Ariston CLAS HE EVO, CLAS HE EVO 24, CLAS HE EVO 30, CLAS HE EVO 38, CLAS HE EVO SYSTEM 18 Installation And Servicing Instructions

...
Page 1
Installation and Servicing Instructions
CLAS HE EVO CLAS HE EVO System
CONDENSING WALL-HUNG GAS BOILER
Country of Destination. GB/IE
G.C.N.:47-116-65 (24 kW) G.C.N.:47-116-66 (30 kW) G.C.N.:47-116-67 (38 kW) G.C.N.:41-116-36 (18 kW) G.C.N.:41-116-37 (24 kW) G.C.N.:41-116-38 (30 kW)
Page 2
INDEX
Overview .......................................................................................................3
General Information ...................................................................................4
Advice for the Installer ...............................................................................4
CE Labelling ...................................................................................................4
Data Plate Symbols .....................................................................................4
Safety Regulations ......................................................................................5
Product description .................................................................................6
Control Panel.................................................................................................6
Overall View ................................................................................................... 7
Overall Dimension ......................................................................................8
Minimum Clearances .................................................................................8
Technical Information ................................................................................9
Installation ................................................................................................ 11
Reference Standards ............................................................................... 11
Installing the Boiler .................................................................................. 14
Gas Connection ......................................................................................... 15
Water Connection .................................................................................... 15
Instructions for Opening the Casing and Performing an
Internal Inspection.............................................................................. 15
Under oor heating .................................................................................. 16
Water circuit diagram..............................................................................17
Connecting the Flue ................................................................................ 18
Fitting the Coaxial Flue (Ø 60/100 Horizontal) ...............................19
Fitting the 5” Flue (Ø 80/125 Horizontal / Vertical) ....................... 20
Fitting the Coaxial Flue (Ø 60/100 Vertical) ..................................... 21
Fitting the Twin Pipe (Ø 80/80) ............................................................ 22
Electrical Connections ............................................................................ 25
Peripheral Unit Connection .................................................................. 25
Room Thermostat Connection ............................................................ 26
Outdoor Sensor Connection ................................................................26
Cylinder connection ................................................................................ 26
Internal mechanical time clock Internal RF receiver for Ariston programmable
room thermostat .................................................................................. 27
Electrical Diagram .................................................................................... 28
Commissioning ....................................................................................... 32
Initial Preparation ..................................................................................... 32
Electricity Supply ...................................................................................... 32
Filling the Heating System .................................................................... 32
Filling of the DHW System .....................................................................32
Gas Supply ..................................................................................................32
Water Treatment ....................................................................................... 32
First Igniton Operation ........................................................................... 33
Ignition procedure ...................................................................................34
Test Function and Combustion Analysis .......................................... 35
AUTO Function ..........................................................................................37
Boiler Protection Devices ................................................................... 38
Boiler Protection Devices ......................................................................38
Table summarising error codes ...........................................................38
Anti-Frost Device ...................................................................................... 39
Settings - Adjustment - Problem Identi cation Menus
Accessing the Menus ..............................................................................40
Maintenance
General Comments .................................................................................. 47
Operational Test ........................................................................................ 47
Draining procedures ...............................................................................47
Cleaning the primary exchanger ........................................................ 47
Cleaning the trap ...................................................................................... 47
Maintenance Guide
General Access ..........................................................................................48
Electrical Unit ............................................................................................. 49
Hydraulic Unit ............................................................................................ 52
Main Heat Exchanger .............................................................................. 60
Burner Unit .................................................................................................61
Fan Unit ........................................................................................................ 64
Gas Valve ...................................................................................................... 65
Annual Maintenance ............................................................................... 66
Benchmark Commissioning Checklist .............................................. 68
Benchmark Service Interval Record ................................................... 69
Page 3
3
overview
These instructions are suitable for CLAS HE boilers : Do not forget the Log Book!
The Benchmark Scheme Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instructions by competent persons and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme. Visit www.centralheating.co.uk for more information.
To The Installer As part of the commissioning of this appliance it is vital that the Log Book is completed and given to the Householder. Please ensure that your customer is aware of the importance of keeping the Log Book safe as a record of the installation and the appliance service history.
Please ensure that your customer is aware of the correct operation of the system, boiler and controls. ARISTON recommend the use of protective clothing, when installing and working on the appliance i.e. gloves.
CUSTOMER CARE
ARISTON, as a leading manufacturer of domestic and commercial water heating appliances is committed to providing high quality products and a high quality after sales service. Advice on installation or servicing can also be obtained by contacting the ARISTON Technical and Customer Service Departments at High Wycombe.
TECHNICAL DEPARTMENT CUSTOMER SERVICE DEPARTMENT Tel: 0333 240 7777 Tel: 0333 240 8777 Fax: 01494 459775 Fax: 01494 459775
GUARANTEE
The manufacturer’s guarantee is for 5 years from the date of purchase. The guarantee is invalidated if the appliance is not installed in accordance with the recommendations made herein or in a manner not approved by the manufacturer. To assist us in providing you with an e cient after sales service, please register the guarantee online at www.ariston.co.uk
CAUTION
In the United Kingdom, installation, start-up, adjustments and maintenance, must be performed by a competent person only, in accordance with the current Gas Safety (Installation & Use) Regulations and the instructions provided.
In the Republic of Ireland, the installation and initial start up of the appliance must be carried out by a Competent Person in accordance with the current edition of I.S.813 “Domestic Gas Installations”, the current Buidling Regulations, reference should also be made to the current ETCI rules for electrical installation.
All GAS SAFE registered installers carry a GAS SAFE ID card, and have a registration number. Both should be recorded in your boiler Log Book. You can check your installer is GAS SAFE registered by calling GAS SAFE directly on:- 0800 408 5500.
Improper installation may cause damage or injury to individuals, animals and personal property for which the manufacturer will not be held liable. To ensure e cient and safe operation it is recommended that the boiler is serviced annually by a competent person.
If it is known that a fault exists on the appliance, it must not be used until the fault has been corrected by a competent person.
This instruction booklet is especially designed for appliances installed in the UK and the Republic of Ireland
Page 4
4
overview
CE labelling
The CE mark guarantees that the appliance conforms to the fol­lowing directives:
- 2009/142/CEE relating to gas appliances
- 2004/108/CEE relating to electromagnetic compatibility
- 92/42/CEE relating to energy e ciency
- 2006/95/CEE relating to electrical safety
Advice for the installer The installation and  rst ignition of the boiler must be performed by quali ed personnel in compliance with current national regulations regarding installation, and in conformity with any requirements established by local authorities and public health organisations. After the boiler has been installed, the installer must ensure that the end user receives the declaration of conformity and the operating manual, and should provide all necessary information as to how the boiler and the safety devices should be handled.
This appliance is designed to produce hot water for domestic use. It should be connected to a heating system and a distribution network for domestic hot water, both of which must be compatible with its performance and power levels. The use of the appliance for purposes other than those speci ed is strictly forbidden. The manufacturer cannot be held responsible for any damage caused by improper, incorrect and unreasonable use of the appliance or by the failure to comply with the instructions given in this manual. Installation, maintenance and all other interventions must be carried out in full conformity with the governing legal regulations and the instructions provided by the manufacturer. Incorrect installation can harm persons, animals and possessions; the manufacturing company shall not be held responsible for any damage caused as a result. The boiler is delivered in a carton. Once you have removed all the packaging, make sure the appliance is intact and that no parts are missing. If this is not the case, please contact your supplier. Keep all packaging material (clips, plastic bags, polystyrene foam, etc.) out of reach of children as it may present a potential hazard. In the event of a fault and/or malfunction, turn the appliance o , turn o the gas cock and do not attempt to repair it yourself. Contact a quali ed professional instead. Before any maintenance or repair work is performed on the boiler, make sure you have disconnected it from the electricity supply by switching the external bipolar switch to the “OFF” position and removing the fuse. All repairs, which should only be performed using original spare parts, should be carried out by a quali ed professional. Failure to comply with the above instructions could compromise the safety of the appliance and invalidate all liability on the part of the manufacturer. In the event of any maintenance or other structural work in the immediate vicinity of the ducts or  ue gas exhaust devices and their accessories, switch the appliance o by switching the external bipolar switch to the “OFF” position and shutting o the gas control valve. When the work has been completed, ask a quali ed technician to check the e ciency of the ducting and the
devices. Turn the boiler o and turn the external switch “OFF” to clean the
exterior parts of the appliance. Clean using a cloth dampened with soapy water. Do not use aggressive detergents, insecticides or toxic products. If the appliance is used in full compliance with current legislation, it will operate in a safe, environmentally-friendly and cost-e cient manner. If using kits or optional extras, make sure they are authentic.
Symbols used on the data plate
MIN
Q
MA
X
P
60/80°C
1
2
5
4
3
3
6
7
19
8
9
10
11
12
14
15
16
17
18
13
20 21 22
1
Legend :
1. Brand
2. Manufacturer
3. Boiler model - Serial number
4. Commercial reference
5. certi cation number
6. Destination country - gas category
7. Gas setting
8. Installation
type
9. Electrical data
10. Maximum domestic hot water pressure
11. Maximum heating pressure
12. Boiler type
13. NOx class / E ciency
14. Input rating nominal heating
15. Power ouput
heating
16. DHW speci c  ow rate
17. Boiler output e ciency
18. Input rating nominal DHW
19. Gases which may be used
20. Minimum ambient temperature for use
21. Max. central heating temperature
22. Max. domestic hot water temperature
Page 5
5
overview
Safety regulations
Key to symbols:
Failure to comply with this warning implies the risk of personal injury, in some circumstances even fatal Failure to comply with this warning implies the risk of damage, in some circumstances even serious, to property, plants or animals.
Install the appliance on a solid wall which is not subject to vibration.
Noisiness during operation.
When drilling holes in the wall for installation purposes, take care not to damage any electrical wiring or existing piping.
Electrocution caused by contact with live wires. Explosions,  res or asphyxiation caused by gas leaking from damaged piping. Damage to existing installations. Flooding caused by water leaking from damaged piping.
Perform all electrical connections using wires which have a suitable section.
Fire caused by overheating due to electrical current passing through undersized cables.
Protect all connection pipes and wires in order to prevent them from being damaged.
Electrocution caused by contact with live wires. Explosions,  res or asphyxiation caused by gas leaking from damaged piping. Flooding caused by water leaking from damaged piping.
Make sure the installation site and any systems to which the appliance must be connected comply with the applicable norms in force.
Electrocution caused by contact with live wires which have been installed incorrectly. Damage to the appliance caused by improper operating conditions.
Use suitable manual tools and equipment (make sure in particular that the tool is not worn out and that its handle is  xed properly); use them correctly and make sure they do not fall from a height. Replace them once you have  nished using them.
Personal injury from the falling splinters or fragments, inhalation of dust, shocks, cuts, pricks and abrasions. Damage to the appliance or surrounding objects caused by falling splinters, knocks and incisions.
Use electrical equipment suitable for its intended use (in particular, make sure that the power supply cable and plug are intact and that the parts featuring rotary or reciprocating motions are fastened correctly); use this equipment correctly; do not obstruct passageways with the power supply cable, make sure no equipment could fall from a height. Disconnect it and replace it safely after use.
Personal injury caused by falling splinters or fragments, inhalation of dust, knocks, cuts, puncture wounds, abrasions, noise and vibration. Damage to the appliance or surrounding objects caused by falling splinters, knocks and incisions.
Make sure any portable ladders are positioned securely, that they are suitably strong and that the steps are intact and not slippery and do not wobble when someone climbs them. Ensure someone provides supervision at all times.
Personal injury caused by falling from a height or cuts (stepladders shutting accidentally).
Make sure any rolling ladders are positioned securely, that they are suitably strong, that the steps are intact
and not slippery and that the ladders are  tted with handrails on either side of the ladder and parapets on the landing.
Personal injury caused by falling from a height.
During all work carried out at a certain height (generally with a di erence in height of more than two metres), make sure that parapets are used to surround the work area or that individual harnesses are used to prevent falls. The space where any accidental fall may occur should be free from dangerous obstacles, and any impact upon falling should be cushioned by semi-rigid or deformable surfaces.
Personal injury caused by falling from a height.
Make sure the workplace has suitable hygiene and sanitary conditions in terms of lighting, ventilation and solidity of the structures.
Personal injury caused by knocks, stumbling etc.
Protect the appliance and all areas in the vicinity of the work place using suitable material.
Damage to the appliance or surrounding objects caused by falling splinters, knocks and incisions.
Handle the appliance with suitable protection and with care.
Damage to the appliance or surrounding objects from shocks, knocks, incisions and squashing.
During all work procedures, wear individual protective clothing and equipment.
Personal injury caused by electrocution, falling splinters or fragments, inhalation of dust, shocks, cuts, puncture wounds, abrasions, noise and vibration.
Place all debris and equipment in such a way as to make movement easy and safe, avoiding the formation of any piles which could yield or collapse.
Damage to the appliance or surrounding objects from shocks, knocks, incisions and squashing.
All operations inside the appliance must be performed with the necessary caution in order to avoid abrupt contact with sharp parts.
Personal injury caused by cuts, puncture wounds and abrasions.
Reset all the safety and control functions a ected by any work performed on the appliance and make sure they operate correctly before restarting the appliance.
Explosions,  res or asphyxiation caused by gas leaks or an incorrect  ue gas exhaust. Damage or shutdown of the appliance caused by out-of-control operation.
Before handling, empty all components that may contain hot water, carrying out any bleeding if necessary.
Personal injury caused by burns.
Descale the components, in accordance with the instructions provided on the safety data sheet of the product used, airing the room, wearing protective clothing, avoid mixing di erent products, and protect the appliance and surrounding objects.
Personal injury caused by acidic substances coming into contact with skin or eyes; inhaling or swallowing harmful chemical agents. Damage to the appliance or surrounding objects due to corrosion caused by acidic substances.
If you detect a smell of burning or smoke, keep clear of the appliance, disconnect it from the electricity supply, open all windows and contact the technician.
Personal injury caused by burns, smoke inhalation, asphyxiation.
