (input-output, input/output-case)
0.75mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z
direction for 1 hour
0.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z
direction for 10 min
300m/s² (approx. 30G) in each X, Y, Z direction for 3 times
100m/s² (approx. 30G) in each X, Y, Z direction for 3 times
-30 to 80℃ (in case of the rated input voltage 90-240VACᜠ: -20 to 70℃),
storage: -30 to 100℃
( The rated load current capacity is different depending on ambient
temperature. Refer to ' SSR Derating Curve'.)
45 to 85%RH, storage: 45 to 85%RH
Min. 1×0.5mm2 (1×AWG20),
max. 1×1.5mm2 (1×AWG16) or 2×1.5mm2 (2×AWG16)
Min. 1×1.5mm2 (1×AWG16),
max. 1×16mm2 (1×AWG6) or 2×6mm2 (2×AWG10)
※
Use wires compliant with load current capacity to connect to the terminal.
0.75 to 0.95N.m
1.6 to 2.2N.m
ᜢ ᜧ
Approx. 111g (approx. 73g)
Connections
Power supply
(AC, DC)
※
Use terminals of size specied below.
Terminal type
a
<Round>
Input
a Min. 3.5mm Min. 5.0mm
b
b Max. 7.0mm Max. 12.0mm
SSR Module
4/A2- 1/L1
SR1 series
Input Output
3/A1+ 2/T1
Output
Load
Rapid fuse
Load
power source
(AC)
SSR Derating Curve
※
Be sure that the ambient temperature and the derating curve is different by the rated input voltage.
: Rated input voltage 4-30VDC (SR1-1 -N)
: Rated input voltage 90-240VAC (SR1-4 -N)
SR1-1210/4210-N
20
With heatsink 2.5℃/W
10
7
Without heatsink
Load current[A]
5
1.5
0
0
10 20 25 30 40 50 60 70 80 90
Ambient temperature[℃]
SR1-1215/4215-N
20
With heatsink 2.5℃/W
15
10
Without heatsink
7
Load current[A]
5
1.5
0
0
10 20 25 30 40 50 60 70 80 90
Ambient temperature[℃]
SR1-1220/4220-N
With heatsink 2.0℃/W
20
10
Without heatsink
7
Load current[A]
5
1.5
0
0
10 20 25 30 40 50 60 70 80 90
Ambient temperature[℃]
SR1-1225/4225-N
30
With heatsink 0.9℃/W
25
20
10
Without heatsink
Load current[A]
7
5
1.5
0
0
10 20 25 30 40 50 60 70 80 90
Ambient temperature[℃]
SR1-1230/4230-N
With heatsink 0.9℃/W
30
20
15
Load current[A]
Without heatsink
6
1.5
0
0
10 20 25 30 40 50 60 70 80 90
Ambient temperature[℃]
SR1-1240/4240-N
With heatsink 0.9℃/W
40
20
15
Load current[A]
Without heatsink
6
1.5
0
0
10 20 25 30 40 50 60 70 80 90
Ambient temperature[℃]
SR1-1250/1450/1450R-N
SR1-4250/4450-N
60
With heatsink 0.9℃/W
50
40
20
Load current[A]
15
Without heatsink
7
1.5
0
0
10 20 30 40 50 60 70 80 90
Since effectiveness of the heat radiation is decreased when multiple SSRs are installed closely,
please supply less than 50% of the rated load current.
※
Above SSR derating curves obtained approval from the UL certication authority.
Ambient temperature[℃]
SR1-1410/1410R/4410-N
20
With heatsink 2.5℃/W
10
Without heatsink
6
Load current[A]
1.5
0
0
10 20 30 40 50 60 70 80 90
Ambient temperature[℃]
SR1-1415/1415R/4415-N
20
With heatsink 2.5℃/W
15
10
Without heatsink
6
Load current[A]
1.5
0
0
10 20 30 40 50 60 70 80 90
Ambient temperature[℃]
SR1-1420/1420R/4420-N
With heatsink 2.0℃/W
20
10
8
6
Load current[A]
Without heatsink
1.5
0
0
10 20 30 40 50 60 70 80 90
Ambient temperature[℃]
SR1-1425/1425R/4425-N
30
With heatsink 2.0℃/W
25
20
10
8
Load current[A]
6
Without heatsink
1.5
0
0
10 20 30 40 50 60 70 80 90
Ambient temperature[℃]
SR1-1430/1430R/4430-N
With heatsink 0.9℃/W
30
20
15
Load current[A]
Without heatsink
Without hea tsink
6
1.5
0
0
10 20 30 40 50 60 70 80 90
Ambient temperature[℃]
SR1-1440/1440R/4440-N
With heatsink 0.9℃/W
40
20
15
Load current[A]
Without heatsink
Without hea tsink
6
1.5
0
0
10 20 30 40 50 60 70 80 90
Ambient temperature[℃]
SR1-1275/1475/1475R-N
SR1-4275/4475-N
With heatsink 0.5℃/W
75
50
25
Load current[A]
16
Without heatsink
7
1.5
0
0
10 20 30 40 50 60 70 80 90
Ambient temperature[℃]
Major Products
Photoelectric Sensors Temperature Controllers
Fiber Optic Sensors Temperature/Humidity Transducers
Door Sensors SSRs/Power Controllers
Door Side Sensors Counters
Area Sensors Timers
Proximity Sensors Panel Meters
Pressure Sensors Tachometers/Pulse(Rate) Meters
Rotary Encoders Display Units
Connectors/Sockets Sensor Controllers
Switching Mode Power Supplies
Control Switches/Lamps/Buzzers
I/O Terminal Blocks & Cables
Stepper Motors/Drivers/Motion Controllers
Graphic/Logic Panels
Field Network Devices
Laser Marking System(Fiber, Co₂, Nd:YAG)
Laser Welding/Cutting System
http://www.autonics.com
HEADQUARTERS:
18, Bansong-ro 513beon-gil, Haeundae-gu, Busan,
South Korea, 48002
TEL: 82-51-519-3232
E-mail:
sales@autonics.com
DRW160912AC