![](/html/0c/0c37/0c37e42566b356e0e7b3ee287c9491689cd396c3a2327c8d12584a95b23d8e54/bg1.png)
KRN100
Series
Features
•
•
Combined•functions•of•paper•recorder•and•paperless•
recorder
•
•
•Enables•to•print•the•saved•data•of•inner•memory•
when•running•out•of•recording•paper•
(data•logger•function)•
•
•
Enables•to•set•parameters•with•USB,•RS485,•Ethernet•
communication
•
•
•High•legibility•and•setting•convenient•by•graph•LCD•
•
•
•High•speed•sampling•of•25ms,•high•speed•record•of•
240mm/H•functions•
•
•
•100mm•paper•record•(selectable•6•kinds•of•record•
color)•
•
•
Supports•inner•memory•and•USB•memory•data•
backup•(storage)
•
•
Supports•several•input•up•to•12•channels•with•slot•
type•input•cards
•
•
Enables•to•select•several•option•cards•with•slot•type•
output•cards
•
•
•Space•saving•for•installation•with•compact•design•
(rear•length:•168mm)
•
•
•Supports•total•27•kinds•of•input•types
•
•
Enables•to•order•several•type•input•cards•(weight,•
voltage,•current,•frequency,•potential•meter,•etc)•
Please read “Caution for your safety” in operation manual
before using this unit.
Manual
••For•more•information•and•instructions,•refer•to•the•user•manual•and•the•user•manual•for•communication.•
Visit•our•web•site•(www.autonics.com)•to•download•the•manuals.
••The•user•manual•includes•product•specications,•functions,•and•operations.
••The•user•manual•for•communication•includes•information•about•Modbus•RTU•protocol,•Modbus•TCP•protocol,•and•Modbus•
mapping•table.•
Integrated device management program(DAQMaster)
••DAQMaster•is•the•integrated•device•management•program•to•set•parameters•and•manage•monitoring•data.
••Visit•our•website•(www.autonics.com)•to•download•user•manual•and•integrated•device•management•program.
<•DAQMaster•screen•><•Computer•specication•for•using•software•>
Item Minimum•requirements
System
Operating•system Microsoft•Windows•98/NT/XP/Vista/7
Memory 256MB•or•more
Hard•disk More•than•1GB•of•free•hard•disk•space
VGA 1024×768•or•higher•resolution•display
Others RS-232•serial•port(9-pin),•USB•port
IBM•PC•compatible•computer•with•Intel•Pentium•
•or•above
Ⅲ
A-2
![](/html/0c/0c37/0c37e42566b356e0e7b3ee287c9491689cd396c3a2327c8d12584a95b23d8e54/bg2.png)
100mm Hybrid Recorder
Ordering information
Ordering information for recorder model
KRN100 12 0 0 0 0 0 0 S
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨
Item Description
①•Item
②•Input•channel
③•Digital•input
④•Alarm•transistor•output
⑤•Alarm•relay•output
⑥•Transmitter•power•output
⑦•Communication•output
⑧•Power•voltage
⑨•Case
KRN100 New•100mm•Paper•Type•Recorder
02 2-channel(KRN-UI2×1EA)
04 4-channel(KRN-UI2×2EA)
06 6-channel(KRN-UI2×3EA)
08 8-channel(KRN-UI2×4EA)
10 10-channel(KRN-UI2×5EA)
12 12-channel(KRN-UI2×6EA)
0 None
1 6EA(KRN-DI6×1EA)
2 12EA(KRN-DI6×2EA)
0 None
1 6EA(KRN-AT6×1EA)
2 12EA(KRN-AT6×2EA)
0 None
1 4EA(KRN-AR4×1EA)
2 8EA(KRN-AR4×2EA)
3 12EA(KRN-AR4×3EA)
0 None
1 3EA(KRN-24V3×1EA)
2 6EA(KRN-24V3×2EA)
3 9EA(KRN-24V3×3EA)
4 12EA(KRN-24V3×4EA)
0 None
1 RS485/Ethernet/USB(KRN-COM×1EA)
0 100-240VAC,•50/60Hz
S Standard•panel•mounting•type
A. Recorder
B.•Indicator
C.•Converter
D.•Controller
E.•Thyristor•
•••••unit
F.•Pressure•
••••transmitter
G.•Temp.•
•••••transmitter
H.•Accessories
KRN100
KRN50
Ordering information for input/output card
Type Model Function•and•number•of•channels Max.•mountable•cards Slot•number
Universal•input•card KRN-UI2 Universal•input•2-channel 6EA 1•to•6
Digital•input•card KRN-DI6 Digital•input•6-channel• 2EA
Alarm•output•card
Transmitter•power•output•card
Communication•output•card• KRN-COM
※
•1.•The•digital•input•card,•alarm•output•card,•transmitter•power•output•card•are•connectable•up•to•4EA•as•mixed.
