DRW161291AA
SWITCHING MODE POWER SUPPLY
SPB SERIES
I N S T R U C T I O N M A N U A L
Please read the following safety considerations before use.
Safety Considerations
※
Please observe all safety considerations for safe and proper product operation to avoid hazards.
※
Safety considerations are categorized as follows.
Warning Failure to follow these instructions may result in serious injury or death.
Caution Failure to follow these instructions may result in personal injury or product damage.
※
The symbols used on the product and instruction manual represent the following.
symbol represents caution due to special circumstances in which hazards may occur.
Warning
1. Fail-safe device must be installed when using the unit with machinery that may cause
serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment,
ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster
prevention devices, etc.)
Failure to follow this instruction may result in personal injury, re, or economic loss.
2. Do not disassemble or modify the unit. Please contact us if necessary.
Failure to follow this instruction may result in electric shock, re or product damage.
3. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock.
4. Power input voltage must be within the rated range and power line should be used as the
rated wire standard by each model.
Failure to follow this instruction may result in electric shock, or re.
5. Check the connection before supplying the power.
Failure to follow this instruction may result in electric shock, re, or product damage.
6. Use the unit within the rated specications.
Failure to follow this instruction may result in re, product damage.
7. Do not insert ngers or other objects into the open part.
Failure to follow this instruction may result in electric shock, personal injury, or product damage.
8. Do not use the unit outdoors or where ammable or explosive gas, water, vibration or impact
may be present.
Failure to follow this instruction may result in electric shock, re or personal injury.
9. Ground the unit individually and ground cable should be over than AWG16.
Failure to follow this instruction may result in electric shock.
10. This unit must be installed on DIN rail or a device panel.
Failure to follow this instruction may result in electric shock.
Caution
1. Do not put obstacles around the unit which may obstruct ventilation.
Failure to follow this instruction may result in product damage or malfunction to peripheral devices by
heating.
2. Do not touch the unit during operation or after stopping.
Failure to follow this instruction may result in burn due to high temperature of surface.
3. Please stop this unit when mechanical trouble occurs.
Failure to follow this instruction may result in re or product damage.
4. Make sure to tighten the terminal screw bolt above 0.3N•m to 0.9N•m.
Failure to follow this instruction may result in re or product damage.
5. Do not touch the terminals during insulation resistance test or insulation dielectric strength
test.
Failure to follow this instruction may result in electric shock.
6. Do not use the unit where heavy vibration may be present.
Failure to follow this instruction may result in product damage.
7. Do not use water or oil-based detergent when cleaning the unit. Use dry cloth to clean the
unit.
Failure to follow this instruction may result in electric shock or re.
8. When disposing the unit, please categorize it as industrial waste.
9. Do not use the unit outdoors.
Failure to follow this instruction may result in shortening the life cycle of the unit or electric shock.
10. Keep dust and wire residue from owing into the unit.
Failure to follow this instruction may result in re or malfunction of the unit.
Ordering Information
SPB 120 24
※
The above specifications are subject to change and some models may be discontinued
without notice.
Thank you for choosing our Autonics product.
--
Output voltage
Output power
Item
5 5VDC
12 12VDC
24 24VDC
48 48VDC
015 15W
030 30W
060 60W
120 120W
240 240W
SPB Switching Mode Power Supply
Specications
Model
SPB
-015-05
SPB
-015-12
SPB
-015-24
SPB
-030-05
SPB
-030-12
SPB
-030-24
SPB
-060-12
SPB
