Bar Graph Digital Indicator
KN-1000B SERIES
M A N U A L
Thank you very much for selecting Autonics products.
For your safety, please read the following before using.
Caution for your safety
Please keep these instructions and review them before using this unit.
※
※
Please observe the cautions that follow;
Warning
Caution
※
The following is an explanation of the symbols used in the operation manual.
Caution: Injury or danger may occur under special conditions.
Warning
1. In case of using this unit with machinery(Ex: nuclear power control, medical
equipment, ship, vehicle, train, airplane, combustion apparatus, safety
device, crime/disaster prevention equipment, etc) which may cause damages
to human life or property, it is required to install fail-safe device.
It may cause a re, human injury or damage to property.
2. Install this unit on a panel.
It may cause electric shock.
3. Do not connect, repair, or inspect this unit when power is ON.
It may cause electric shock.
4. Do not disassemble the case. Please contact us if it is required.
It may cause electric shock or a re.
5. Wire properly after checking terminal numbers.
It may cause a re.
Caution
1. This unit shall not be used outdoors.
It might shorten the life cycle of the product or cause electric shock.
2. Please observe the rated specications.
It might shorten the life cycle of the product or cause a re.
3. In cleaning this unit, do not use water or organic solvent. And use dry cloth.
It may cause electric shock or a re.
4. Do not use this unit where there are ammable or explosive gas, humidity,
direct ray of the sun, radiant heat, vibration and impact etc.
It may cause a re or explosion.
5. Do not inow dust or wire dregs into the unit.
It may cause a re or malfunction.
6. Wire it properly after checking terminal numbers when connecting power
cable and measuring input.
It may cause a re or explosion.
Ordering information
Part descriptions
8
7
6
The above specifications are subject to change without notice.
Serious injury may result if instructions are not followed.
Product may be damaged, or injury may result if instructions are not followed.
1KN 0 0 0 B
Size
B DIN W36×H144 mm
Power supply
Option output
Alarm output
Display part(red)
1.
●Run mode: Displays current measurement value.
1
●Parameter set mode: Displays parameter and SV.
2
Unit sticker part (unit sticker is an accessory)
2.
3
Alarm output indicator : Turns ON when the alarm is ON.
3.
M key: Used to e nter para meter set m ode, move to paramet ers, save
4.
4
5
SV and return to RUN mode.
key : Used to enter and change parameter SV.
5. 1, 3, 4
D.IN3 : Press the 3 and 4 keys for 3 sec. at the same time, it operates
6.
the set function (alarm clear, display hold, zero-point adjustment)
at
7. Bar Graph(with 101 bar LEDs, green)
: Displays measured value as bar graph.
8. Space for recognizing device by user
DI-K
0 100-240 VAC 50 to 60 Hz
1 24 VDC
0 No option
1 Transmission output (4-20 mA)
4 RS485 communication output
0 No alarm output
2 2EA alarm output
4 4EA alarm output
Item
KN-1 Bar Graph Indicator
at program mode.
Connections
● KN-10□□B
Dimensions
144
156
16
36
ANALOG
10
80
Input
2-wire
transmitter
DC output
Selecting
input S/W
Digital
Input
Relay output
SOURCE
max. 87.7
b
ANALOG
b
-1~+10V
● KN-12□□B
● KN-14□□B
Selecting
input S/W
139
32
Input type and range
Input type selection switch
٧
● 0-20 mA : Select it for 0(4)-20 mA input
● 1-10 V : Select it for 1 V-10 V input
● RTD/TC/mV/±1V : Select it for RTD, TC temperature
sensor or ±1V, mV input
This unit is multi input product. Select the proper input with the input type
selection switch and select this input type in IN-P in program mode.
The setting of input type selection switch and the input type IN-P parameter
should be same and it can display the proper measurement value.
Factory default is 0-20 mA.