Page 6
6
product description
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
9
6
12
I
1
2 3
4
5 6
7
8
9
10
11
12
Control panel
Legend :
1. Display
2. Domestic Hot Water temperature adjustment button +/-
(only for Clas HE EVO models)
3. M
ODE button
(Operation mode selection (summer/winter)
4. Pressure gauge
5. Auto Function and/or Comfort Function enable/disable button
(Comfort function only for Clas HE EVO models)
6. ESC button - reserved for technical assistance
7. “encoder” programming knob
- reserved for technical assistance
8. OK button - reserved for technical assistance
9. ON/OFF button
10.
TIME CLOCK (CLAS HE Evo System models optional)
11. RESET button
12. Heating temperature adjustument button +/-
Digits indicating:
- boiler status and temperature indication (°C)
- error code signals (Err)
- menu settings Technical assistance request
Flame detected with indication of power used or indication of operation shutdown
Heating operation set
Heating operation active
Hot water operation set
Hot water operation active Hot Water Comfort activated
Boiler o with antifreeze function active
Antifreeze function activated
AUTO
AUTO function activated (Temperature regulation activated)
Clip-in solar connected (optional)
Note: A radio frequency (RF) Programmable Room Thermostat is available from Ariston stockists. The Receiver unit can be  tted in the time clock position (10)
Page 7
7
product description
Overall view
1
2
3
4
5
6
7
9
10
12
14
16
19
20
21
22
23
24
8
1
2
3
4
5
6
7
9
10
12
14
15
19
20
21
22
23
24
1. Flue connector
2. Manual air vent
3. Main heat exchanger
4. Detection electrode
5. C.H. Return temperature probe
6. C.H. Flow temperature probe
7. Silencer
8. Secondary heat exchanger
9. Gas valve
10. Trap
12. C.H. Pressure relief valve
14. C.H. Circuit  lter
16. Circulation pump with air release valve
17. D.H.W. Flow switch
18. Diverter valve
19. Low Water Pressure Switch
20. Modulating fan
21. Ignition electrodes
22. Ignitor
23. Thermal fuse
24. Combustion analysis test point
CLAS HE EVO
CLAS HE EVO SYSTEM
Page 8
8
product description
28
200
150
315 mod. 24
F
385 mod. 30/38
120 120
200
180
65 65 67 67
25 770
28
200
120 120
200
132 6567
F
Overall Dimensions
A. Central Heating Flow B. Domestic Hot Water Outlet C. Gas Inlet D. Domestic Cold Water Inlet E. Central Heating Return F. Safety Relief Valve
450
0 0 3
0 0 3
55
Minimum clearances
In order to allow easy access to the boiler for maintenance operations, The boiler must be installed in accordance with the clearances stated below.
5
CLAS HE EVO CLAS HE EVO SYSTEM
Page 9
9
product description
Technical Data
GENERAL NOTE
Model: CLAS HE EVO 24 30 38
CE Certi cation (pin) 0085CL0440
Boiler type
C13(X)-C23-C33(X)-C43(X)-C53(X)-C63(X)
C83(X)-C93(X)-B23-B23P-B33
POWER SPECIFICATIONS
Max/min nominal calori c  ow rate (Pci) Qn KW 22.0/5.5 28.0/6.5 31.0/7.5 Max/min nominal calori c  ow rate (Pcs) Qn KW 24.4/6.1 31.1/7.2 34.4/8.3 Domestic hot water max/min nominal calori c  ow rate (Pci) Qn KW 26.0/5.5 30.0/6.5 38.0/7.5 Domestic hot water max/min nominal calori c  ow rate (Pcs) Qn KW 28.9/6.1 33.3/7.2 42.2/8.3 Max/min power output (80°C-60°C) Pn KW 21.5/5.4 27.3/6.3 30.2/7.3 Max/min power output (50°C-30°C) Pn KW 23.3/5.7 29.7/6.8 33.0/7.9 Domestic hot water max/min power output Pn KW 26.0/5.5 29.3/6.3 38.0/7.5 Combustion e ciency (of  ue gas) % 97.8 97.8 97.9 Nominal calori c  ow rate e ciency (60/80°C) Hi/Hs % 97.5/87.8 97.6/87.8 97.6/87.9 Nominal calori c  ow rate e ciency (30/50°C) Hi/Hs % 105.8/95.3 106.0/95.5 106.4/95.8 E ciency at 30% at 30°C Hi/Hs % 107.7/97.0 107.7/97.0 107.7/97.0 E ciency at 30% at 47°C Hi/Hs % 97.7/88.0 97.6/87.9 97.6/87.9 Minimum calori c  ow rate e ciency (60/80°C) Hi/Hs % 97.6/87.9 97.5/87.8 97.5/87.8 E ciency rating (dir. 92/42/EEC) stars
**** **** **** Sedbuk class class A/90 A/90 A/90.1 Loss when stopped (∆T = 50°C) % Loss of burner gas when operating % 2.2 2.2 2.2
EMISSIONS
Available air pressure Pa 100 100 100 NoX class class 5 5 5 Flue gas temperature (G20) (80°C-60°C) °C 64 64 64 CO2 content (G20) (80°C-60°C) % 9.0 9.0 9.0 CO content (0%O2) (80°C-60°C) ppm 119 101 98 O2 content (G20) (80°C-60°C) % 4.5 4.5 4.5 Maximum  ue gas  ow (G20) (80°C-60°C) Kg/h 42.8 49.4 62.6 Excess air (80°C-60°C) % 27 27 27
HEATING CIRCUIT
Expansion chamber in ation pressure bar 1 1 1 Maximum heating pressure bar 2,5 2,5 2,5 Expansion chamber capacity L 6.5 6.5 6.5 Min/max heating temperature (high temperature range) °C 35 / 82 35 / 82 35 / 82 Min/max heating temperature (low temperature range) °C 20 / 45 20 / 45 20 / 45
DOMESTIC HOT WATER CIRCUIT
Domestic hot water max/min temperature °C 36 / 60 36 / 60 36 / 60 Speci c  ow rate of domestic hot water (∆T=30°C) l/mn 12.2 14.1 18.4 Quantity of hot water ∆T=25°C l/mn 14.5 16.8 21.3 Quantity of hot water ∆T=35°C l/mn 10.4 12.0 15.2 Hot water comfort rating (EN13203) stars *** *** *** Hot water minimum  ow rate l/mn <2 <2 <2 Domestic hot water max/min pressure bar 7 / 0.3 7 / 0.3 7 / 0.3
ELECTRICAL
Power supply frequency/voltage V/Hz 230/50 230/50 230/50 Total electrical power absorbed W 110 113 116 Minimum ambient temperature for use °C +5 +5 +5 Protection level for the electrical appliance PI X5D X5D X5D Weight kg 32 35 36
Page 10
10
product description
GENERAL NOTE
Model: CLAS HE EVO SYSTEM 18 24 30
CE Certi cation (pin) 0085CL0440
Boiler type
C13(X)-C23-C33(X)-C43(X)-C53(X)-C63(X)
C83(X)-C93(X)-B23-B23P-B33
POWER SPECIFICATIONS
Max/min nominal calori c  ow rate (Pci) Qn kW 18.0/4.5 22.0/5.5 28.5/6.5 Max/min nominal calori c  ow rate (Pcs) Qn kW 20.0/5.0 24.4/6.1 31.1/7.2 Max/min power output (80°C-60°C) Pn kW 17.6/4.4 21.5/5.4 27.3/6.3 Max/min power output (50°C-30°C) Pn kW 19.1/4.7 23.3/5.7 29.7/6.8 Combustion e ciency (of  ue gas) % 98.0 97.8 97.8 Nominal calori c  ow rate e ciency (60/80°C) Hi/Hs % 97.6/87.9 97.5/87.8 97.6/87.8 Nominal calori c  ow rate e ciency (30/50°C) Hi/Hs % 106,1/95.5 105.8/95.3 106.0/95.5 E ciency at 30% at 30°C Hi/Hs % 107.7/97.0 107.7/97.0 107.7/97.0 E ciency at 30% at 47°C Hi/Hs % 97.7/88.0 97.7/88.0 97.6/87.9 Minimum calori c  ow rate e ciency (60/80°C) Hi/Hs % 97.6/87.9 97.6/87.9 97.5/87.8 E ciency rating (dir. 92/42/EEC) stars **** **** **** Sedbuk Band / Rating Band / % A/90.1 A/90.0 A/90.0 Loss when stopped (∆T = 50°C) % Loss of burner gas when operating % 2.0 2.2 2.2
EMISSIONS
Available air pressure Pa 100 100 100 NoX class (5 = less than 70mg/kWh class 5 5 5 Flue gas temperature (G20) (80°C-60°C) °C 61 64 64 CO2 content (G20) (80°C-60°C) % 9.0 9.0 9.0 CO content (0%O2) (80°C-60°C) ppm 93 119 101 O2 content (G20) (80°C-60°C) % 4.5 4.5 4.5 Maximum  ue gas  ow (G20) (80°C-60°C) Kg/h 29.7 36.3 46.1 Excess air (80°C-60°C) % 27 27 27
HEATING CIRCUIT
Expansion chamber in ation pressure bar 1 1 1 Maximum heating pressure bar 2,5 2,5 2,5 Expansion chamber capacity L 6.5 6.5 6.5 Min/max heating temperature (high temperature range) °C 35 / 82 35 / 82 35 / 82 Min/max heating temperature (low temperature range) °C 20 / 45 20 / 45 20 / 45
DOMESTIC HOT WATER CIRCUIT ELECTRICAL
Power supply frequency/voltage V/Hz 230/50 230/50 230/50 Total electrical power absorbed W 106 113 116 Minimum ambient temperature for use °C +5 +5 +5 Protection level for the electrical appliance PI X5D X5D X5D Weight kg 32 32 35
Page 11
11
installation
Reference Standards
In the United Kingdom, the installation and initial start-up of the boiler must be by a Gas Safe registered installer in accordance with the installation standards currently in e ect, as well as with any and all local health and safety standards i.e. Gas Safe.
In the Republic of Ireland the installation and initial start-up of the appliance must be carried out by a Competent Person in accordance with the current edition of I.S.813 “Domestic Gas Installations” and the current Building Regulations, reference should also be made to the current ETCI rules for electrical installation.
The installation of this appliance must be in accordance with the relevant requirements of the Local Building Regulations, the current I.E.E. Wiring Regulations, the by-laws of the local authority, in Scotland, in accordance with the Building Standards (Scotland) Regulation and Health and Safety document No. 635, “Electricity at Work Regulations 1989” and in the Republic of Ireland with the current edition of I.S. 813 and the Local Building Regulations (IE).
C.O.S.H.H.
Materials used in the manufacture of this appliance are non­hazardous and no special precautions are required when servicing.
Codes of Practive
Installation should also comply with the following British Standards Code of Practice:
BS 7593: Treatment of water in domestic hot water central heating systems BS 5546: Installation of hot water supplies for domestic purposes BS 5440-1: Flues BS 5440-2: Air supply BS 5449: Forced circulation hot water systems BS 6798: Installation of gas  red hot water boilers of rated input not exceeding 70kW BS 6891: Installation of low pressure gas pipes up to 28mm BS 7671: IEE Wiring Regulations BS 4814: Speci cation for expansion vessels BS 5482: Installation of L.P.G.
and in the Republic of Ireland in accordancce with the following codes of practice:
I.S. 813 Domestic Gas Installations
Avoid installing the boiler where the air inlet can be polluted by chemical products such as chlorine (swimming pool area), or ammonia (hair dresser), or alkalin products (launderette).
Flue
Detailed information on  ue assembly can be found in the “Connecting the Flue” section. The boiler must be installed so that the  ue terminal is exposed to the free passage of external air at all times and must not be installed in a place likely to cause nuisance. It must not be allowed to discharge into another room or space such as an outhouse or closed lean-to.
Condensing boilers have a tendency to form a plume of water vapour from the  ue terminal due to the low temperature of the  ue gasses. The terminal should therefore be located with due regard for the damage or discolouration that may occur to building within the vicinity and consideration must also be given to adjacent boundaries, openable windows should also be taken into consideration when siting the  ue.
The minimum acceptable clearances are shown below:
- A Directly below an opening, window, etc 300 mm
- B Horizontally to an opening, window, etc 300 mm
- C Below gutters, soils pipes or drain pipes 75 mm
- D Below eaves 200 mm
- E From vertical drain pipe or soil pipe 75 mm
- F From internal or external corner 300 mm
- G Above ground, roof or balcony level 300 mm
- H From a surface facing the terminal 600 mm
- I From a terminal facing a terminal 1200 mm
- J Vertically from a terminal on the same wall 1500 mm
- K Horizontally from an terminal on the same wall 300 mm
- L Fixed by vertical  ue terminal
N
OTE: THE FLUE MUST NOT BE INSTALLED IN A PLACE LIKELY TO CAUSE A NUISANCE AND POSITIONED TO ENSURE THAT PRODUCTS OF COMBUSTION DO NOT DISCHARGE ACROSS A BOUNDARY
It may be necessary to protect the terminal with a guard, if this is the case it will be necessary to purchase a stainless steel terminal guard. Reference should be made to the Building Regulations for guidance.
Ventilation
The room in which the boiler is installed does not require speci c ventilation. If the boiler is installed in a cupboard or compartment ventilation is not required for cooling purposes.
Page 12
12
installation
Gas Supply
The gas installation and tightness testing must be in accordance with the requirements of BS6891. Ensure that the pipe size is adequate for demand including other gas appliances on the same supply.
Electrical Supply
The appliance requires an earthed 230V - 50 Hz supply and must be in accordance with current I.E.E. regulations. It must also be possible to be able to completely isolate the appliance electrically. Connection should be via a 3 amp double pole fused isolating switch with contact separation of at least 3mm on both poles. Alternatively, a fused 3 amp, 3 pin plug and unswitched socket may be used, provided it is not used in a room containing a bath or shower, it. It should only supply the appliance.
Water Supply
The boiler is suitable for sealed systems only. The maximum working pressure for the appliance is 6 bar. All  ttings and pipework for the appliance should be of the same standard. If there is a possibility of the incoming mains pressure exceeding 6 bar, particularly at night, then a suitable pressure limiting valve must be  tted. The boiler is designed to provide hot water on demand to multiple outlets within the property. If there is a requirement for greater demands, for example if the boiler has several bathrooms and cloakrooms, a vented or unvented hot water storage system may be used.