KRN-AR4 Alarm•relay•output•4-channel• 3EA
KRN-AT6 Alarm•transistor•output•6-channel 2EA
KRN-24V3
Transmitter
24VDC•power•output•3-channel
RS485•+•USB•+•Ethernet•communication•
output
4EA
1EA C
7•to•10
※
1
Example of ordering
To•use•universal•input•10-channel,•digital•input•4-channel,•alarm•relay•output•5-channel,•and•RS485•communication•output,•it•is•
ordered•as•KRN100-10102-01-0S•and•the•connected•I/O•card•is•as•below.•
•••KRN100(recorder):•1EA
•••KRN-UI2(universal•input•card):•5EA•(universal•input•card•1EA•is•2-channel•and•5EA×2-channel•=•10-channel.)
•••KRN-DI6(digital•input•card):•1EA
•••KRN-AR4(alarm•relay•output•card):•2EA
•••KRN-COM(Communication•output•card):•1EA
A-3
![](/html/0c/0c37/0c37e42566b356e0e7b3ee287c9491689cd396c3a2327c8d12584a95b23d8e54/bg3.png)
KRN100
Series
Connections
Rear side of KRN100 standard model
This•gure•is•the•rear•side•of•KRN100-04000-00-0S.
SOURCE
100-240VAC
50/60Hz,•55VA
Slot Description
1•to•6 Connects•universal•input•card(KRN-UI2).•
7•to•10
C Connects•communication•output•card(KRN-COM).
Connects•digital•input•card(KRN-DI6),•alarm•output•card(KRNAR4,•KRN-AT6),•transmitter•power•output•card(KRN-24V3).•
I/O card
Universal input card [KRN-UI2] Digital input card [KRN-DI6]
UI2
-
+
-
+
※
Each•channel•is•isolated•and•dielectric•strength•is•500V.
Alarm output card [KRN-AR4(relay output)] Alarm output card [KRN-AT6(transistor output)]
Inner Inner
AR4
250VAC•3A•1a
DI6
AT6
A-4
※
AL1,2,3•and•AL4,5,6••are•isolated.
Transmitter power output card [KRN-24V3] Communication output card [KRN-COM]
24V3
24VDC•30mA
24VDC•30mA
24VDC•30mA
※
24V•output•of•3EA•is•isolated•individually.
COM
![](/html/0c/0c37/0c37e42566b356e0e7b3ee287c9491689cd396c3a2327c8d12584a95b23d8e54/bg4.png)
100mm Hybrid Recorder
Specications
Series
Power•voltage 100-240VAC•50/60Hz
Allowable•voltage•range 85•to•110%•of•rated•voltage
Power•consumption Max.•55VA
LCD•type STN•Graphic•LCD
Screen
Resolution 320×120Pixel
Adjusting•brightness 4-level(OFF/Min/Standard/Max)
Backlight White•LED,•2-level(Temp/Always)
Input•channels 2•/•4•/•6•/•8•/•10•/•12-channel(2-channel/card)-Expandable
Universal•input
※1
Sampling•cycle
Recording•period•in•graph•mode
Recording•speed•accuracy F.S.•±0.5%
Storage•cycle 1•to•3600sec.•(storage•interval•time•to•inner•log•le•is•1•sec.)•
Inner•memory 512MB
USB•memory User•purchased,•recognizes•max.•32GB,•enables•to•use•cable•up•to•1.5m
Dielectric•voltage
Vibration•strength•
(for•convey•and•storage)•and•
operating•vibration•
Insulated•resistance Min.•20MΩ(at•500VDC•megger)
Noise ±2kV•the•square•wave•noise•(pulse•width•1㎲)•by•the•noise•simulator••
Time•accuracy Within•±2min./year•(enables•to•use•up•to•2100•year)
Mechanism
Ink•cartridge Enables•to•normal•print•with•going•and•returning•printing•max.•5•times•within•7•days•after•opening•the•unit•
Ink•dry•time Max.•15•minutes
Protection IP40(for•front•panel)
Recording•paper 113mm×9m
Environment
Ambient•temperature
Ambient•humidity 35•to•85%•RH,•storage•:•35•to•85%•RH
Approval
Unit•weight Approx.•1.7•to•2.0kg•
※
•1.•For•more•information•of•universal•input,•please•refer•to•「I/O•card」of•the•A-6•page.
※
•2.•When•using•this•unit•in•high•humidity,•it•may•cause•paper•jam.•Please•do•not•use•this•unit•in•high•humidity.•
※
•Environment•resistance•is•rated•at•no•freezing•or•condensation.
KRN100
Temperature•sensor(RTD,•thermocouple),•analog
1•to•4-channel•:•25ms/125ms/250ms,•5•to•12-channel•:•125ms/250ms
(inner•sampling•cycle•is•operation•unit•time•for•average•movement•lter•and•alarm•output•function.)
※Max.•sampling•cycle•for•TC-R,•U,•S,•T•sensor•is•50ms.