Input type Parameter Input range(℃) Input range(℉)
K(CA)
K(CA)
J(IC)
E(CR)
T(CC)
B(PR)*
Thermo
R(PR)
couple
S(PR)*
N(NN)*
C(W5)*
L(IC)*
U(CC)*
Platinel II*
Cu50Ω*
Cu100Ω*
RTD
JPt100Ω
DPt50Ω
DPt100Ω
Current
Analog
Voltage
0.00 - 20.00 mA
4.00 - 20.00 mA
50.0 - 50.0 mV
199.9 - 200.0 mV
1.000 - 1.000 V
1.00 - 10.00 V
※Above input types which have the * mark are not displayed.
To display the above input types, supply the power with pressing the M key.
TcK1
TcK2
TC-J
TC-E
TC-T
TC-B
TC-R
TC-S
TC-N
TC-C
TC-L
TC-U
TC-P
Cu50
Cu10
JPt1
DPt5
DPt1
aMA1
aMA2
aMV1
aMV2
A-V1
A-V2
200 to 1350 328 to 2462
199.9 to 999.9 328 to 1832
199.9 to 800.0 328 to 1472
199.9 to 800.0 328 to 1472
199.9 to 400.0 199.9 to 752.0
100 to 1800 212 to 3272
0 to 1750 32 to 3182
0 to 1750 32 to 3182
200 to 1300 328 to 2372
0 to 2300 32 to 4172
199.9 to 900.0 328 to 1652
199.9 to 400.0 199.9 to 752.0
0 to 1390 32 to 2534
199.9 to 200.0 199.9 to 392.0
199.9 to 200.0 199.9 to 392.0
199.9 to 600.0 328 to 1112
199.9 to 600.0 328 to 1112
199.9 to 850.0 328 to 1530
1999 to 9999
(Display range is variable
according to decimal point position. )
(unit: mm)
● Panel cut-out
+0.6
+0.6
33
-0
Specication
Series KN-1000B
Power
supply
AC voltage 100-240 VAC 50 to 60 Hz
DC voltage 24 VDC
Allowable voltage range 90 to 110% of rated voltage
Power
consumption
AC voltage Max. 6 VA
DC voltage Max. 4 W
Display method 4digit : 7Segment LED Display (red), Bar LED : 101EA (green)
RTD JPt100Ω, DPt100Ω, DPt50Ω, Cu50Ω, Cu100Ω (5 types)
Input
type
Digital input
Sub
output
Thermocouple
Analog
Alarm output
Trans. output
K, J, E, T, R, B, S, N, C (W5), L, U, PLII (12 types)
●Voltage : ±1.000 V, ±50.00 mV, -199.9-200.0 mV,
1.00 V-10.00 V (4 types)
●Current : 4.00-20.00 mA, 0.00-20.00 mA (2 types)
●Contact input : Max. 2 kΩ in ON,Max. 90 kΩ in OFF
●Non-contact input : Residual voltage max. 1.0 V in ON,
Leakage current max. 0.03 mA in OFF
●Outow current : Approx. 0.2mA
2-point : Relay contact capacity 250 VAC 3 A 1c,
4-point : Relay contact capacity 250 VAC 1 A 1a
ISOLATED DC 4-20 mA(PV transmission) load resistance
max. 600 Ω (accuracy: ±0.2%F.S., resolution: 8000)
Com. output RS485 (Modbus RTU)
±0.2% F.S. ±1digit (25 ℃±5 ℃)
Display accuracy
±0.3% F.S. ±1digit ( 10 ℃ to 20 ℃, 30 ℃ to 50 ℃)
In case of thermocouple and below -100 °C input,
[±0.4%F.S.]±1digit
※TC-T, TC-U is min. ±2.0 ℃
Setting method Set by front keys, or RS485 communication
Alarm output hysteresis Set ON/OFF interval (1 to 999 digit)
Sampling cycle Analog input : 100 ms, Temperature sensor input : 250 ms
Dielectric voltage
Vibration
Relay
life cycle
-0
140
Insulation resistance Min. 100 MΩ (at 500VDC megger)
2-point
4-point
2000 VAC 50/60 Hz for 1 min.
(between input terminal and power terminal)
0.75 mm amplitude at frequency of 5 to 55 Hz (for 1 min.)