Showers
Any shower valves used with the appliance should be of a thermostatic or pressure balanced type. Refer to the shower manufacturer for performance guidance and suitability.
Flushing and Water Treatment
The boiler is equipped with a stainless steel heat exchanger.
The detailed recommendations for water treatment are given in BS 7593:1992 (Treatment of water in domestic hot water central heating systems); the following notes are given for general guidance.
If the boiler is installed on an existing system, any unsuitable additives must be removed.
Under no circumstances should the boiler be  red before the system has been thoroughly  ushed; the  ushing procedure must be in line with BS 7593:1992.
We highly recommend the use of a  ushing detergent appropriate for the metals used in the circuit. These include cleansers produced by Fernox BetzDearbon, whose function is to disolve any foreign matter that may be in the system.
In hard water areas or where large quantities of water are in the system the treatment of water to prevent premature scaling of the main exchanger is necessary.
The formation of scale heat compromises the e ciency of the thermic exchanger because small areas of scale cause a high increase of the temperature of the metallic walls and therefore add to the thermal stress of the heat exchanger.
Demineralised water is more aggressive so in this situation it is necessary to treat the water with an appropriate corrosion inhibitor.
Any treatment of water by additives in the system for frost protection or for corrosion inhibition has to be absolutely suitable for all metals used in the circuit.
The use of a corrosion inhibitor in the sysem such as Fernox MB-1, BetzDearborn Sentinel X100 or Fernox System Inhibitor is recommended to prevent corrosion (sludge) damaging the boiler and system;
If anti-freeze substances are to be used in the system, check carefully that they are compatible with the metals used in the circuit.
ARISTON suggests the use of suitable anti-freeze products such as Fernox ALPHI 11, which will prevent rust and incrustation taking place.
Periodically check the pH balance of the water/anti-freeze mixture of the boiler circuit and replace it when the amount measured is out of the range stipulated by the manufacturer (7 < pH < 8). DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE
In under- oor systems, the use of plastic pipes without protection against penetration of oxygen through the walls can cause corrosion of the systems metal parts (metal piping, boiler etc), through the formation of oxides and bacterial agents.
To prevent this problem it is necessary to use pipes with an “oxygen proof barrier”, in accordance with standards DIN 4726/4729. If
pipes of this kind are not used, keep the system separate by installing heat exchangers of those with a speci c system water treatment.
IMPORTANT Failure to carry out the water treatment procedure will invalidate the appliance guarantee.
System Controls
The boiler is electrically controlled and is suitable for most modern electronic time and temperature controls. The addition of such external controls can be bene cial to the e cient operation of the system. The boiler connections for external controls are 12V DC and so only controls of 12V DC that have voltage free contacts should be used. (page 25). ARISTON supply a range of wired and wireless system controls. Contact your supplier for more details.
Location
The boiler can be installed on any suitable internal wall (suitable sound proo ng may be required when installing onto a stud partition wall). Provision must be made to allow for the correct routing of the  ue and siting of the terminal to allow the safe and e cient removal of the  ue products. A compartment or cupboard may be used provided that it has been built or modi ed for this purpose. It is not necessary to provide permanent ventilation for cooling purposes. Detailed recommendations are given in BS 5440 Part 2. If it is proposed that it is to be installed in a timber framed building then reference should be made to British Gas Document DM2, IGE/UP/7 or advice sought from CORGI.
Where a room sealed appliance is installed in a room containing a bath or shower, the appliance and any electrical switch or appliance control, utilising mains electricity should be situated speci cally in accordance with current IEE Wiring Regulations.
For unusual locations, special procedures may be necessary. BS 6798:2000 gives detailed guidance on this aspect.
Page 13
13
installation
Codensate Discharge
The condensate discharge hose from the boiler must have a continuous fall of 2.5o and must be inserted by at least 50mm into a suitable acid resistant pipe - e.g. plastic waste or over ow pipe. The condensate discharge pipe must have a minimum diameter of 22mm, must have a continuous fall and preferably be installed and terminated to prevent freezing. The discharge pipe must be terminated in a suitable position:
i) Connecting into an internal soil stack (at least 450mm above
the invert of the stack). A trap giving a water seal of at least 75mm must be incorporated into the pipe run, there also must be an air beak upstream of the trap.
ii) Connecting into the waste system of the building such as
a washing maching or sink trap. The connection must be upstream of the washing machine/sink. If the connection is downstream of the waste trap then an additional trap giving a minimum water seal of 75mm and an air break must be incorporated in the pipe run, as above.
iii) Terminating into a gully, below the grid level but above the
water level
iv) Into a soakaway
Note: If any condensate pipework is to be installed externally then it should be kept to a minimum and be insulated with a waterproof insulation and have a continuous fall. The total length of external pipe used should not exceed 3 metres.
Some examples of the type of condensate terminations can be found below.
1. Internal termination of condensate drainage pipe to internal stack.
2. External termination of condensate drainage pipe via internal discharge branch (e.g. sink waste) and condensate siphon.
3. External termination of condensate drainage pipe via internal discharge branch (e.g. sink waste - proprietary  tting).
4. External termination of condensate drainage pipe via condensate siphon
Tundish
trap
Tundish
trap
Tundish
Tundish
External pipe length max. 3 metres (must be insulated)
Condensate Discharge
Push  t the  exible condensate pipe into the outlet spigot on the appliance. Cut to length and locate outlet into a tundish
Page 14
14
installation
Installing the Boiler
Please check that you are familiar with the installation requirement before commencing work (pages 11 - 15).
The installation accessories described in the following list are included in the boiler packaging:
- Hanging bracket
- A paper template (showing the dimensions of the boiler with 5 mm side clearances)
- Connection valves (compression)
- Screws and washers
- Filling loop
- Installation, Servicing and User manual
Method of positioning the boiler on the wall
The paper template can be used to ensure the correct positioning of kitchen cabinets etc.
The paper template has to be  xed to the wall and used to locate the position of the hanging bracket and the centre for the  ue hole. Drill and plug the wall and secure the hanging bracket using the screws provided ensure the hanging bracket is level. Remove the boiler from its packaging and remove the front casing panel. Place the boiler on the hanging bracket.
N
OTE: THE APPLIANCE MUST NOT BE FITTED ON A COMBUSTIBLE WALL SURFACE.
Connecting the boiler to the system
- Remove the boiler casing as described on page 15
- Remove the caps and connect the valves to the boiler using the washers provided
- 5 x  bre washers for the CH  ow and return, cold water inlet, gas and hot water outlet connections
Safety Valve Discharge
The pressure relief valve pipe is made of copper. It should terminate below the boiler safely outside the premises. Care should be taken that it does not terminate over an entrance or window or where a discharge of heated water could endanger occupants or passers by.
Warning !
Do not apply heat to the copper safety valve outlet pipe
whilst it is connected to the 3 bar safety relief valve.
Fill the central heating and DHW system and bleed air from the system as described in the Commissioning instructions (page 31).
The system should be carefully checked for leaks, as frequent re lling could cause premature system corrosion or unnecessary scaling of the heat exchanger. The pipe from the trap should be connected to a drain as described in the relevant regulations.
Pay special attention not to bend the condensate silicone drain pipe is such a way as to interrupt the  ow. Please only use drain pipe material compatible with condensate products (refer to BS 6798:2000).
The condensate  ow can reach 2 litres/hour because of the acidity of the condensate products (Ph close to 2), take care before operation.
See page 13 for condensate discharge options.
Note: Connections viewed from behind boiler
A
A
- remove the 2 screws A from the transport bar
- dispose of the transport bar and reassemble the  xing screws.
Note: Connections viewed from behind boiler
CLAS HE EVO
CLAS HE EVO SYSTEM
Note.
Connections viewed from behind boiler.
Page 15
15
installation
Gas connection
Make sure, using the labels on the packaging and the data plate on the appliance itself, that the boiler is in the correct country and that the gas category for which the boiler was designed corresponds to one of the categories available in the country where it will be used. The gas supply piping must be created and measured out in compliance with speci c legal requirements and in accordance with the maximum power of the boiler. Check that the supplied gas corresponds to the type of gas for which the boiler was designed (see the data plate located on the appliance itself). It is also important to check that the pressure of the gas (methane or LPG) you will be using to feed the boiler is suitable, because if it is insu cient the power may be reduced, causing inconvenience for the user.
Instructions for opening the casing and performing an internal inspection
Before performing any work on the boiler,  rst disconnect it from the electrical power supply using the external bipolar switch removing the fuse and shutting o the gas valve. To access the inside of the boiler, the following is necessary:
1. Remove the casing by unhooking it from the control panel (a)
2. Loosen the two screws on the front casing (b), pull it forwards and unhook it from the upper pins (c)
3. Lower the control panel (d)
4. Unhook the two clips on the combustion chamber panel and lift o (e).
(c)
Water connection
The illustration below shows the connections for the water and gas attachments of the boiler. See valves con guration on page
14. Check that the maximum water mains pressure does not exceed 6 bar; if it does, a pressure reducing valve must be installed. For the measuring of the pipes and of the heating bodies in the heating system, the residual head value should be calculated as a function of the requested  ow rate, in accordance with the values shown in the circulation pump graph.
A. Central heating Flow B. Domestic Hot Water Outlet C. Gas Inlet D. Domestic Cold Water Inlet E. Central Heating Return F. Safety Valve Discharge H. Drain Valve I. Drain condensate
(e)
A
B
C
D
E
I
H
F
A
C
D
E
I
H
F
CLAS HE EVO
CLAS HE EVO SYSTEM
(a)
(b)
(d)
Page 16
16
installation
To calculate the size of the heating installation, refer to the "Available pressure" graph below.
Graph representing the available circulation pump pressure
T20
o
C
Before the equipment is used, for the  rst time the trap
must be  lled with water. To do this, add approximately 1/4 litre of water via the  ue outlet before  tting the  ue system, or unscrew the cap on the trap positioned under­neath the boiler,  ll it with water and re t it
Warning! Insu cient water in the trap can temporarily cause the  ue gas to be expelled into the surrounding ambient air
Under oor heating
For appliances with under oor heating, it is possible but not necessary to  t a safety thermostat onto the under oor heating outlet. For the electrical connection of the thermostat see the section on “Electrical connections - page 25”.
If the outlet temperature is too high, the boiler will stop both domestic hot water and the heating production and the error code 1 16 “ oor thermostat contact open” will appear on the display. The boiler will restart when the thermostat is closed during automatic resetting.
If the thermostat cannot be installed, the under oor heating equipment must be protected by a thermostatic valve, or by a by­pass to prevent the  oor from reaching too high a temperature.
0
1
2
3
4
5
6
0 100 200 300 400 500 600 700 800 900 1000
[mCE]
18/24
30
0
0,5
1
1,5
2
2,5
3
3,5
4
4,5
5
0 100 200 300 400 500 600 700 800 900 1000 1100
[mCE]
[l\h]
24
30
38
I
CLAS HE EVO
CLAS HE EVO SYSTEM
Page 17
17
installation
1. Manual air vent
3. Burner
4. Detection electrode
5. C.H.  ow temperature probe
6. C.H. return temperature probe
7. Secondary heat exchanger
8. C.H. pressure relief valve
10. By-pass
11. Drain valve
12. Condensate trap
13. Filling loop
14. C.H. circuit  lter
15. D.H.W. Flow switch
16. diver ter valve
17. water pressure sensor
18. circulation Pump
19. expansion vessel
20. modulating Fan
21. ignition elec trodes
22. thermal fuse
Water circuit diagram
1
4
3
11
8
10
12
14
17
18
19
20
21
22
6
5
A C E
1
4
3
11
8
10
12
13
14
15
16
17
18
19
20
21
22
7
6
5
A
A
B
B
C
C
D D E
E
Page 18
18
installation
Connecting the Flue
Flue System The provision for satisfactory  ue termination must be made as described in BS 5440-1. The appliance must be installed so that the  ue terminal is expo­sed to outdoor air. The terminal must not discharge into another room or space such as an outhouse or lean-to. It is important that the position of the terminal allows a free pas­sage of air across it at all times. The terminal should be located with due regard for the damage or discolouration that might occur on buildings in the vicinity, it must also be located in a place not likely to cause nuisance. In cold or humid weather water vapour may condense on leaving the  ue terminal. The e ect of such “steaming” must be considered. If the terminal is less than 2 metres above a balcony, above ground or above a  at roof to which people have access, then a suitable stainless steel terminal guard must be  tted.
The minimum acceptable spacing from the terminal to obstruc­tions and ventilation openings are speci ed in Fig. 1.
- A Directly below an opening, window, etc 300 mm
- B Horizontally to an opening, window, etc 300 mm
- C Below gutters, soils pipes or drain pipes 75 mm
- D Below eaves 200 mm
- E From vertical drain pipe or soil pipe 75 mm
- F From internal or external corner 300 mm
- G Above ground, roof or balcony level 300 mm
- H From a surface facing the terminal 600 mm
- I From a terminal facing a terminal 1200 mm
- J Vertically from a terminal on the same wall 1500 mm
- K Horizontally from an terminal on the same wall 300 mm
- L Fixed by vertical  ue terminal
Fig. 1
118 mm
150 mm
Minimum Length = 500 mm
180 mm
Fig. 2
Page 19
19
installation
Warning
The exhaust gas ducts must not be in contact with or close to in ammable material and must not pass through building structures or walls made of in ammable material. When replacing an old appliance, the  ue system must be changed.
Important
Ensure that the  ue is not blocked. Ensure that the  ue is supported and assembled in accordance with these instructions.
150 mm
118
* Min slope: 1˚
1˚= 17.5mm per metre
150 mm
* pente
Installation without extension
Installation with extension
Level
Level
Fitting the Coaxial Flue (Ø 60 / 100 Horizontal)
Contents: 1x Silicone O-Ring (60mm) 1x Elbow (90°) 2x Wall Seals (Internal & External) 1x Flue Pipe including Terminal (1 metre - 60/100) 2x Flue Clamps 4x Screws 2x Seals
Once the boiler has been positioned on the wall,  t the rubber  ue seal into the internal  ue turret (see diagram opposite),
Insert the elbow into the socket and rotate to the required position. note: It is possible to rotate the elbow 360° on its vertical axis.