-060-24
SPB
-060-48
SPB
-120-12
SPB
-120-24
SPB
-120-48
SPB
-240-12
SPB
-240-24
SPB
-240-48
Output power 15W 15.6W 25W 30W 31.2W 60W 62.4W 96W 120W 240W
Voltage 100-240VACᜠ (permissible voltage: 85-264VACᜠ/120-370VDCᜡ)
Frequency 50/60Hz
※
1
Efciency
(Typical)
Power factor
Current
Input condition
consumption
(Typical)
Power factor correction circuit
100VACᜠ77% 80% 83% 77% 82% 84% 81% 84% 85% 82% 85% 85% 87% 89% 89%
240VACᜠ76% 79% 82% 78% 83% 85% 83% 86% 87% 85% 88% 88% 90% 92% 92%
※
1
100VACᜠ0.35A 0.35A 0.34A 0.56A 0.63A 0.63A 1.24A 1.21A 1.19A 1.19A 1.49A 1.43A 2.76A 2.71A 2.73A
※
1
240VACᜠ0.19A 0.19A 0.19A 0.30A 0.35A 0.35A 0.66A 0.65A 0.64A
- - -
- - -
Min. 0.9 Min. 0.9
0.52A 0.61A 0.61A 1.14A 1.12A 1.13A
Built-in Built-in
Voltage 5VDCᜡ12VDCᜡ24VDCᜡ5VDCᜡ12VDCᜡ24VDCᜡ12VDCᜡ24VDCᜡ48VDCᜡ12VDCᜡ24VDCᜡ48VDCᜡ12VDCᜡ24VDCᜡ48VDC
Current 3A 1.3A 0.65A 5A 2.5A 1.3A 5A 2.5A 1.3A 8A 5A 2.5A 20A 10A 5A
Voltage adjustment range
Input variation
Load variation Max. ±1% Max. ±1% Max. ±1% Max. ±1% Max. ±1%
Ripple&Ripple noise
Start-up time
(Typical)
Output characteristics
Hold time
(Typical)
Inrush current
protection (Typical)
※
※
1
Over-current protection
Over-voltage protection
Protection
Output low-voltage indicate
※
2
※
3
※1,※
1
100VACᜠ500ms 550ms 650ms 600ms 550ms 550ms 520ms 550ms 1200ms 1200ms 1200ms 1200ms 75ms 87ms 75ms
Max. ±10% Max. ±10% Max. ±5% Max. ±5% Max. ±5%
Max. ±0.5% Max. ±0.5% Max. ±0.5% Max. ±0.5% Max. ±0.5%
4
Max. ±1.5%
Max. ±1%
Max. ±1.5%
Max. ±1% Max. ±1% Max. ±1%
Max. ±1.5%
Max. ±1%
240VACᜠ550ms 550ms 650ms 600ms 550ms 550ms 530ms 550ms 400ms 400ms 400ms 400ms 45ms 56ms 45ms
100VACᜠ24ms 25ms 25ms 20ms 15ms 15ms 15ms 14ms 15ms 98ms 75ms 87ms 33ms 36ms 25ms
240VACᜠ190ms 190ms 190ms 130ms 110ms 110ms 100ms 110ms 108ms 97ms 43ms 86ms 33ms 36ms 25ms
100VACᜠ7A 7A 7A 7A 7A 6A 13A 14A 10A 9A 11A 10A 8A 8A 8A
240VACᜠ32A 30A 31A 29A 31A 29A 19A 17A 37A 37A 36A 37A 22A 25A 26A
※
4
105 to 160% 105 to 160% 105 to 160% 105 to 160% 105 to 160%
- - -
4.2V
±10%
9.6V
±10%
20.0V
±10%
4.2V
±10%
9.6V
±10%
20.0V
±10%
9.6V
±10%
20.0V
±10%
43.0V
±10%
16.0V
±10%
9.6V
±10%
30.0V
±10%
20.0V
±10%
58.0V
±10%
43.0V
±10%
16.0V
±10%
10.0V
±10%
30.0V
±10%
20.0V
±10%
58.0V
±10%
43.0V
±10%
Indicator Output indicator: Green LED, Output low-voltage indicator: Red LED
Insulation resistance Over 100MΩ (at 500VDC megger between all input and output terminals)
Dielectric strength
Vibration 0.75mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y
Shock 300m/s
3,000VAC 50/60Hz for 1 min (between all input and output terminals)
1,500VAC 50/60Hz for 1 min (between all input terminals and F.G.)
2
(approx. 30G) in each X, Y, Z direction for 3 times
, Z direction for 2 times
EMS Conforms to EN61000-6-2
EMI Conforms to EN61000-6-4
Safety standards EN60950, EN50178
Environ-
ment
Ambient temperature
Ambient humidity 25 to 85%RH, storage: 25 to 90%RH
※
5
-10 to 50℃, storage: -25 to 65℃ (surrounding air temp.: max. 40℃)
Input cable AWG24 to 19 (material: Cu) AWG24 to 19 (material: Cu) AWG21 to 19 (material: Cu) AWG21 to 19 (material: Cu) AWG18 to 16 (material: Cu)
Terminal tightening torque 0.3 to 0.5N.m 0.3 to 0.5N.m 0.7 to 0.9N.m 0.7 to 0.9N.m 0.7 to 0.9N.m
Protection structure IP20 (IEC standard)
Approval
※
6
Weight
※
1: It is for 100% load. ※2: The output voltage adjuster (V.ADJ) should be used within voltage adjustment range.
※
3: It is for the rated input voltage 100-240VAC (85-264VAC) and 100% load. ※4: It is for the rated input voltage 100-240VAC.
※
5: Refer to '
※
Environment resistance is rated at no freezing or condensation.
Dimensions
● SPB-015 Series
● SPB-120 Series
132
Installation
● Mounting to DIN rail
Put the unit on the part
before press it to the direction ⓑ.
ⓑ
Output Derating Curve By Ambient Temperature'. ※6: The weight includes packaging. The weight in parenthesis is for unit only.
107
100
125
90
22.5 2-Ø4.2
7-M3.5
50
ⓐ of the rail
Approx. 202g (approx. 129g) Approx. 249g (approx. 176g) Approx. 347g (approx. 274g) Approx. 570g (approx. 466g) Approx. 866g (approx. 736g)
● SPB-030 Series ● SPB-060 Series
100
35.4
90
115
1102-Ø4.2
● Removing from DIN rail
Put a screw driver into the part
downward.