in each of X, Y, Z directions for 2 hours
Mechanical: Min. 10,000,000, Electrical: Min. 100,000
(250 VAC 3 A resistance load)
Mechanical: Min. 20,000,000, Electrical: Min. 500,000
(250 VAC 1 A resistance load)
Noise resistance Square shaped noise by noise simulator (pulse width 1 ㎲) ±2 kV
Memory retention Approx. 10 years (non-volatile semiconductor memory type)
Environ
-ment
Ambient
temperature
Ambient
humidity
10 to 50 ℃, storage: 20 to 60 ℃
35 to 85%RH, storage: 35 to 85%RH
Approval
Unit weight Approx. 200 g
※
Environment resistance is rated at no freezing or condensation.
Factory default
■ Monitoring mode
Parameter Default Parameter Default Parameter Default
AL1 09(9 AL3 00)1 hPEK ---AL2 09(9 AL4 00)1 lPEK ----
■ Program mode
Parameter
Default
Parameter Default Parameter Default Parameter Default
IN-P AMa1 IN-B 0000 AL-1 AT!A DI-T HOLD
UNIT ?C L-BS 00)0 AL-2 AT!A DI-K HOLD
L-RG 0)00 H-BS 10)0 AL-3 AT@A BURN OFF
H-RG 2)00 BAR fBAR AL-4 AT@A ADDR 01
dP )0 lOUT 00)0 A-HY 001 BAUD 9600
L-SC 00)0 hOUT 10)0 InSF LIN LOCK OFF
H-SC 10)0 E .10 SP MAuF 04
Monitoring mode
Alarm 1
value
Alarm 2
value
Alarm 3
value
Alarm 4
value
High peak
value
Low peak
value
RUN mode
M
Press key.
※
AL1 09(9
M M
AL2 09(9
M
AL3 00)1
M
AL4 00)1
M
hPEK ----
M
lPEK ----
M
※1. S :Press any key among the 1, 3, 4.
※2. 1 : Moves digits / 4, 3: Changes SV.
※3. Press the M key after checking/changing SV in each parameter.
The value ashes twice and is saved. It moves to next parameter.
※After entering setting group, press the M key for 3 sec. or there is no
additional key operation in 30 sec., it returns to RUN mode.
※ : This parameter may or may not appear, depending on the other
parameter set or model type.
1
※
2
S
※
3
Set each alarm value; [
S
S
S
S
S
• Set range: Temp. sensor input → within temperature range
Analog input → L-SC to H-SC
※
When alarm operation [
no alarm [
parameters are not displayed.
※
For 2EA alarm output model(KN-12 B),
displayed.
Displays high/low peak value.
※
High/Low peak value is available only to check and initialize it.
(Refer to ‘■High/Low peak monitoring’ for initialization.)
※
Initial high/low peak is saved after 2 sec. from supplying the
power.
※Displayed only for alarm output models.
to
AL-1
AL-
to
AL-1
] or sensor break alarm [
AT)_
4] in program mode.
AL-
4] in program mode is
], these
SBa_
AL3, AL4 are not
Program mode
RUN mode
Press M key
for 3 sec.
Input type
Temperature
Low limit
input value
High limit
input value
Decimal
Low limit
scale value
High limit
scale value
correction
Bar graph
low limit
scale value
Bar graph
high limit
scale value
Bar graph
display
method
4 mA output
scale value
20 mA output
scale value
Input and
trans. output
extension
AL1 mode
AL2 mode
AL3 mode
AL4 mode
AL output
hysteresis
Input
special
function
Digital
Digital input
terminal
Digital
input key
Sensor
break alarm
output
Com.
address
Com.
speed
unit
point
Input
lter
Lock
IN-P
M
UNIT ?C
M
L-RG 0$00
M
H-RG 2)00
M
dP
M
L-SC 00)0
M
H-SC 100.0
M
IN-B 0000
M
L-BS
M
H-BS 00)0
M
BAR
M
lOUT 00)0
M
hOUT 10)0
M
EX.I0
M
AL-1 AT!A
M
AL-2 AT!A
M
AL-3 AT@A
M
AL-4 AT@A
M
A-HY 001
M
InSF
M
MAvF 04
M
DI-T HOLD
M
DI-K HOLD
M
BURN ON
M
ADDR 01
M
BAUD (6K
M
LOCK OFF
M
※1. S :Press any key among the 1, 3, 4.