Using the  ue clamp, seals and screws supplied (Fig 4) secure the elbow to the boiler.
The 1 metre horizontal  ue kit (3318073) supplied is suitable for an exact X dimension of 753mm.
Measure the distance from the face of the external wall to the face of the  ue elbow (X - Fig 2), this  gure must now be subtracted from 753mm, you now have the total amount to be cut from the plain end of the  ue.
Draw a circle around the outer  ue and cut the  ue to the required length taking care not to cut the inner  ue, next cut the inner  ue ensuring that the length between the inner and outer  ue is maintained. (Fig 4).
e.g. X = 555mm 753-555 = 198mm (Length to be cut from the plain end of the  ue).
Once cut to the required length, ensure that the  ue is free from burrs and reassemble the  ue. If  tting the  ue from inside of the building attach the outer wall seal to the  ue terminal and push the  ue through the hole, once the wall seal has passed through the hole, pull the  ue back until the seal is  ush with the wall. Alternatively, the  ue can be installed from outside of the building, the outer seal being  tted last.
Should the  ue require extending, the  ue connections are push  t, however, one  ue bracket should be used to secure each metre of  ue.
Note: See table for maximum and minimum  ue runs.
slope
Fig. 3
Note: A Plume management kit is available for 60/100 horizontal termination. Instructions for installation are supplied with the Plume management kit.
Page 20
20
installation
Fitting the 5” Flue (Ø 80 / 125 Horizontal/vertical)
Once the boiler has been positioned on the wall, it is necessary to insert the Ø80/125 adaptor (Fig. 5) for both horizontal and vertical  ue runs into the boiler  ue socket (not supplied with  ue kit ­Part No 3318095).
Push the adaptor onto the boilers  ue connection, grease the seals then add extensions or elbows as required, secure the adaptor, using the clamp and screws provided.
To  t extensions or elbows it is  rst necessary to ensure that the lip seal is  tted correctly into the inner  ue, once veri ed, it is simply necessary to push them together, no clamps are necessary to secure the  ue components.
Before proceeding to  t the  ue, ensure that the maximum  ue length has not been exceeded (See the tables) and that all elbows and bends have been taken into consideration, for each additional 90° elbow 1 metre must be subtracted from the total  ue length, and for each 45° 0.5 metres must be subtracted from the total  ue length (the height of the vertical adaptor and a 45° bend can be seen in Fig.6 and a 90° bend in Fig. 7).
Note: DO NOT cut the vertical  ue kit.
180 mm
Total length
of Vertical Kit
1240 mm
5" Adaptor Part no: 3318095
* This length will vary according to the type of ashing installed
Useable length
of Vertical ue
575 mm*
Fig. 5
Clamp
Seal
Screws
Fig. 4
Fig. 6
Fig. 7
Page 21
21
installation
Fitting the Coaxial Flue (Ø 60 / 100 Vertical)
Note: See table for maximum and minimum  ue runs.
Contents: 1x Conical Adaptor (60/100mm) 1x Vertical Flue Kit (80/125mm)
The vertical  ue kit is supplied with a specially designed weather proof terminal  tted, it can be used either with a  at roof or a pitched roof.
The Vertical  ue kits useable lengths with the pitched roof  ashings are indicated in Fig. 7.
Before proceeding to  t the  ue, ensure that the maximum  ue length has not been exceeded (See the tables) and that all elbows and bends have been taken into consideration, for each additional 90° elbow 1 metre must be subtracted from the total  ue length, and for each 45° 0.5 metres must be subtracted from the total  ue length (the height of the vertical adaptor and a 45° bend can be seen in Fig. 8).
Mark the position of the  ue hole in the ceiling and/or roof (see Fig. 7 for distance from wall to the centre of the  ue).
Cut a 130mm diameter hole through the ceiling and/or roof and  t the  ashing plate to the roof.
DO NOT cut the vertical  ue kit.
To connect the vertical  ue kit directly to the boiler, place the vertical starter kit (Part No. 3318079) (see Fig. 7) onto the exhaust manifold and secure with the clamp,  t the vertical adaptor onto the vertical starter kit (note: there is no need to use a clamp to secure this as it is a push  t connection), the vertical  ue kit must then be inserted through the roof  ashing, this will ensure that the correct clearance above the roof is provided as the terminal is a  xed height.
Should extensions be required, they are available in 1 metre (Part No. 3318077), 500mm (Part No. 3318078) and they must be connected directly to the vertical starter kit before connecting the adaptor to allow the vertical  ue kit to be  tted. In the event that extension pieces need to be shortened, they must only be cut at the male end and it must be ensured that the inner and outer  ue remain  ush.
When utilising the vertical  ue system, action must be taken to ensure that the  ue is supported adequately to prevent the weight being transferred to the appliance  ue connection by using 1  ue bracket per extension.
When the  ue passes through a ceiling or wooden  oor, there must be an air gap of 25mm between any part of the  ue system and any combustible material. The use of a ceiling plate will facilitate this. Also when the  ue passes from one room to another a  re stop must be  tted to prevent the passage of smoke or  re, irrespective of the structural material through which the  ue passes.
180 mm
Vert Adaptor (supplied with ue kit)
Vertical Starter Part No: 3318079
* This length will vary according to the type of ashing installed
Total length
of Vertical Kit
1355 mm
Useable length
of Vertical ue
690 mm*
Fig. 7
Fig. 8
Page 22
22
installation
Fitting the Twin Pipe (Ø80 / 80)
Note: See table for maximum and minimum  ue runs.
Where it is not possible to terminate the  ue within the distance permitted for coaxial  ues, the twin  ue pipe can be used by  tting a special adaptor to the  ue connector and using the aperture for the air intake located on top of the combustion chamber.
Always ensure that the  ue is adequately supported, using one  ue bracket per extension and avoiding low points. (ARISTON supply suitable clamps as Part No. 705778). To utilise the air intake it is necessary to:
1) Take the air intake cover o the top of the appliance
2) Assemble the  ange on the header supplied with the boiler
3) Insert the header on the tube or the elbow up until the lower stop (you do not have to use the washer).
4) Insert the elbow/header in the boiler air intake hole and fasten it with screws.
The twin  ue pipes can be  tted with or without additional elbows and need no clamps, simply ensure that the lip seal is inserted in the female end of the  ue pipe and push the extension piece fully into the previous section of  ue pipe or elbow, check that the lip seal is not dislodged when assembling the  ue (greasing the seal will aid assembly).
Twin pipe can also be converted back to Coaxial  ue to enable vertical termination with a coaxial kit by using the pipe bridge (Twin - Coaxial Adaptor - Part No. 3318089). When running the twin  ue pipe vertically.
It is not possible to terminate concentrically horizontally. Termination is only possible with separate air and exhaust terminals.
When siting the twin  ue pipe, the air intake and exhaust terminals must terminate on the same wall, the centres of the terminals must be a minimum of 280 mm apart and the air intake must not be sited above the exhaust terminal (refer to Fig. 10). The air intake pipe can be run horizontally, however, the terminal and the  nal 1 metre of  ue must be installed either horizontally or with a slight fall away from the boiler to avoid rain ingress.
It is also strongly recommended that the air intake pipe run be constructed of insulated pipe to prevent condense forming on the outside of the tube.
Ensure the exhaust tube has a minimum fall back to the boiler of 1˚ / metre (1˚ = 17.5mm/metre)
The maximum permissible  ue length for twin  ue is dependent on the type of run used (see table on page 24).
For further information relating to  ue runs not illustrated, please contact the Technical Department on 0870 241 8180.
Page 23
23
installation
For coaxial systems, the maximum development value, mentioned in the table below also takes into account an elbow. For twin  ue systems the maximum development value, mentioned in the table includes the exhaust gas/air intake terminal.
Twin  ue systems outlets should respect the following instructions: 1- Use the same ø 80 mm  ue pipes for the air intakes and exhaust
gas ducts.
2- If you need to insert elbows in the air intake and exhaust gas
ducts, you should consider for each one the equivalent length
to be included in the calculation of developed length. 3- The exhaust gas duct should jut above the roof by at least 0.5 m. 4- The intake and exhaust gas ducts in Type C13 + C53 must be
installed on the same wall, or where the exhaust is vertical and
the air intake horizontal, the terminals must be on the same
side of the building.
EXHAUST
AIR INTAKE
AIR INTAKE
AIR INTAKE MUST NOT BE
FITTED ABOVE THE EXHAUST
195
105
120
180
Fig. 9
Fig. 10
Page 24
24
installation
Table of  ue gas exhaust duct lengths
S1 = Air intake S2 = Flue gas exhaust
S1 = S2 - Air intake and  ue gas exhaust equal lengths S1 + S2 - Air intake and  ue gas exhaust unequal lengths
FLUE TYPE
Maximum Extension Exhaust-air (m)
Diameter of pipe
(mm)
CLAS HE EVO CLAS HE EVO SYSTEM
24 30 38 18 24 30
Coaxial System
C13 C33 C43
12 10 7 14 12 10 ø 60/100
C13 C33 C43
36 30 20 42 36 30 ø 80/125
Twin-pipe System
S1 = S2
ø 80/80
C13 24/24 26/26 16/16 36/36 24/24 26/26 C33 40/40 50/50 28/28 60/60 40/40 50/50 C43 24/24 26/26 16/16 36/36 24/24 26/26
C53
S1 + S2 S1 + S2
60 50 35 50 60 50 ø 80/80
TYPE C13
TYPE C33 TYPE C53
TYPE C33 TYPE C33
Page 25
25
installation
WARNING Before performing any work on the boiler,  rst disconnect it from the electrical power supply using the external bipolar switch and remove the fuse.
Electrical connections
For increased safety, ask a quali ed technician to perform a thorough check of the electrical system. The manufacturer is not responsible for any damage caused by the lack of a suitable earthing system or by the malfunctioning of the electricity mains supply. Make sure that the system is able to withstand the maximum power absorbed by the boiler (this is indicated on the appliance data plate). Check that the section of the wires is suitable and is not less 0,75 mm
2
The appliance must be connected to an e ecient earthing system if it is to operate correctly. The power supply cable must be connected to a 230V-50Hz network, where the L-N poles and the earth connection are all respected. Important! In the event that the power supply cable must be changed, replace it with one with the same speci cations.
Power supply cable
Important! The appliance is supplied with a  y-lead already connected, this must be connected to a 240V supply fused at 3 Amp and must facilitate completed electrical isolation of the appliance, by use of a fused double pole isolator having a contact separation of at least 3mm in all poles or alternatively by means of a 3A fused three pin plug and unswitched shuttered socket outlet both complying with BS1363.
The use of multiplugs, extension leads or adaptors is strictly prohibited. It is strictly forbidden to use the piping from the hydraulic, heating and gas systems for the appliance earthing connection. The boiler is not protected against the e ects caused by lightning. If the mains fuses need to be replaced, use 2A rapid fuses.
Peripheral unit connection
To access peripheral unit connections carry out the following steps:
- Disconnect the boiler from the power supply
- Remove the casing by unhooking it from the instrument panel
- Rotate the control panel while pulling it forwards
- Unhook the two clips “a”, rotate the cover “b” to have access to the peripherical connections
- Unscrew the two screws “c” and remove the cover “d” of the instrument panel to have access to the main P.C.B.
H05V2V2-F
60
N
L
a
b
c
d
BUS
T
B
TA2
SE
TNK
SOL TA1
BUS
TB
TA2
FLOOR
SETNK SOL TA1
CN1
emote Control
Outdoor sensor Underoor heating thermostat Room Thermostat 2
Room Thermostat 1
Peripheral connections:
BUS = Remote control connection FLOOR/TA2 = the under oor heating thermostat or the room
thermostat 2 (selected via parameter 223)
SE = the external sensor. SOL = Solar temperature probe TA1 = the room thermostat 1
Page 26
26
installation
Room Thermostat / Remote Clock Connection
To connect a room thermostat, it is necessary to:
1. Open the control panel
2. Loosen the cable clamp using a screwdriver and insert the wires leading from the room thermostat
3. Connect the wires to the terminals as indicated in the  gure below, removing the link
4. If a remote time clock is to be  tted, using a volt free switching time clock connect the switching wires from the time clock following points 1 - 3 above
5. If using an external time clock and room thermostat, these must be connected in series as shown in diagram C,
6. Ensure that they are well connected and not subject to stress when the control panel is closed
DO NOT CONNECT 240V TO ANY PERIPHERAL CONNECTIONS
Outdoor sensor connection
- Introduce the outdoor sensor wires
- Loosen the cable clamp using a screwdriver and insert the wires leading from the outdoor sensor one at a time.
- Connect the wires to the terminals as indicated in the  gure below;
- Make sure that they are well connected and that they are not subject to stress when the control panel lid is opened or closed;
- Close the  ap again, then replace the control panel cover and the front casing.
- Refer to page 39 for setting the parameters when using the outdoor sensor.
N
OTE: WHEN CONNECTING THE BOILER TO EXTERNAL CONTROLS, DO
NOT RUN 240V CABLES AND CABLES FOR SWITCHING CIRCUITS
(
WHICH ARE LOW VOLTAGE) TOGETHER, USE SEPERATE CABLES TO
PREVENT INDUCED VOLTAGE ON THE LOW VO LTAGE CIRCUITS.
Connector SE on PCB
Outdoor Sensor
Connector TA on PCB (low voltage switching)
Connector TA on PCB (low voltage switching)
Connector TA on PCB (low voltage switching)
Cylinder connection (CLAS HE EVO SYSTEM)
The boiler can be connected to a central heating system that uses two zone valves to allow connection to an indirect storage cylinder. There are two wiring diagrams shown, one for the connection to an Unvented Cylinder and one for connection to an open vented cylinder. In both cases the boiler connection is shown as TA1.
When connecting the boiler to an external cylinder do not run 240V cables and the cables for the TA1 together, use separate cables to prevent induced voltage on the low voltage switching circuit.
NOTE: THE USE OF A ‘Y’ PLAN SYSTEM IS NOT POSSIBLE WITH THE CLAS HE SYSTEM BOILER DUE TO THE LOW VOLTAGE SWITCHING OF THE APPLIANCE
UNLESS SUITABLE RELAY CONTROLS ARE USED.
Important!! Ensure that a balancing valve is  tted on the cylinder return and balanced correctly at commissioning stage.