10,•20,•40,•60,•120,•240mm/H
250VAC•50/60Hz•for•1min.•(power•terminal•and•case)•
※•Excepts•USB•Device•and•Ethernet
Vibration•strength•:•10•to•60Hz•4.9m/s2•(each•of•X,•Y,•Z•axes•for•1•hour)•
Operating•vibration•:•10•to•60Hz•1m/s2•(each•of•X,•Y,•Z•axes•for•10•min.)•
0•to•50℃,•storage•:•-20•to•60℃•(without•ink•cartridge)
•
A. Recorder
B.•Indicator
C.•Converter
D.•Controller
E.•Thyristor•
•••••unit
F.•Pressure•
••••transmitter
G.•Temp.•
•••••transmitter
H.•Accessories
KRN100
KRN50
Dimensions
144
● Panel cut-out
18.6
Min.175
+1.0•
••0
138
Min.175•
138
+1.0•
••0
※
168
137
※
•This•rear•side•dimension•is•with•
installed•I/O•cards•to•every•slot.
•Use•a•steel•plate•which•is•2•to•8mm•thickness.
137
(unit:•mm)
A-5
![](/html/0c/0c37/0c37e42566b356e0e7b3ee287c9491689cd396c3a2327c8d12584a95b23d8e54/bg5.png)
KRN100
Series
I/O card
Type Model I/O•specications Descriptions
RTD JPt100Ω,•DPt100Ω,•DPt50Ω,•Cu100Ω,Cu50Ω(supply•current••420㎂)
Thermocouple B,•C(W5),•E,•G,•J,•K,•L,•L(Russia),•N,•P,•R,•S,•T,•U
※
1
Analog
RTD
Thermocouple
※
2
Analog
Capacity 250VAC,•3A,•30VDC•3A,•1•Form•A•(resistance•load)
Life
RS485
EtherNet IEEE802.3(U),•10/100•BASE-T(Modbus•TCP)
※
USB•Device
4
Universal•input•
card
Digital•input•card• KRN-DI6•
Alarm•output•card
Transmitter•power•
output•card
Communication•
output•card
KRN-UI2
KRN-AR4•
KRN-AT6 Alarm•transistor•output NPN•Open•Collector,•12-24VDC/30mA•Max.
KRN-24V3• Transmitter•power•output
KRN-COM Com.•output
※
3
Input•type
Input•impedance
Display•
accuracy
Resolution 16Bit
Non-contact•input ON:•Max.•1V•of•residual•voltage,•OFF:•Max.•0.1mA•of•leakage•current
Contact•input ON:•Max.•1kΩ,•OFF:•Min.•100kΩ,•Outow•current•for•short:•Approx.•4mA
Alarm
relay
output
Voltage:•±60mV•±200mV•±2V,•1-5V,•±5V,•-1V-10V
Current:•0.00-20.00mA,•4.00-20.00mA
Voltage(V):•Min.•150kΩ
RTD,•Thermocouple,•Voltage(mV):•Min.•2MΩ
Current:•51Ω
Warm-up•time:•Min.•30•min.
Room•temperature•(25℃±5℃):•±0.1%F.S•±1digit
Out•of•room•temperature•range:•±0.2%F.S•±1digit
For•RTD,•500•to•800℃•is•±0.5%±1digit•of•PV•value,•
For•Thermocouple,•below•-100℃•is•±0.3%F.S.±1digit.
Mechanical:•Min.•50,000,000•operations
Electrical:•Min.•100,000•operations•(3A•250VAC,•3A•30VDC)
24±2VDC,•,•total•3-channel,•max.•30mA•per•1-channel
built-in•over-current•protection•circuit
Modbus•RTU
※
Recommended•to•use•shield•cable•over•AWG24
USB•V2.0•Full•Speed(Device•Control)
※
1.To•change•input•specication,•you•must•turn•OFF•the•power•of•KRN100,•remove•universal•input•cards,•set•inner•jumper•pins•(please•
refer•to•‘ I/O•card’•of•the•A-4•page)•and•re-connect•it.•
※
•2.•Exception•range•for•measuring•accuracy•by•each•sensor(accuracy•after•30min•warm-up•time)••
••••••••· R,S,C,G:•0≤T≤100±4.0℃,•
••••••••· B:•No•regulation•accuracy•below•400℃
••••••••· U,T:-200≤T≤-100±3.0℃,•-100≤T≤400±2.0℃,•
••••••••· Cu50:•-200≤T≤200±1.0℃•
••••••••· DPt50:•-200≤T≤600±1.5℃
※
•3.•RS485,•Ethernet•communication•output•are•not•available•at•the•same•time.•••
※
•4.The•front•USB•device•is•only•for•data•backup•and•rear•USB•device•is•available•only•for•parameter•setting.
※
•It•is•recommended•to•use•shield•cable•to•decrease•noise•when•sensor•input•cable•is•longer.
※
If connecting or disconnecting input/output card when power is ON, it may cause malfunction.
To connect or disconnect input/output card, you must turn OFF the power.
A-6