※2. 1 : Moves digits / 4, 3: Changes SV.
※3. Press the M key after checking/changing SV in each parameter.
The value ashes twice and is saved. It moves to next parameter.
※After entering setting group, press the M key for 3 sec. or there is no
additional key operation in 30 sec., it returns to RUN mode.
※ : This parameter may or may not appear, depending on the other
parameter set or model type.
※1
※2
S
aMA2
S
S
S
S
S
S
S
S
00)0
S
S
fBAR cBAR
S
S
S
S
S
S
S
S
S
LIN ROOT SQAR TUF
S
S
S
S
S
S
S
Select input type. (Refer to Input type and range.)
MODE
※3
※
Displayed only when selecting temperature sensor input type.
3
?F
4
※
•Set low limit of input range.
•Set range : within analog input type range
•Set high limit of input range.
•Set range : within analog input type range
3
)0
4
Select decimal point position of display scale value.
Set low limit scale value.
• Set range : -1999 to 9999
Set high limit scale value.
• Set range : -1999 to 9999
Set input correction value.
• Set range : -999 to 999
Set low lim it scale va lue for ba r graph dis play.
• Set range : Temp. sensor input
→ within temp. range (low limit) ≤ L-BS ≤ (H-BS-1)
Analog input → L-SC ≤ L-BS ≤ (H-SC-1)
Set high li mit scal e value for b ar graph di splay.
• Set range : Temp. sensor input → (L-BS+1) ≤ H-BS ≤
within temp. range (high limit)
Analog input → (L미미-SC+1) ≤ H-BS ≤ H-SC
3
4
Set output scale value for 4 mA.
• Set range : Temp. sensor input → within temp. range,
Analog input → L-SC to H-SC
Set output scale value for 20 mA.
• Set range: Temp. sensor input → within temp. range,
Analog input → L-SC to H-SC
3
5P 10P 0P
4
Select extension range of 4-20 mA input and transmission output.
Set AL1 to
AL4 alarm
operation
and option.
※SV changing method of
※For 2EA alarm output model (KN-12 B),
※
No alarm [
※
AT)_
Set alarm value [
Set alarm output hysteresis. • Set range : 001 to 999
※
When alarm operation [ AL-1 to AL-4] in program mode is no
alarm [ AT)_] or sensor break alarm [ SBa_], this parameter is
not displayed.
3
4
Select input special function.
Set the number of moving average digital lters.
• Set range : 01 to 16
3
4
Select digital input function by no. 12 and 13.
※
For the model without alarm output (KN-10 B), AlRE is not displayed.
3
4
Select digital input function by front keys.
※Press the 4, 3 keys for 3 sec. at the same time and
it executes the selected function.
※For the model without alarm output (KN-12 B), AlREis not displayed.
3
4
Set communication address.
• Set range : 01 to 99
3
4
Select communication speed (baud rate).
3
4
Select lock function.
Displayed only when selecting analog input type.
3
)00 0)000
4
Set display method for bar graph.
※Displayed only for transmission output model.
※Displayed only when selecting analog input type.
3
4
※Displayed only for alarm output models.
S
AL-1
M
M
AL-2
M
AL-3
M
AL-4
M
Next para meter
to
AL-2
], sensor break alarm [
to
] in monitoring mode.
AL1
AL4
※
Displayed only when selecting analog input type.
3
4
3
ZERO
4
3
ZERO
4
※Displayed only for alarm, transmission output models.
Select output status when sensor disconnection.
OFF
※Displayed only for RS485 communication output model.