(see p.25)
Page 27
27
installation
Fitting instructions for:
• Internal mechanical time clock
• Internal RF receiver for Ariston programmable
room thermostat
These instructions to be used in conjunction with the appliance installation instructions. Ensure the appliance is electrically isolated before working on the appliance. Remove the outer casing, and remove the front control panel by removing the 2 securing screws. Remove the clock blanking plate (or existing clock if  tting the RF receiver in a product with an existing mechanical clock) from the front control panel of the boiler. Using the 4 securing screws supplied with the clock accessory, secure the clock/RF receiver into position, ensuring the accessory is oriented correctly. Connect the wires to the clock accessory using the spade connectors (see  g. 1 for wiring con guration)
Fig. 1
Reassemble appliance, turn on electrical supply and operate accessory using instructions supplied.
1 Red Wire 2 Double Black wire 3 Black wire 4 Spare terminal 5 Blue wire
Rear view of
Time clock
Accessory
Page 28
28
installation
Electrical diagram
For increased safety, ask a quali ed technician to perform a thorough check of the electrical system.
The manufacturer is not responsible for any damage caused by the lack of a suitable earthing system or by the malfunctioning of the electricity mains supply.
Peripheral unit connection
LV connection
BUS
TB
TA2 SETNK SOL TA1
CN1
1
Display
C.H. Return temp. probe
C.H. Flow temp. probe
Thermal fuse
D.H.W. ow switch
Switch ON/OFF
Br
Rd Rd
Bl
Bl
Br
Br
Bk
Bk
Bk
BUS
- Remote Control (modulating device)
TA2/FLOOR
- Underoor heating thermostat
Room Thermostat 2
SE
- Outdoor Sensor
SOL
- Solar temperature probe
TA1
- Room thermostat 1
HV connection
CN14
CN3
1
1
CN8
CN9
1
1
CN25
1
1
CN6
N
N
FLAME
L
L
CN19
CN4
Bk
Bk
Gr
Wh
Rd
Bl
Modulating Fan
Detection electrode
Gas valve
Ignitor
Diverter valve
Circulation Pump
Bk
Bk
Bk
Bk
Br
Bl
Bk
Bl
Br
CN2
CN11
1
1
N
N
FLAME
L
L
BUSTBTA2
FLOOR
SETNK SOL TA1
CN19
CN1
CN4
1
Peripheral unit
LV connections
HV connections
CN14
CN3
1
1
CN8
CN9
1
1
CN25
1
1
CN6
CN11
1
1
CLAS HE EVO
Page 29
29
installation
Peripheral unit connection
LV connection
BUS
TB
TA2 SETNK SOL TA1
CN1
1
Display
C.H. Return temp. probe
C.H. Flow temp. probe
Thermal fuse
Switch ON/OFF
Br
Rd Rd
Bl
Bl
Br
Br
Bk
BUS
- Remote Control (modulating device)
TA2/FLOOR
- Underoor heating thermostat
Room Thermostat 2
SE
- Outdoor Sensor
SOL
- Solar temperature probe
TA1
- Room thermostat 1
HV connection
CN14
CN3
1
1
CN8
CN9
1
1
CN25
1
1
CN6
N
N
FLAME
L
L
CN19
CN4
Bk
Bk
Gr
Wh
Rd
Bl
Modulating Fan
Detection electrode
Gas valve
Ignitor
Circulation Pump
Bk
Bk
Bk
Bk
Br
Bl
CN2
CN11
1
1
N
N
FLAME
L
L
BUSTBTA2
FLOOR
SETNK SOL TA1
CN19
CN1
CN4
1
Peripheral unit
LV connections
HV connections
CN14
CN3
1
1
CN8
CN9
1
1
CN25
1
1
CN6
CN11
1
1
CLAS HE EVO SYSTEM
Page 30
30
installation
Earths omitted for clarity
R/STAT
REMOTE 2 CHANNEL PROGRAMMER
TERMINAL
STRIP
C/H
2 PORT VALVE
240V
3AMP
L
N
E
L N
Remove
Link
CYL STAT
ON OFF
L
N
H/W
2 PORT
VALVE
Boiler
HW
CH
BUS
TA2
SE
TNK SOL TA1
Note:
Boiler switching on TA1 is low voltage,
use a seperate cable to supply TA1.
Do not use 5 core cable.
MOTOR
N
L
MOTOR
ON
OFF
S plan wiring diagram.
Page 31
31
installation
Earths omitted for clarity
R/STAT
REMOTE 2 CHANNEL PROGRAMMER
TERMINAL
STRIP
C/H
2 PORT VALVE
240V
3AMP
L
N
E
L N
Remove
Links
CYL STAT
ON OFF
L
N
H/W
2 PORT
VALVE
Outside sensor
Boiler
Change parameter:
223 from 0 to 1
521 from 1 to 3
421 from 1 to 0
Activate Auto Function
BUS TA2 SETNK SOL TA1
Note: Boiler switching on TA1 & TA2 is low
voltage. Use a separate cable to supply TA1 &
TA2. Do not mix high voltage and low voltage
wires in the same cable.
MOTOR
N
L
MOTOR
ON
OFF
S plan wiring diagram using an outside sensor.
Page 32
32
commissioning
Initial preparation
Thermo UK Ltd support the benchmark initiative. On pages pages 69 and 70 of this manual the Benchmark Commissioning Checklist and Service interval Record can be found. It is important that this is completed in the presence of your customer, they are shown how to use it, and it is signed by them. Please instruct your customer that they must have this manual with them whenever they contact a service engineer or us.
Preliminary electrical system checks to ensure electrical safety must be carried out by a competent person i.e. polarity, earth continuity, resistance to earth and short circuit.
Electricity supply
- Check that the voltage and frequency of the electricity supply correspond to the data shown on the boiler data plate;
- Make sure that the earthing connection is e cient.
Filling the Heating System:
Remove the front casing panel and lower the control panel as described on page 15). Open the central heating flow and return cocks supplied with the connection kit; Lift the cap on the automatic air release valve and leave open permanently; Close all air release valves on the central heating system; Gradually open the valves at the filling point (filling loop) until water is heard to flow, do not open fully; Open each air release tap starting with the lowest point and close them only when clear water free of air is visible; Purge the air from the pump by unscrewing the pump plug anti­clockwise, also manually rotate the pump shaft in the direction indicated by the pump label to ensure the pump is free; Refit the pump plug; Continue filling the system until at least 1.5 bar registers on the pressure gauge; Inspect the system for water tightness and remedy any leaks discovered.
I
MPORTANT!
MANUALLY VENT THE HEAT EXCHANGER AT THE MANUAL AIR VENT. FAILURE TO
VENT ADEQUATELY MAY DAMAGE THE HEAT EXCHANGER (PAGE 7, LEGEND 2).
Filling of the DHW System:
Close all hot water draw off taps; Open the cold water inlet cock supplied with the connection kit; Slowly open each draw off tap and close them only when clear water, free of bubbles, is visible.
Gas Supply:
Inspect the entire installation including the gas meter and test for tightness. The entire installation should be in accordance with the relevant standards. In GB this is BS 6891 and in IE this is the current edition of I.S.813.
The connection on the the appliance is a 15mm (22mm on 38Kw) nut and olive located at the rear of the gas service cock.
If the gas supply serves other appliances, ensure that an adequate supply is available both to the boiler and the other appliances when they are in use at the same time.
Pipe work must be of an adequate size. The final pipe size must not be smaller than the appliance inlet size.
Open the gas cock (supplied with the connection kit) to the appliance and check the gas connection on the appliance for leaks.
Water Treatment:
The boiler is equipped with a stainless steel heat exchanger. The detailed recommendations for water treatment are given in BS 7593:1992 (Treatment of water in domestic hot water central heating systems); the following notes are given for general guidance;
If the boiler is installed on an existing system, any unsuitable additives must be removed;
Under no circumstances should the boiler be fired before the system has been thoroughly flushed; the flushing procedure must be in line with BS7593:1992.
Firstly fill the central heating system with the power off, and flush through cold, fill the central heating system again, adding a flushing detergent, run the boiler on central heating until it reaches its operating temperature and flush the system, refill the system with a suitable corrosion inhibitor,
N
OTE: FAILURE TO CARRY OUT THE FLUSHING PROCEDURE WILL RESULT IN THE
WARRANTY BECOMING VOID.
Page 33
33
commissioning
FIRST IGNITION OPERATION
1. Check the electrical supply.
Complete . . . . . . . . . . . . . . . . . . .
Date . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installer . . . . . . . . . . . . . . . . . . . . . . . . . .
2. Check the type of gas and change the gas if necessary.
Complete . . . . . . . . . . . . . . . . . . .
3. Check the gas tightness.
Complete . . . . . . . . . . . . . . . . . . .
4. Measure the gas inlet.
Complete . . . . . . . . . . . . . . . . . . .
5. Check the Flue
Complete . . . . . . . . . . . . . . . . . . .
6. Fill the installation.
Complete . . . . . . . . . . . . . . . . . . .
7. Check the hydraulic water tightness.
Complete . . . . . . . . . . . . . . . . . . .
8. Spin the pump.
Complete . . . . . . . . . . . . . . . . . . .
9. Purge the air with once pressing on ESC button during 5 sec.
Complete . . . . . . . . . . . . . . . . . . .
10. Set the heating power.
Complete . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11. Balance the central heating circuit.
Complete . . . . . . . . . . . . . . . . . . .
12. Check the operation in DHW mode.
Complete . . . . . . . . . . . . . . . . . . .
13. Adjust DHW  ow rate on the boiler (if necessary).
Complete . . . . . . . . . . . . . . . . . . .
15. Check gas rate.
Complete . . . . . . . . . . . . . . . . . . .
14. Check combustion by pressing the RESET button for 5 sec.
Complete . . . . . . . . . . . . . . . . . . .
16. Check the ionisation current.
Complete . . . . . . . . . . . . . . . . . . .
17. Explain to the end user the working of the boiler.
Complete . . . . . . . . . . . . . . . . . . .
Page 34
34
commissioning
Ignition procedure
Press the ON/OFF button on the control panel to switch on the boiler. The display shows:
the operating mode:
winter
summer
Only heating - CLAS HE EVO SYSTEM
The  gures indicate:
-
the  ow temperature when no heating requests have been made
- the  ow temperature in central heating mode
-
the temperature of the hot water set in domestic hot water
The carrying out of certain functions is shown:
Deaeration cycle started
Centrl Heating Post-circulation
D.H.W. circuit Post-circulation
Electricity supply
- Check that the voltage and frequency of the electricity supply correspond to the data shown on the boiler data plate;
- Make sure that the earthing connection is e cient.
First ignition
1. Make sure that:
- The gas valve is closed;
- The electrical connection has been properly carried out. Make sure that, in any case, the green/yellow earthing wire is connected to an e cient earthing system;
- Use a screwdriver to lift the cap on the automatic air relief valve;
- Switch on the boiler (by pressing the ON/OFF button) and use the M
ODE button to select the standby
mode, where no hot water or heating requests are made.
- Start the deaeration cycle by pressing ESC for 5 seconds
The boiler will start a deaeration
cycle lasting about 7 minutes (See below). If you need to stop it press E
SC, alternatively it is possible to manually vent the heat
exchanger.
- At the end, check that the system is completely deaerated and, if not, repeat the procedure.
- Bleed the air from the radiators;
- The exhaust duct for combustion products should be suitable and free from any obstructions;
- Any necessary ventilation inlets in the room should be open (type B installation).
- Check whether the condense trap contains water; if not, it must be re lled.
N.B.: if the boiler will not be used for long periods, the
trap should be  lled before the boiler is started up again. It is dangerous not to re ll the siphon as fumes may be
released into the environment.
2. Open the gas cock and check the connection seals, including
the boiler connection joints, making sure that the meter does not detect any passage of gas. Eliminate any leaks.
3. Start the boiler by selecting the heating or domestic hot water operation using the M
ODE button.
Description of Function Deaeration cycle
During the  lling stage or if there is excess air in the system, the deaeration cycle can be activated by holding the OK button for 5 seconds. The boiler will start a cycle which lasts approximately 7 minutes. When this is complete the menu screen will be restored. The cycle may either be repeated, if necessary, or stopped by pressing OK. Press the OK button until the normal display screen is restored. I
F THE CYCLE IS STOPPED BE SURE TO MANUALLY VENT THE APPLIANCE.
Page 35
35
commissioning
Combustion checking procedure
The order of operations for this procedure must always be respected.
Operation 1 - Supply pressure check
Loosen the screw 1 and insert the pressure gauge connection pipe into the pipe tap. Switch the boiler on at maximum power. To activate combustion test function:
- Press the mode selector to ensure the +
icons displayed.
- Pres & hold the reset button for 10 seconds. ‘Test’ will appear on the screen. Ensure the boiler is on max power by rotating the encoder.
The supply pressure should correspond to the value established in relation to the type of gas ,for which the boiler is designed see Table summarising changes.
Operation 2 - Preparing the measuring equipment
Connect the calibrated  ue gas analyser to the left-hand combustion outlet by unscrewing the screw and removing the blanking cover.
Operation 3 - Adjusting the CO2 at maximum gas  ow rate (domestic hot water)
Draw o the domestic hot water at the maximum water  ow rate (if a combi). Select the Test function by pressing the RESET button for 10 seconds.
WARNING! When the cleaning function is activated, the temperature of the water coming out of the boiler may be more than 65°C.
On the display appear TEST and the icon . The boiler is
foced to the maximum heating power.
Rotate the encoder
to forced the boiler at the maximum DHW power. On the
display appear the icon
. Wait 1 minute for the boiler to stabilise before carrying out the combustion analyses.
Read the CO2 value (%) and compare it with the values given in the table below N.B.: values with the casing closed.
If the CO2 value (%) read di ers from the values given in the table, then adjust the gas valve following the instructions below, otherwise move directly onto operation 4.
Adjusting the gas valve at maximum gas  ow
Adjust the gas valve by turning setting screw 4 clockwise in increments to reduce the CO2 level (a 1 turn adjusts the CO2 level by approximately 0.2%). Wait 1 minute after each change in setting for the CO2 value to stabilise. If the value measured corresponds to the value given in the table, max adjustment is complete, otherwise start the setting procedure again. N.B. The Test function is automatically deactivated after 10 minutes or manually by brie y pressing the RESET button.