ⓐ
107
35.4
※
When mounting this unit
on the rail, place the unit
at least 30mm above
from the oor to remove
it easily.
90
2-Ø4.230
ⓒ before push it
35.4
90
● SPB-240 Series
132
125
80
Output Derating Curve By Ambient Temperature
]
%
[
100
7-M3.5
117
110
115
2-Ø4.2
80
Load ratio
60
50
40
5-M3.5
100
36 2-Ø4.2
110
110
(unit: mm)
35.4
20
Rail hook
ⓒ
Min. 30mm
0
-10 0 10 20 30 40 506070
Ambient temperature
[℃]
35.4
Wiring Diagram/Unit Description
SPB-015/030 Series
A
B
ᜡ
● Wiring Diagram
1. Output power [+V] terminal
2. Output power [-V] terminal
3. Input power [L] terminal
4. Input power [N] terminal
5. F.G. (Frame Ground) terminal
※
SPB-015/060 series has an output power [+V] terminal (1) and an output power [-V] terminal (2).
Over-Heating Protection
If the inner temperature of the switching element is around 140℃ by overheat, it stops switching
operation and becomes open state. Output voltage is not output.
Cautions During Use
1. Cautions for operating
This product does not have the function for parallel or series operation.
①
The output current must be used within the rated specication.
②
If over current is applied to the product, over-current protection is operating.
It causes shorten the life cycle of the product.
The output voltage must be used within the rated output specication.
③
For the product, which has the control function for over-voltage, if making the output voltage
④
adjuster (V.ADJ) to over rated voltage, the function starts to work.
This product has the function of over-heating protection.
⑤
The over-heating protection operates when the product has over-heating condition.
The product normally operates if the load is removed for over 5 minutes.
In case of the SPB-015/030/060, it does not have the harmonics suppression and power factor
⑥
improvement circuit. To improve harmonics suppression and power factor, install the additional
device.
In case of the SPB-015/030/060, it uses condenser rectication, and power factor is within 0.4
⑦
to 0.6 range. To use a cabinet panel or a electric transformer, select input power capacity of this
product as below formula.
3
4
Input apparent power[VA] =
This product is provided with a noise lter, but noise is variable according to operating conditions
⑧
such as installation environment and wiring.
When the inner fuse is damaged, replace the fuse of same specication.
⑨
2. Cautions for mounting
Mount this product on the surface of metal panel vertically for the reliability.
①
②
Mount this product at a well-ventilated place in order to increase the heat radiation efciency.
Mounting
③
When installing more than two power supplies, min. 20mm distance is required to radiate heat
effectively. Assure min. 75mm distance of the upper or the lower product and mount the products
as following gure.
3. Dielectric or insulation resistance test when this unit is installed in the control panel.
Separate the unit completely from a control panel circuit.
①
Short all terminals of the unit.
②
4. Caution for connecting the input power terminal
Connect input line (AC) to the input terminal correctly.
When you connect this to the other terminal, it may cause damage to the power supply.
5. Do not use the unit in the following environments.
Environments with high vibration or shock.
①
Environments with strong alkalis or acids.
②
Environments with exposure to direct sunlight.
③
Near machinery which produce strong magnetic force or electric noise.
④
6. This unit may be used in the following environments.
※
① Indoors
Pollution degree 2
③
Failure to follow these instructions may result in product damage.
Major Products
Photoelectric Sensors Temperature Controllers
Fiber Optic Sensors
Door Sensors SSRs/Power Controllers
Door Side Sensors Counters
Area Sensors Timers
Proximity Sensors Panel Meters
Pressure Sensors Tachometers/Pulse (Rate) Meters
Rotary Encoders Display Units
Connectors/Sockets Sensor Controllers
Switching Mode Power Supplies
Control Switches/Lamps/Buzzers
I/O Terminal Blocks & Cables
Stepper Motors/Drivers/Motion Controllers
Graphic/Logic Panels
Field Network Devices
Laser Marking System (Fiber, Co₂, Nd:YAG)
Laser Welding/Cutting System
Temperature/Humidity Transducers
21
C
5
Air ow
Air ow
② Max.
Installation category II
④
SPB-060/120/240 Series
1
A
B
3
2
C
5
4
● Unit Description
A. Output (DC ON) indicator (Green)
B. Output low-voltage (DC LOW) indicator (Red)
C. Output voltage adjuster (V.ADJ)
Output active power[W]
Power factor × Efciency
Min. 75mm
Min. 20mm
Min. 75mm
altitude: 2,000m
http://www.autonics.com
HEADQUARTERS:
18, Bansong-ro 513beon-gil, Haeundae-gu, Busan, South
Korea, 48002
TEL: 82-51-519-3232
E-mail: sales@autonics.com