1(2K
3
LOC1
4
3
4
<Alar m operat ion> <Alarm opt ion>
AT!A
AT@A
SBa_
AT)_
is same as
AL-4
AL3, AL4 are not displayed.
] do not have alarm option.
SBa_
3
4
AlRE
AlRE
3 33
4 44
LOC2
AT!A
AT!B
AT!C
AT!D
’s.
AL-1
@4K $8K!2K

Functions
■
Alarm [ AL-1, AL-2, AL-3, AL-4]
This product has 2 or 4 alarms to operate individually when
the value is too high or low. Alarm function is set by the
combination of alarm operation and alarm option.
AT !A
Alarm option
Alarm operation
To clear alarm, use digital input function (setting 미DI-T, DI-K
as AlRE) or turn the power OFF and ON.
※
For the model (KN-10 B) without alarm output, these parameters are not displayed.
Alarm operation
٧
Mode Name Operation Descriptions
ㅡ ㅡ
AT)_
High limit alarm
AT!
Low limit alarm
AT@
OFF
High limt alarm
value: 800
℃
ON
H
Low limt alarm
PV
value:200
OFF
No alarm operation
ON
H
PV ≥ alarm temperature,
alarm is ON
PV
PV ≤ alarm temperature,
alarm is ON
℃
It will be ON when it detects
Sensor break alarm
SBa_
ㅡ
sensor disconnection.
Sensor break alarm does not
have alarm option.
※
H : Alarm output hysteresis
Alarm option
٧
Option Name Descriptions
AT .A
AT .B
Standard
alarm
Alarm latch
If it is an alarm condition, alarm output is ON. Unless an alarm
condition, alarm output is OFF.
If it is an alarm condition, alarm output is ON. Before clearing the
alarm, an ON condition is latched. (Holding the alarm output)
First alarm condition is ignored. From the second alarm
AT .C
Standby
sequence
condition, standard alarm operates.
When power is ON and it is an alarm condition, it is ignored.
From the second alarm condition, standard alarm operates.
Alarm
latch and
AT .D
standby
sequence
■
Alarm output hysteresis [Program mode: ㅁA-HY]
If it is an alarm condition, it operates both alarm latch and
standby sequence.
When power is ON and it is an alarm condition, it is ignored.
From the second alarm condition, alarm latch operates.
Set the interval of ON/OFF alarm output.
The set hysteresis is applied to AL1 to AL4 and it is as below.
※
Ex)
: 4, high limit alarm value: 800, low limit alarm value: 200
A-HY
High limit
alarm value
800
800
■
High/Low peak monitoring [Monitoring mode: H.PEK, L.PEK]
ON
796
OFF
A-HY
:4
Low limit
alarm value
200
200
ON
204
OFF
A-HY
This function is to save high/low peak to check the invisible abnormal condition of
system at [h PEK ] or [l P E K] in monitoring mode.
When the high/low peak is out of the temperature range, it displays HHHH or LLLL.
To initialize high/low peak, press the 3, 4keys at the same time for 3 sec. at [h P EK ]
or [l P EK ]. In this case, peak value is the present input value.
■
Error
Display Descriptions Troubleshooting
Flashes when measured sensor input
LLLL
is lower than the temperature range.
Flashes when measured sensor input is
HHHH
higher than the temperature range
Flashes when the sensor is break or
BURN
not connected.
ERR
Flashes when there is error to SV Check set conditions and re-set it.
■
Parameter initialization
To initialize all parameter as factory default,
supply the power to the product with
pressing the M and 1 keys at the same
time and it enters initialization parameter.
■
Decimal point [Program mode: d P]
When input is moved within the
temperature range, it is cleared.
Check temperature sensor
connection.
Press the +1 keys
at the same time.
Supply the power.
CLR
M
NO
Completes initialization.
YES
M
It is able to change decimal point position for high/low limit scale value.
It changes decimal point position of display value.
■
Transmission output scale [Program mode : lOUT, hOUT]
For 4-20 mA current output, this function is to set the display value for 4 mA [ l O U T]
and the display value for 20 mA [h O U T].