18 24 30 38
Gas CO2 (%) G20 9,0±0,2 G31 10,0±0,2
Page 36
36
commissioning
Operation 4 - Checking the CO2 at minimum gas  ow
With the Test function active, rotate the encoder to select the icom
and . The boiler is forced to the minimum power. Wait 1 minute for the boiler to stabilise before carrying out the combustion analyses. If the
CO2 value (%) read di ers by 0.5 % from the value found, then adjust the gas valve following the instructions below, otherwise move directly onto operation 5.
Adjusting the gas valve to minimum gas  ow
Remove cap and adjust screw 2 by turning anti-clockwise in increments to reduce the CO2 level. Wait 1 minute after each adjustment for the CO2 value to stabilise. WARNING! this adjustment is sensitive: a rotation of a 1 turn corresponds to 0.2% of CO2. If the value measured corresponds to the value given in the table, adjustment is complete, otherwise start the setting procedure again.
Attention! If the value of the CO2 at the minum power has been changed, it is necessary repet the adjusting at maximum gas  ow.
Operation 5 - Ending the adjustment
Exit cleaning mode by pressing RESET. Stop the draw-o . Verify and repair any leaks of gas. Re t the front panel to the device. Re t the blanking cover at combustion test point.
menu 2 - Boiler parameters submenu 3 - parameter 1 Maximum Heating Power adjustment submenu 2 - parameter 0
Soft light Ignition
submenu 3 - parameter 5 Heating ignition delay
Maximum Heating Power adjustment
The maximum heating power can be adjusted to between the maximum power allowed by the boiler and the minimum power). The display shows the value between 100% (“100” on the display) and 0% (“0”) of this interval. To check the maximum heating power, access menu 2/sub menu 3/parameter 1, check the value and, if necessary, modify it as indicated in the Gas Regulation table below. (See page 40 for more details).
Checking slow ignition power
The soft light can be adjusted between the maximum power (shown on the display as “100”, i.e. 100%) and the minimum power (shown on the display as “1”, i.e. 1%). To check the slow ignition power, access menu 2/sub menu 2/ parameter 0.
Heating ignition delay adjustment
This parameter – menu 2/sub menu 3/parameter 5 - can be used to manually (0) or automatically (1) set the delay time before the subsequent reignition of the burner after it has switched o on reaching the desired temperature in central heating mode. By selecting manual, it is possible to set the delay in minutes using the successive parameter (menu 2/sub menu 3/parameter 6), to a time between 0 and 7 minutes. Automatic selection means that the boiler will establish the delay time based on the set-point temperature
Converting the appliance from Natural gas to LPG
These appliances are designed to operate with di erent gas types. The appliance must only be converted for use with a di erent gas type by a Gas Safe Registered installer. To convert the appliance to LPG:
(use these instructions in conjunction with the Instruction sheet supplied with the LPG Kit).
1. Electrically isolate the appliance
2. Turn o the gas supply ( g 1)
3. Remove the outer case, lower the front control panel and remove the front combustion chamber panel.
4. Remove the green silencer ( g 2)
5. Disconnect the gas supply from the venturi assembly ( g 3)
6. Inset the correct diaphragm (depending on the output of the appliance) into the venturi spigot
7. Reassemble the gas supply onto the venture assembly ( g 4)
8. Turn on gas supply and test for tightness
9. Purge gas supply
10. Turn the electrical supply on to the appliance.
11.Commission the appliance, check the working pressure is adequate then test and adjust the CO values at maximum and minimum output described in the commissioning section of the appliance installation instructions. Ensure the  ue gas analyser used is calibrated and set for the gas group the appliance is being adjusted for.
12. Check the appliance for gas leaks using gas leak detection  uid.
13. A x the label to the appliance that is supplied with the conversion kit.

CLAS HE EVO 38 CLAS HE EVO 30 CLAS HE EVO SYSTEM 30 CLAS HE EVO 24 CLAS HE EVO SYSTEM 24 CLAS HE EVO SYSTEM 18
1
2
3
4
Page 37
37
commissioning
parameter
CLAS HE EVO
CLAS HE EVO SYSTEM
18 24 30 38
G20 G31 G20 G31 G20 G31 G20 G31
Lower Wobbe index (15°C, 1013 mbar) ( MJ/m3) 45,67 70,69 45,67 70,69 45,67 70,69 45,67 70,69
Slow ignition 220 55 55 60 60 Minimum fan speed (%) 233 19 18 18 19 Maximum central heating fan speed (%) 234 85 76 78 78 Maximum D.H.W fan speed (%) 232 85 91 86 93 Maximum heating power adjstment 231 55 55 60 60 Gas valve restrictor (ø) 3.8 2.9 5.0 3.6 5.7 4.3 6.6 5.0
Gas  ow max/min (15°C, 1013 mbar) (nat - m3/h) (GPL - kg/h)
max D.H.W 1.90 1.40 2.75 2.02 3.17 2.33 4.02 2.95 max C.H 1.90 1.40 2.33 1.71 2.96 2.17 3.28 2.41 min 0.48 0.35 0.58 0.43 0.69 0.50 0.79 0.58
Table summarising changes
AUTO function
This is a function which enables the boiler to automatically adapt its operation routine (the temperature of the heating elements) in line with the outdoor conditions, in order to achieve and maintain the requested room temperature conditions. Depending on the peripheral units connected and the number of zones controlled, the boiler adjusts its  ow temperature automatically. The various corresponding parameters should therefore be set (see adjustments menu). To activate the function, press the A
UTO button.
Example 1:
Single zone system (high-temperature) with on/o room Thermostat:
In this case the following parameters must be set: 4 21 - Activation of temperature adjustment using sensors
- Select 1 = Basic temperature adjustment 2 44 - Boost Time (optional) The wait time for the  ow temperature increase in steps of
4°C may be set. The value varies according to the type of system and installation.
If the Boost Time value = 00 the function is not activated.
Example 2:
Single zone system (high-temperature) with on/o room Thermostat + outdoor sensor:
In this case the following parameters must be set: 4 21 - Activation of temperature adjustment using sensors
- Select 3 = outdoor sensor only 4 22 - Temperature adjustment curve selection
- Select the relevant curve according to the type of system, installation, heat insulation used in the building, etc.
4 23 - Perform a parallel curve shift if necessary, increasing or
decreasing the set-point temperature (this may also be modi ed by the user, using the heating temperature adjustment knob, which, with the Auto function activated, is used to shift the curve in a parallel manner).
Example 3:
Single zone system (high-temperature) with REMOCON remote Control + outdoor sensor
In this case the following parameters must be set: 4 21 - Activation of temperature adjustment using sensors
- select 4 = outdoor sensor + room sensor 4 22 - Temperature adjustment curve selection
- Select the relevant curve according to the type of system, installation, heat insulation used in the building, etc
4 23 - Perform a parallel curve shift if necessary, increasing or
decreasing the set-point temperature. (This may also be changed by the user by the encoder which, with the Auto function activated, is used to shift the curve in a parallel manner.)
4 24 - In uence of room sensor
- used to adjust the in uence the room temperature has on the calculation of the set-point  ow temperature (20 = maximum, 0 = minimum).
Note: See page 39 for details on accessing menus.
Page 38
38
boiler protection devices
Boiler protection devices
The boiler is protected from malfunctioning by means of internal checks performed by the electronic microprocessor P.C.B., which stops the boiler from operating if necessary. In the event of the boiler being shut o in this manner, a code appears on the display which refers to the type of shut-o and the reason behind it. There are two types of shut-o :
Safety shut-o
This type of error is “volatile”, which means that the boiler starts up again automatically as soon as the prob­lem which caused the shut-o is re­moved; the error is indicated by the «Err» symbol which appears on the display and the error code. In fact, soon as the cause of the shut­o disappears, the boiler starts up again and continues to operate nor­mally.
In the event of error 1 08 - Shut-o due to insu cient water pressure inside the heating circuit - the boiler will perform a safety shut-o . You can increase the pressure by  lling the heating circuit. In this case or if the re-balancing request is performed on a frequent basis, switch the boiler o , turn the external electric switch to the OFF position, shut o the gas cock and contact a quali ed technician to check for any leaks of water.
Shutdown
This type of error is “non-volatile”, which means that it is not removed automatically. To restore normal operation press the
button on the control panel.
Malfunction warning
This warning is shown by the display in the following format: 5 P1 = FIRST IGNITION ATTEMPT UNSUCCESSFUL the  rst  gure indicating the operational assembly is followed by a P (warning) and the code relating to the speci c warning.
Important
If this shutdown occurs frequently, contact an authorised Technical Service Centre for assistance. For safety reasons, the boiler will permit a maximum of 5 resets in 15 minutes (5 presses of the RESET button); at the 6th attempt within this 15-minute period the boiler will shut down and may only be operated again after the electricity supply has been disconnected. If the shutdown is occasional or an isolated event, this is not a problem.
The  rst  gure of the error code (e.g. 1 01) indicates within which operational assembly the error occurred. 1 - Primary Circuit 2 - Domestic Hot Water Circuit 3 - Internal Electronic Part 4 - External Electronic Part 5 - Ignition and Detection 6 - Air inlet -  ue gas outlet 7 - Multi-zone Heating
Table summarising error codes
Central Heating circuit
Display Description
1 01
Overheat
1 02
Pressure Sens Error
1 03
Insu cient circulation
1 04 1 05 1 06 1 07 1 08
Insu cient water (request  lling)
1 10
C.H. Flow temp. probe circuit open / short circuit
1 12
C.H. Return temp. probe circuit open / short circuit
1 14
External sensor circuit open / short circuit
1 16
Floor Thermostat contact open
1 18
Heating delevery probe problem
1 P1
Insu cient circulation indication
1 P2
1 P3
D.H.W. circuit
2 02
Bottom storage temperature probe open / short circuit
Solar kit
(optional)
2 04
Solar collector temperature probe open / short circuit
2 07
Solar collector overheating
2 08
Collector frost protection temperature
Internal P.C.B.’s
3 01
EEPROM error
3 02
Comunication error
3 03
Main P.C.B. error
3 04
Too many (> 5) resets in 15 minutes
3 05
Main P.C.B. error
3 06
Main P.C.B. error
3 07
Main P.C.B. error
External P.C.B.’s
4 07
Room sensor circuit open/short circuit
Ignition and Detecion
5 01
No  ame detected
5 02
Flame detected with gas valve closed
5 04
Flame lift
5 P1
1st Ignition Failed
5 P2
2nd Ignition Failed
5 P3
Flame cut-o
Air Inlet / Flue gas outlet
6 04
Insu cient fan speed
6 10
Thermofuse open
Page 39
39
boiler protection devices
Anti-frost Device.
The anti-frost function acts on the central heating  ow temperatu­re probe, independently from other regulations, when the electri­cal supply is turned on. If the primary circuit temperature is between 3°C and 8°C the pump will run (with the diverter valve switching between central heating and hot water every 1 minute) until the temperature reaches > 9°C. If the  ow temperature remains between 3°C and 8°C the pump will continue to run for a maximum of 20 minutes unless a temperature above > 9°C is detected in the central heating  ow, after this the the burner will  re (heating position) until a temperature of > 30°C is detected. If the central heating  ow temperature is < 3°C, the burner will  re (heating position) at minimum power until the temperature rea­ches > 30°C, the burner will go out. If lockout is caused by overheat the burner will not  re but the pump will continue to run (heating position). The anti-frost device activates only when (with the boiler opera­ting correctly):
- the system pressure is correct;
- the boiler is electrically powered;
- there is a supply of gas.
Multi-zone Heating (Heating Zone Modules - optional)
7 01
Zone 2 outgoing sensor defective
7 02
Zone 2 return sensor defective
7 03
Zone 3 outgoing sensor defective
7 04
Zone 3 return sensor defective
7 05
Hydraulic separation sensor defective
7 06
Zone 2 overheating
7 07
Zone 3 overheating
Page 40
40
settings - adjustment - problem identi cation menus
Accessing the settings - adjustment - problem identi cation menus
The boiler can be used to manage the heating and domestic hot water production system in its entirety. Navigation within the menus enables the boiler system + connected peripheral units to be customised, optimising operation for maximum comfort and maximum saving. It also provides important information relating to the e cient operation of the boiler.
Before access to the menus, the display show some “quick settings” to have direct access to the parameters. To see all available parameters and menu access to view FULL MENU.
GAS - Direct access to the parameters:
220 - 231- 232- 233 - 234 - 270
SET - Direct access to the parameters:
220 - 231- 223 - 245 - 246
PCB - Direct access to the parameters:
220 - 228 - 229 - 231- 232- 233 - 234 - 247 - 250 - 253
VIS - Direct access to the parameters:
821 - 822 - 824 - 825 - 827 - 830 - 831 - 832 - 833- 840 - 835
ZONE - Direct access to the parameters:
402 - 502 - 602 - 420 - 520 - 620 -434 - 534 - 634 - 830
FULL MENU - see table on following pages
0 NETWORK
0 4 User Interface
2 Boiler Parameter
2 0 General setting 2 2 General setting 2 3 C.H. Parameters - Part 1 2 4 C.H. Parameters - Part 2 2 5 Domestic Hot Water 2 6 Boiler manual settings 2 7 Test & Utilities 2 8 Menù 2 Reset to factory setting
4 Zone 1 Parameters
4 0 Set-point Zone1 4 2 Zone 1 Setting 4 3 Diagnostics
5 Parametri Zona 2
5 0 Set-point Zone2 5 2 Zone 2 Setting 5 3 Diagnostics
6 Parametri Zona 3
6 0 Set-point Zone3 6 2 Zone 3 Setting 6 3 Diagnostics
8 Service Parameter
8 1 Statistics 8 2 Boiler 8 3 Boiler Temperature 8 4 Solar & Storage 8 5 Service 8 6 Error History
The parameters relating to each individual menu are listed in the following pages. The various parameters can be accessed and modi ed using the OK button and the encoder (see  g. below). The description of the menus and of each individual parameter will be shown on the display.
6. ESC button
7. “encoder” programming knob
8. OK button programming key
6
7
8
To access the Menus, proceed as follows (for example: “
231
231”:
1. Simultaneously press the
ESC button and OK button for 5
seconds; the display show
CODE
and
222
.