The inter val between lOUTand hOUTis 10% F.S. If it is below 10%, it is xed as 10%
of SV.
Output
20mA
4mA
lOUT
hOUT
Display
Output
20mA
4mA
lOUT
hOUT
Display
■
User input range [Program mode: L-RG, H-RG]
When selecting analog input, you can set the input range for your purpose. Set low limit
input value [ L-RG] and high limit input value [ H - RG] to limit the input range.
•Set conditions : Low limit input value [ L-RG] +20%F.S. < High limit input value [ H-RG]
■
Display scale [Program mode: L-SC, H-SC]
For analog input, this function is to set (-1999 to 9999) for particular high/low limit value
in order to display high/low limit value of measurement input. If measurement inputs are ‘a’
and ‘b’ and particular values are ‘A’ and ‘B’, it will display a=A, b=B as below graphs.
Display
value
Display
value
Input
value
B
A
B
A
a b
a b
Display
value
Input
value
Display
value
b
Input
value
B
A
B
A
a b
Display
value
Input
value
Display
value
a b
A
B
Input
value
Display scale function is able to change display value for max./min. measured input by
setting high limit scale [H-SC] and low limit scale [L-SC] in program mode.
※
Ex) Set high/low scale value (input range is 0 to 10V)
• L-SC= )00
• H-SC= %00, 1)00, 1%00
`)00
Display
value
1%00
1)00
%00
0
`)00
※
When changing input type, high/low scale is changed as factory default.
10V
Input
value
• L-SC=1)00
,
H-SC= `)00
Display
value
1%00
1)00
`)00
,
0
10V
Input
value
• L-SC=-%00
H-SC= %00
Display
value
1%00
1)00
%00
0
-%00
■ Input correction [Program mode: IN-B]
This function is to correct the error occurring from a thermocouple, a RTD or analog input
out of allowable error range of this unit.
This is also available to correct error when a sensor cannot contact the subject position
by calculating the error temperature.
Variable temperature sensors have accuracy level. Because high accuracy type is
expansive, standard thermocouples are generally used.
In this case, temperature sensor may occur error. By executing this function, you can get
more accurate temperature.
When executing input correction function, you should measure the error from a sensor
accurately. If the measured error is not correct, error may be greater.
(If InSF= TUF, IN-B as atmospheric pressure input value not as input correction
function. Refer to Two unit function.)
Ex)When measured temperature is 4 ℃ and actual temperature is 0 ℃. Set IN-B as
:4
-4, and and display value is 0 ℃.
■
Bar graph scale [Program mode: L-BS, H-BS]
This is to set display range for bar graph.Display range is as below.
Parameter Input Display range
L-BS
Temp. sensor input
Input range
(low limit)
Analog input
Temp. sensor input (L-BS+1) ≤
H-BS
Analog input (L-SC+1) ≤
Relation among input range, user input range, display scale, bar graph scale, and
※
L-SC
≤
L-BS
≤
L-BS
H-BS
H-BS
≤ (H-BS-1)
≤ (H-SC-1)
Input range
≤
(high limit)
H-SC
≤
transmission scale.
The below gure is the example for 4 to 20 mA.
Input range
User
input range
Display scale
(display value)
Bar graph
scale
Transmission
output scale
4 mA 20 mA
L-RG= 6 H-RG= 16
L-SC= 0 H-SC= 1000
LLLL HHHH
L-BS= 0 H-BS= 1000
lOUT= 100 hOUT= 900
4 mA
transmission
20 mA
transmission
■ Bar graph display method [Program mode: BAR]
There are two methods for bar graph display; full bar and center bar.
Full bar [ f B A R] displays input from the bottom, and center bar method [ c B A R]
displays input from ‘0’ as below gures.
Ex)When
※
٧
= 100,
L-BS
Full Bar :
100
Displays the input
from the bottom for
bar graph scale
0
-50
-100
← Bottom
(datum point)
fBAR
= 100, PV = 50,
H-BS
Center Bar :
٧
100
0
-50
-100
cBAR
Displays the input
from 0 for bar graph
scale
← 0
(datum point)
■
Input and transmission output extension[Program mode: ExIO]
This is to extend analog input and 4 to 20mA transmission output to 5% or 10% range.
Mode Operation
0P
Outputs 4 to 20 mA within analog input range.
5P
Outputs 3.2 to 20.8 mA for 5% out of the analog input range.
10P
Outputs 2.4 to 21.6 mA for 10% out of the analog input range.
※
This parameter is displayed only for transmission output (4-20 mA) model. But it is not
displayed when selecting temperature sensor input.
※
A
b
The below of 0 mA, 0 V cannot be extended.
※
±1 V, 10 V inputs are only available for 5% extension.
■ Alarm display in bar graph
B
,
When setting or occurring the alarm, it displays the status by the bar graph.
You can check the alarm status. When setting alarm value, the bar LED for this alarm
Input
value
value turns ON. When alarm occurs, the bar LED for this alarm value ashes.
When setting alarm value,
①
The bar LED for alarm SV ashes. When alarm set is complete, the bar LED for this
alarm value turns ON.
RUN mode
②
• All set alarm values are displays in RUN mode.
• When it is alarm value, the bar LED for this alarm value ashes.
If alarm set value is out of bar graph scale when setting the value or in RUN mode,
this value does not display in bar graph.
10V
Input
value
When setting alarm value
٧
in monitoring mode,
When all alarms are OFF,
Alarm display in RUN mode
٧
When AL1 and AL2 are low limit alarm,
and AL3 and AL4 are high limit alarm.
■ Burn Out [Program mode: BURN]
When disconnecting input sensor, you can set the status of transmission output.
•When setting BURN as ON, 4-20 mA transmission output is xed as 20 mA.
When setting
•
4-20 mA transmission output is xed as 4 mA.
It is available only for temperature sensor input and 4-20 mA transmission output.
※
BURN
as
OFF
,
■ Digital input [Program mode: DI-T, DI-K]
By digital input terminal [ D I-T] (no. 12, 13 terminals) or digital input key [ D I-K]
(D.IN3 : 4+3 for 3 sec.), one of three functions executes as the below table.
Function Operation
Alarm
AlRE
clear
Display
HOLD
HOLD
Zero-
point
ZERO
adjustment
■ Lock [Program mode: LOCK]
It limits to check parameter set value and to change it.
Program mode
Monitoring mode
: Enable to check/set, ◐: Enable to check, disable to set, ○: Disable to check
●
※
In
LO C2
Communications
■
Communication manual
When alarm is ON in RUN mode, it clears alarm forcibly. (It applies only
for alarm latch, alarm latch and standby sequence options.)
Alarm clear operates only when the value is out of the alarm value
range. After clearing alarm, alarm operates its option normally.
※ For the model without alarm output (KN-
not displayed.
Temporarily indicated value is stopped in order to check indicated value
in unstable input.
Set preset display value as 0.
This function is related with input correction [ IN-B].
When executing zero adjustment function in display value as 4,
input correction value [IN-B] is set as -4 automatically.
10 B
), this parameter is
OFF LOC1 LOC2
● ◐ ○
● ● ◐
, only
parameter displays in program mode.
LO CK
Refer to communication manual for RS485 communication.
Visit our web site (www.autonics.com) to download communication manual and
software [Integrated device management program: DAQMaster].
■
Software [Integrated device management program: DAQMaster]
Integrated device management program, DAQMaster, is able to set and monitor
parameters. It is available only for RS485 communication model.
※
The bar LED for the alarm value ashes.
■ Input special function [Program mode: InSF]
When selecting analog input, this function is to display the calculated actual value by
square, root (√), or two unit function (TUF) as display value.