Caution! The menus reserved for quali ed technicians may only
be accessed after setting the access code.
2. Turn the encoder
in a clockwise direction to select code
234
3. Press the OK button; the display show the  rst “quick setting”
GAS
4. Turn the encoder to select
MENU
;
5. Press the OK button; the dispaly show the menu
0
.
6. Turn the encoder
in a clockwise direction to select the menu 2
7. Press the OK button to access to the menu. The display show the sub-menu
20
8. Turn the encoder to select a sub menu 23;
9. Press the OK button to access the sub menu parameters; the display show
230
10. Turn the encoder to select a parameter
231
11. Press the OK button to access the parameter; the display will indicate the value, e.g “
70
”.
Note: The parameter value will be displayed for 20 seconds, then
will begin to  ash in alternation with the parameter, e.g. “
70
>
231
“.
12. Turn the encoder
to select the new value, e.g. “
75
”.
13. Press OK button to save the change or press ESC to exit without saving.
To exit, press the E
SC button until the normal display screen is restored.
For menus which do not require the access code, it is possible to pass directly from the menu to the sub menu.
Page 41
41
settings - adjustment - problem identi cation menus
menu
sub-menu
Parameter
Description value
default setting
SERVICE CODE
Rotate encoder clockwise to select code 234 and press O
K. Turn the encoder to select MENU and press OK button
0 NETWORK
0 4 DISPLAY SETTING
040Zone to be set by display 1 = 1 Zone
2 = 2 Zone 3 = 3 Zone
1
041
Backlight timing
from 0 to 10 (minutes) or 24 (hour)
24
042Thermoregulation button deactivation 0 = OFF
1 = ON
0
2 BOILER PARAMETER SETTING
2 0 GENERAL
200
DHW Setpoint Temperature from 36 to 60 (°C) Setting by DHW button 1
2 2 BOILER GENERAL SETTINGS 220Soft ignition from 0 to 90 60 See parag. Gas settings
223Under oor thermostat or zone 2 ambient
thermostat selection
0 = Floor safety thermostat 1 = Zone 2 ambient thermostat
0
224Thermoregulation 0 = Absent
1 = Present
0
225Heating ignition delay 0 = Deactivated
1 = 10 seconds 2 = 90 seconds 3 = 210 seconds
0
228Boiler Version - CLAS HE EVO
CANNOT BE MODIFIED
from 0 to 5 0
RESERVED FOR TECHNICAL ASSISTANCE Only if the PCB is changed
Boiler Version - CLAS HE EVO SYSTEM CANNOT BE MODIFIED
from 0 to 5 2
229
Set boiler heat power
2 3 BOILER PARAMETER  PART 1 231Maximum heating power setting from 0 to 99 60 see the “Gas setting” table,
information on Starting
232Domestic hot water maximum percentage
CANNOT BE MODIFIED
from 0 to 99
RESERVED FOR TECHNICAL ASSISTANCE Only if the gas or PCB is changed see “gas setting” table
233Minimum percentage
CANNOT BE MODIFIED
from 0 to 99
234Heating maximum percentage
CANNOT BE MODIFIED
from 0 to 99
235Selection of ignition delay type when
heating
0 = Manual 1 = Automatic
1
236Ignition delay when heating timer setting from 0 to 7 (minutes) 3 237Post-circulation when heating from 0 to 15 minutes or OC (AC) 3
238
Pump speed control 0= Low speed
1= High speed 2= Modulating
2
239Set Delta T Pump from 10 to 30 °C 20
Parameter to set if Pump Speed control (237) is setted on modulating ΔT ( ow - return) for circulation pump modulation This parameter can be used to set the di erence between the  ow and return temperatures, which determines the commutation between low and high circulation pump speed. E.g.: param. 14 = 20 if the T ow - Tret > 20°C; the circulation pump will be activated at maximum speed. If the T ow - Tret < 20 - 2°C; the circulation pump will be activated at minimum speed. The minimum wait time between speed changes is 5 minutes.
Page 42
42
settings - adjustment - problem identi cation menus
menu
sub-menu
Parameter
Description value
default setting
2 4 BOILER PARAMETER  PART 2 243Post-ventilation after heating request 0 = OFF
1 = ON
0
244Time delay after heating temperature
increase
from 0 to 60 (minutes)
16 Activated only with thermostat On/
O and heating control activated (parameter 421 - 521 - 621 = 01)
This parameter allows the time delay to be set before automatic increase of the  ow temperature calculated in increments of 4°C (max 12°C). If this parameter retains the value 00, this function is not active.
245<Not Available> 246<Not Available> 247Device indicator for heating circuit pressure 0 = temperature sensor only
1 = pressure switch at minimum 2 = pressure sensor
1 RESERVED FOR TECHNICAL
ASSISTANCE
Only if the PCB is changed
248<Not Available> 249External temperatura correction from -3 to +3 (°C) 0 Only active with external sensor
connected
2 5 DOMESTIC HOT WATER PARAMETER 250COMFORT function
CLAS HE EVO
0 = deactivated 1 = timed 2 = always on
0 Timer = activated for 30 minutes
after domestic hot water draw-o
The appliance allows the hot water heating comfort to be increased via the “COMFORT” function. This function keeps the secondary exchanger temperature stable when the boiler is not in use. When the function is active, the display shows COMFORT Note: this function can be activated and deactivated by pressing the COMFORT button
251Comfort Anti-cycling Time
CLAS HE EVO
from 0 to 120 (minutes) 0
252Hot water  ow delay
CLAS HE EVO
from 5 to 200 (0.5 to 20 seconds) 5 Anti “water hammering”
253Extinction of the burner in D. H. W.
CLAS HE EVO
0 = anti-scale (stop at > 67°C) 1 = + 4°C /setting
0
254Post-circulation and post-ventilation after a
domestic hot water draw-o
0 = OFF 1 = ON
0
OFF = 3 minutes post-circulation and post-ventilation after domestic hot water draw-o
if the boiler temperature measured requires it.
ON = always on for 3 minutes post-circulation and post-ventilation after domestic hot
water draw-o .
255Domestic hot water timer from 0 to 30 (minutes) 0
257<Not Available> 258<Not Available>
2 6 BOILER MANUAL SETTINGS Only to test components 260Manual mode activation 0 = OFF
1 = ON
0
261Boiler pump control 0 = OFF
1 = ON
0 Set parameter 260=1
262Fan control 0 = OFF
1 = ON
0 Set parameter 260=1
2633 way valve control 0 = Sanitary
1 = Heating
0 Set parameter 260=1
264<Not Available>
Page 43
43
settings - adjustment - problem identi cation menus
menu
sub-menu
Parameter
Description value
default setting
2 7 TEST & UTILITIES
270
Test mode TEST+ = Max Heating power
TEST+ = Max DHW power TEST+
=
Minimum power.
activation can also be obtained by pressing the Reset button for 10 seconds. The function is deactivated after 30 minutes or by pressing Reset
271Bleed cycle press OK button for 5 seconds see First Ignition parag.
2 8 RESET MENU’ 2 280Automatically resetting to the default
setting in menu 2
Reset OK = yes ESC = no
To reset all default parameter settings, press the OK button
4 ZONE 1 PARAMETER
4 0 ZONE 1 TEMPERATURE SETTING 402Heating  xed temperature setting
“Heating  xed temp”
from 35 to 82 °C (high temperature - para. 420 =1)
70 Activated only with temperature
control and  xed temperature (see 421)
from 20 to 45 °C (high temperature - para. 420 =0)
20
4 2 ZONE 1 SETTING 420Heating appliance temperature value
setting
0 = from 20 to 45°C (low temperature) 1 = from 35 to 85°C (high temperature)
select in the appliance type base
421Basic heating control type selection type
depending on the peripheral devices connected
0 =  xed  ow temperature 1 = device On/O 2 = room sensor 3 = external sensor only 4 = room sensor + external sensor
1 To activate heating control, press
the AUTO button. The display lights up the AUTO symbol
422Slope from 0_2 to 0_8 (low temperature)
from 1_0 to 3_5 1_5 (high temperature)
Flow T emperature
Low temperature High temperature
External temperature
Ambiente temperature
setting value
°C
20
25
15
30
40
50
60
70
80
90
100 °C
10
2.5 3.0 3.5 2.0
1.5
1.2
1.0
0.8
0.6
0.4
0.2
5 0 -5 -10 -15 -20 °C
If the external sensor is used, the boiler calculates the most suitable heating  ow temperature taking the external temperature and the type of appliance into account. The type of curve must be chosen according to the type of appliance radiator and the heat losses present in the building.
Page 44
44
settings - adjustment - problem identi cation menus
menu
sub-menu
Parameter
Description value
default setting
423Parallel shift from - 7 to + 7 (low temperature) 0
from - 14 to + 14
(high temperature)
To adapt the thermal curve to the appliance requirements, it is possible to perform a parallel shift of the curve in order to alter the calculated  ow temperature and therefore the ambient temperature. By accessing this parameter or pressing the buttons 12 the curve can be shifted in a parallel manner as indicated in the  gure shown below. The value is indicated on the display:
- from -7 to +7
(low temperature)
- from -14 to +14
(high temperature)
Each step represents a  ow temperature increase/decrease of 1°C in relation to the set-point value.
424Compensation from 0 to 20 20
if setting = 0, the temperature taken from the ambient sensor does not a ect the calculation of the setting. If setting = 20, the temperature taken has maximum in uence on the setting.
425Zone 1 heating MAXIMUM temperature
setting
from 35 to 85 °C 82 if parameter 420 = 1 from 20 to 45 °C 45 if parameter 420 = 0
426Zone 1 heating MINIMUM temperature
setting
from 35 to 85 °C 35 if parameter 420 = 1 from 20 to 45 °C 25 if parameter 420 = 0
4 3 DIAGNOSTICS 434Zone 1 heat request 0 = OFF
1 = ON
5 ZONE 2 PARAMETER
5 0 ZONE 2 TEMPERATURE SETTING 502Heating  xed temperature setting
“Heating  xed temp”
from 35 to 82 °C (high temperature - para. 420 =1)
70 Activated only with temperature
control and  xed temperature (see
521)
from 20 to 45 °C (high temperature - para. 420 =0)
20
5 2 ZONE 2 SETTING 520Heating appliance temperature value
setting
0 = from 20 to 45°C (low temper ature) 1 = from 35 to 85°C (high temperature)
1 select in the appliance type base
521Basic heating control type selection type
depending on the peripheral devices connected
0 =  xed  ow temperature 1 = device On/O 2 = NOT PRESENT 3 = external sensor only 4 = NOT PRESENT
1 To activate heating control, press
the AUTO button. The display lights up the AUTO symbol
522Slope from 0_2 to 0_8 (low temperature)
from 1_0 to 3_5 1_5 (high temperature)
- see graph on the previous page If the external sensor is used, the boiler calculates the most suitable heating  ow temperature taking the external temperature and the type of appliance into account. The type of curve must be chosen according to the type of appliance radiator and the heat losses present in the building.
523Parallel curve shift Zone 2 O set from - 7 to + 7 (low temperature) 0
from - 14 to + 14
(high temperature)
To adapt the thermal curve to the appliance requirements, it is possible to perform a parallel shift of the curve in order to alter the calculated  ow temperature and therefore the ambient temperature. By accessing this parameter or pressing the buttons 12 the curve can be shifted in a parallel manner as indicated in the  gure shown below. The value is indicated on the display:
- from -7 to +7
(low temperature)
- from -14 to +14
(high temperature)
Each step represents a  ow temperature increase/decrease of 1°C in relation to the set-point value.
Page 45
45
settings - adjustment - problem identi cation menus
menu
sub-menu
Parameter
Description value
default setting
524Compensation from 0 to 20 20 if setting = 0, the temperature
taken from the ambient sensor does not a ect the calculation of the setting. If setting = 20, the temperature taken has maximum in uence on the setting.
525Zone 2 heating MAXIMUM temperature
setting
from 35 to 85 °C 82 if parameter 520 = 1 from 20 to 45 °C 45 if parameter 520 = 0
526Zone 2 heating MINIMUM temperature
setting
from 35 to 85 °C 35 if parameter 520 = 1 from 20 to 45 °C 25 if parameter 520 = 0
5 3 DIAGNOSTICS
534Zone 2 heat request 0 = OFF
1 = ON
6 ZONE 3 PARAMETER 6 0 ZONE 3 TEMPERATURE SETTING 602Heating  xed temperature setting
“Heating  xed temp”
from 35 to 82 °C (high temperature - para. 420 =1)
70 Activated only with temperature
control and  xed temperature (see
621)
from 20 to 45 °C (high temperature - para. 420 =0)
20
6 2 ZONE 3 SETTING 620Heating appliance temperature value
setting
0 = from 20 to 45°C (low temper ature) 1 = from 35 to 85°C (high temperature)
1 select in the appliance type base
621Basic heating control type selection type
depending on the peripheral devices connected
0 =  xed  ow temperature 1 = device On/O 2 = NOT PRESENT 3 = external sensor only 4 = NOT PRESENT
1 To activate heating control, press
the AUTO button. The display lights up the AUTO symbol
622Slope from 0_2 to 0_8 (low temperature)
from 1_0 to 3_5 1_5 (high temperature)
- see graph on page 42 If the external sensor is used, the boiler calculates the most suitable heating  ow temperature taking the external temperature and the type of appliance into account. The type of curve must be chosen according to the type of appliance radiator and the heat losses present in the building.
623Parallel curve shift Zone 2 O set from - 7 to + 7 (low temperature) 0
from - 14 to + 14
(high temperature)
To adapt the thermal curve to the appliance requirements, it is possible to perform a parallel shift of the curve in order to alter the calculated  ow temperature and therefore the ambient temperature. By accessing this parameter or pressing the buttons 12 the curve can be shifted in a parallel manner as indicated in the  gure shown below. The value is indicated on the display:
- from -7 to +7
(low temperature)
- from -14 to +14
(high temperature)
Each step represents a  ow temperature increase/decrease of 1°C in relation to the set-point value.
624Compensation from 0 to 20 20 if setting = 0, the temperature taken
from the ambient sensor does not a ect the calculation of the setting. If setting = 20, the temperature taken has maximum in uence on the setting.