Parameter Functions Graph Applications
Outputs as input
LIN
value
Outputs the
ROOT
rooted
(√) input value
Outputs the
SQAR
squared input
value
TUF
Refer to ‘Two unit function’
※Display value and mA output value for SQAR:
Display value={( ) ×(
(output value)
※Display value and mA output value for ROOT :
Display value={( )×(
(output value)
Input value -
H-RG
Input value -
H-RG
-
L-RG
-
Display
Display
L-RG
L-RG
L-RG
Display
2
Y = AX + B
Input
Y = A( X ) + B
(X ≥ 0)
Y=0(X < 0)
Input
Y = A(X)2 + B
(X > 0)
Input
Y = -A(X)
(X < 0)
H-SC-L-SC
H-SC-L-SC
Standard characteristics.
Input for linearity.
Used for measuring ows by
pressure signal.
Used for outputting differential
pressure by ow signal.
2
+ B
)}+
L-SC
)}+
L-SC
■ Two Unit Function [Program mode: TUF]
When connecting a pressure sensor, compound pressure which is below atmospheric
pressure (0) is for vacuum as mmHg and which is atmospheric pressure or over it is for
positive pressure as kg/cm2.
Atmospheric pressure is 0 kg/cm2. When this unit does not display 0 kg/cm2 , you can
correct zero-point adjustment function.
When using two unit function, L-SC is xed as -760.
L-SC
is displayed but you cannot set this. You can set
Display
H-SC
within 0 to 9999 range.
Ex) When pressure range is 760.0
mmHg to 3.000 kg/cm2 , and pressure
transmitter outputs 4-20 mA, set the
Input
scale as H-SC:
unit displays for
3000, dP: )000
. This
4 mA input as -76)0, and for 20 mA
input as #000.
■ Digital filter [Program mode: MAvF]
Moving average digital lter is able to stably display and output the noise from input
line and irregular signals as software.
Filter set range : 01 to 16
•
(When setting as 01, digital lter function does not run.)
Display cycle is same when executing moving average digital lter.
※
Item Minimum requirements
System IBM PC compatible computer with Intel Pentium Ⅲ or above
Operating system Microsoft Windows 98/NT/XP/Vista/7
Memory 256MB or more
Hard disk More than 1GB of free hard disk space
VGA 1024×768 or higher resolution display
Others RS-232 serial port(9-pin), USB port
■ Communication specifications
Item Specications Item Specications
Com. method RS485 2-wire half duplex Protocol MODBUS 1.1 RTU
Com. speed (BPS)
9600, 4800, 2400, 1200 Parity None
Converter Converter built in RS232 Stop Bit 1Bit
Max. connections
Com. distance
Caution for using
32 units Data length 8Bit
Max. 1200m
(within 700m recommended)
- -
1. For connecting the power, use a crimp terminal(M3.5, min. 7.2 mm).
2. The connection of this unit should be separated from the power line and high voltage
line in order to prevent inductive noise.
3. Install a power switch or a circuit breaker to supply or cut off the power.
4. Switch or circuit breaker should be installed nearby users for convenient control.
5. Do not use this unit near the high frequency instruments (high frequency welding
machine & sewing machine, large capacity SCR controller).
6. When supplying input, if H H HH or LLLL is displayed, measured input may have
problem. Turn off the power and check the line.
7. Installation environment
It shall be used indoor. ② Pollution Degree 2
①
Altitude max. 2,0 00 m ④ Installation category
③
※
It may cause malfunction if above instructions are not followed.
Major products
▣
Photoelectric sensors Temperature controllers
Fiber optic sensors
Door sensors SSR/Power controllers
Door side sensors Counters
Area sensors Timers
Proximity sensors Panel meters
Pressure sensors Tachometer/Pulse(Rate)meters
Rotary encoders Display units
Connectors/Sockets Sensor controllers
Switching mode power supplies
Control switches/Lamps/Buzzers
I/O Terminal Blocks & Cables
Stepper motors/drivers/motion controllers
Graphic/Logic panels
Field network devices
Laser marking system(Fiber, CO₂, Nd:YAG)
Laser welding/soldering system
Temperature/Humidity transducers
HEAD QUARTERS:
OVERSEAS SALES:
E-mail: sales@autonics.com
The proposal of a product improvement and
Ⅱ
Recorders Thyristor units
Indicators Pressure transmitters
Converters Temperature transmitters