625Zone 3 heating MAXIMUM temperature
setting
from 35 to 85 °C 82 if parameter 620 = 1 from 20 to 45 °C 45 if parameter 620 = 0
626Zone 3 heating MINIMUM temperature
setting
from 35 to 85 °C 35 if parameter 620 = 1 from 20 to 45 °C 25 if parameter 620 = 0
Page 46
46
settings - adjustment - problem identi cation menus
menu
sub-menu
Parameter
Description value
default setting
6 3 DIAGNOSTICS 634Zone 3 heat request 0 = OFF
1 = ON
8 SERVICE PARAMETERS
81
BOILER STATISTICS
810Number of hours burner operating in heater mode (xxh/10) 811Number of hours burner operating in hot water mode (xxh/10) 812Number of  ame separations (nr/10) 813Number of ignition cycles (nr/10) 814Average length of heating request (minutes)
8 2 BOILER 821Fan Status 0 = OFF
1 = ON
822
Fan speed (x100) rpm
823Circulation pump speed 0 = OFF
1 = Low speed 2 = High speed
824Diverter valve position 0 = D.H.W.
1 = Central Heating
825D.H.W. Flow Rate (l/min) 828Gas Power (kW)
8 3 BOILER TEMPERTURE 831Heating  ow temperature (in °C) 832Heating back ow temperature (in °C)
8 4 SOLAR & STORAGE
842Solar appliance water input temperature activated only with the solar kit
connected
8 5 SERVICE
850Months to next maintenance from 0 to 60 (month) 24
If setted the boiler will display that is time to call the installer for maintenance
851Enable Maintenance advice 0 = OFF
1 = ON
0
852Maintenance Warning Reset Reset? OK= Yes Esc = No
to erase the advice for maintenance
8532nd Heat Exchanger Clogging State 0 = DHW Exchanger OK
1 = Partially Clogged 2 = Very Clogged Please Replace
854
PCB hardware version
855PCB software version
8 6 ERROR LIST 86010 last errors from E00 to E99
This parameter allows the last 10 boiler errors  agged to be displayed, indicating the day, month and year. When the parameter is accessed, the errors are displayed listed from E00 to E99. For each error, the following sequence is displayed: E00 - error number 108 - error code
861Error list reset Reset
OK = yes ESC = no
Page 47
47
maintenance
Important
Maintenance is an essential part of the safe and e cient operation of the boiler and ensures its durability. It should be performed according to the instructions given in current legislation. Perform combustion analysis regularly in order to check the operating e ciency of the boiler and to make sure any polluting substances released are within the boudaries set by current legislation. Before beginning maintenance work:
- Disconnect the appliance from the electricity supply by turning the external bipolar switch to the “OFF” position;
- Close the gas valve and the central heating and domestic hot water system valves.
After the work has been completed the initial settings will be restored.
General comments
It is recommended that the following inspections be carried out on the boiler at least once a year:
1. Check the seals in the water part and, if necessary, replace the gaskets and restore the seal to perfect working order.
2. Check the seals in the gas part and, if necessary, replace the gaskets and restore the seal to perfect working order.
3. Visually check the overall condition of the boiler.
4. Visually check and, if necessary, disassemble and clean the burner.
5. Following the inspection detailed in point “3”, disassemble and clean the combustion chamber, if necessary.
6. Following the inspection detailed in point “4”, disassemble and clean the burner, if necessary.
7. Cleaning the primary heat exchanger
8. Make sure the following heating safety devices are operating correctly:
- temperature limit safety device.
9. Make sure that the following gas part safety devices are operating correctly:
- absence of gas or  ame safety device (ionisation).
10. Check the e ciency of the domestic hot water production process (test the  ow rate and temperature).
11. Perform a general inspection of the boiler operation.
12. Remove oxide from the detection electrode using an emery cloth.
13. These checks are not exhaustive. Further mechanical, electrical and combustion maintenance checks may be required.
Operational test
After having carried out the maintenance operations,  ll the heating circuit at a pressure of approximately 1.5 bar and release the air from the system. Fill the domestic hot water system at the same time.
- Begin operating the boiler.
- If necessary, release the air from the heating system again.
- Check the settings and make sure all the command, adjustment
and monitoring parts are working correctly.
- Check the  ue system is sealed and operating correctly.
Draining procedures
The heating system must be drained using the following
procedure:
- Switch o the boiler, make sure the external bipolar switch is in the OFF position and shut o the gas valve;
- Loosen the automatic air relief valve;
- Open the system drain o cock and collect the escaping water in a container;
- Empty the water from the lowest points of the system (where applicable).
If the system is to be left inactive in areas where the room temperature may fall below 0°C during winter, we recommend that anti-freeze liquid is added to the water in the heating system in order to avoid the need for repeated draining; when this liquid is used make sure it is compatible with the stainless steel used for the bodywork of the boiler. We recommend the use of anti-freeze products which contain PROPYLENE GLYCOLS as these inhibit corrosion and that they are used in conjunction with the anti-scaling and anti-corrosion function, in the quantities suggested by the manufacturer, at the mimimum temperature. Regularly check the pH level of the water/anti-freeze mix in the boiler circuit and replace it when the value measured is lower than the limit prescribed by the manufacturer.
DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE.
The manufacturer will not be held liable for any damage caused by the appliance or the system due to the use of inappropriate anti-freeze substances or additives.
Draining the domestic hot water system and indirect cylinder
Every time there is a danger of freezing, the domestic hot water system must be drained as follows:
- Shut o the water mains inlet valve;
- Open all the hot and cold water taps;
- Empty the water from the lowest points of the system (where applicable).
WARNING
Before handling, empty all components which may contain hot water, performing bleeding where necessary. Descale the components in accordance with the instructions provided on the safety data lea et supplied with the product used, make sure the room is well ventilated, wear protective clothing, avoid mixing di erent products, and protect the appliance and surrounding objects. Seal all openings used to take a gas pressure reading or to make any gas adjustments. If a smell of burning is detected or smoke is seen leaking from the appliance, or there is a smell of gas, disconnect it from the electricity supply, shut o the gas valve, open the windows and call for technical assistance.
Cleaning the primary exchanger
Cleaning the combustion side The inside of the primary exchanger is accessed by removing the burner. Wash with water and detergent using a non-metallic ri e­type brush, rinse with water.
Cleaning the trap
The trap is accessed by emptying the condensate bowl located in the bottom section. Wash with water and detergent. Replace the condensate collection bowl in its housing. NB: In the event of prolonged use of the appliance, the trap must be  lled before being used again. A lack of water in the trap is dangerous and may cause products to be released into the atmosphere.
Page 48
48
MAINTENANCE GUIDE
1. GENERAL ACCESS
1.1 General Access
Tools
TIME
3 min
Unclip the cover to remove
1
Remove the two screws
2
Remove the front panel
3
Lower the electrical front panel
4
Remove the combustion chamber front panel by releasing the clips
5
Page 49
49
MAINTENANCE GUIDE
2. ELECTRICAL UNIT
2.1 Control box access
Tools
TIME 4 min
Remove the front panel as above and pivot the electricl box
1
Unhook the two clip and rotate the cover
2
3
Unscrew the two screws and remove the cover
3
4
5
Page 50
50
MAINTENANCE GUIDE
2.2 Fuse
Tools
TIME
5 min
Open the control box as above
1
Remove the fuse
2
3
2.3 Main P.C.B.
Tools
TIME
5 min
After opening the control box, disconnect the elctrical plug connections
1
Unhook and remove the P.C.B.
2
Page 51
51
MAINTENANCE GUIDE
2.4 Display P.C.B.
Tools
TIME 5 min
Unscrews the two screws and pull the assembly towards you
1
Disconnect the elctrical plug connections and unhook and remove the P.C.B.
2
3
Page 52
52
MAINTENANCE GUIDE
3. HYDRAULIC UNIT
3.1 RIGHT HAND HYDRAULIC BLOCK ASSEMBLY
Legend: 1 - Diverter valve motor 2 - Diverter valve 3 - Auto air vent 4 - Primary water pressure switch 5 - Pump 6 - Central heating  lter 8 - D.H.W.  ow switch assembly 9 - Central Heating return 10 - Cold water inlet (D.H.W.) 11 - C.H. drain valve
3.2. 3 Way valve unit
Tools
TIME 5 min
Unplug the diverter valve cable
1
Remove the clip and lift the motor from the diverter valve body.
2
Drain the boiler (see 3.3). Remove the clip and lift the diverter valve from the assembly.
3
When reassembling, ensure the diverter valve is aligned correctly.
4
Page 53
53
MAINTENANCE GUIDE
3.3 Draining
Tools
TIME
5 min
Turn the drain valve anti-clockwise to open and drain the water from the boiler
1
3.4 Automatic air vent
Tools
TIME 5 min
Drain the boiler (see 3.3). Remove the clip and lift the AAV from the assembly.
1
2
3.5 Primary water pressure sensor
Tools
TIME
5 min
Drain the boiler (see 3.3). Slide the  xing clip, (it is held captive) unplug the electrical connector and lift the sensor from the assembly.
1
2
Page 54
54
MAINTENANCE GUIDE
3.6 Pump
Tools
TIME
10 min
Drain the boiler (see 3.3). Remove the clip and the two screws
1
Disconnect the pipe and then move the pump to the right to disengage
2
Remove the pump
3
Remove the sensor (see 3.5)
4
Remove the AAV (see 3.4)
5
6
Page 55
55
MAINTENANCE GUIDE
3.8 D.H.W. Flow switch assembly
Tools
TIME
10 min
Drain the boiler (see 3.3). Remove the clip and pull the  ow switch assembly towards you
1
Twist the  ow switch assembly to disengage
2
3.7 C.H. Filter
Tools
TIME 5 min
Drain the boiler (see 3.3). Remove the clip and remove the  lter
1
Remove the  lter
2
Page 56
56
MAINTENANCE GUIDE
3.11 Secondary heat exchanger
Tools
TIME
10 min
Drain primary and domestic hot water circuits. Remove the two screws and remove the heat exchanger
1
2
3.9 LEFT HAND HYDRAULIC BLOCK ASSEMBLY
Legend: 1 - Left hand hydraulic block 2 - By-pass assembly 3 - Safety valve 4 - Central heating  ow 5 - Domestic hot water outlet
Page 57
57
MAINTENANCE GUIDE
3.12 Condensate trap
Tools
TIME
5 min
Unscrew the condensate trap from the condensate body
1
3.13 Safety valve
Tools
TIME 5 min
Drain the boiler (see 3.3). Disconnect the discharge pipe. Remove the  st clip on the left and pull the safety valve towards you
1
2
Page 58
58
MAINTENANCE GUIDE
3.14 By-pass assembly
Tools
TIME 5 min
Drain the boiler (see 3.3). Remove the second clip and pull the assembly towards you
1
2
3
3.15 Temperature sensors
Tools
TIME 5 min
NTC1 : Black NTC2: Red
1
Unplug the electrical connectors
2
NTC1
NTC2
Page 59
59
MAINTENANCE GUIDE
3.16 Manual Air vent
Tools
TIME
5 min
Drain boiler (see 3.3) Unscrew and lift the manual air vent from the exchanger
1
2
Remove the clip and the temperature sensor
3
IMPORTANT ! Do not use conducting paste for the contact
sensors because it will alter the resistance value.
TEMPERATURE RESISTANCE (kOhm)
027 10 17 20 12 25 10 30 8 40 5 50 4
Page 60
60
MAINTENANCE GUIDE
3.17 Main heat exchanger
Tools
TIME
20 min
Drain boiler (see 3.3) Remove the silencer
1
Remove the two clips and disconnect the pipes. Isolate the gas supply and disconnect the gas pipe. Remove the four screws.
2
Remove the burner unit
3
Remove the four screws to free the heat exchanger
4
Unscrew and lift the manual air vent from the exchanger
5
Page 61
61
MAINTENANCE GUIDE
4. BURNER UNIT
1
2
3
4
5
6
7
8
Legend: 1 - Burner 2 - Silencer 3 - Gas diaphram 4 - Mixing tube 5 - Fan 6 - Detection electrode 7 - Ignition electrode 8 - Spark generator
Page 62
62
MAINTENANCE GUIDE
4.1 Spark generator
Tools
TIME
5 min
Unplug the ignition electrode from the spark generator.
1
Remove the screws and the spark generator
2
4.2 Electrodes
Tools
TIME
5 min
Unplug the electrodes
1
Remove the screws and pull the electrodes towards you.
2
3
Page 63
63
MAINTENANCE GUIDE
4.3 Burner
Tools
TIME
15 min
Remove the silencer
1
Isolate the gas supply. Disconnect the gas pipe.
2
Pull the assembly towards you
3
Remove the ten screws to free the burner door
4
Pull the burner toward you Replace any gaskets that are damaged or showing signs of deterioration
5
1
3
2
Fan & mixer venturi according to the model
Power Length Venturi diameter 18 kW 104.6 mm Ø 14 24 kW 104.6 mm Ø 17 30 kW 135.8 mm Ø 21 38 kW 167 mm Ø 25
Legend: 1 - Stainless steel Burner 2 - Ignition electrode 3 - Detection electrode
Page 64
64
MAINTENANCE GUIDE
1
3
2
4.4 Fan
Tools
TIME
15 min
Remove the combustion assembly (see 4.3)
1
Remove the three screws to free the fan.
2
Legend: 1 - Fan 2 - Venturi 3 - Gasket
Fan & mixer venturi according to the model
Power Fan Venturi diameter 18 kW EBM RG 118 40 W Ø 14 24 kW EBM RG 118 40 W Ø 17 30 kW EBM RG 118 40 W Ø 21 38 kW EBM RG 118 40 W Ø 25
Page 65
65
MAINTENANCE GUIDE
4.5 Gas Valve
Tools
TIME 15 min
Remove the two screws under the boiler and disconnect the gas pipe on the top of the gas valve
1
Remove the gas valve
2
Legend: 1 - Gas valve 2 - Solenoids 3 - Throttle adjustment 4 - O set adjustment 5 - Inlet test nipple
Page 66
66
MAINTENANCE GUIDE
5. ANNUAL MAINTENANCE
Plate heat exchanger
Maintenance Interval: As necessary How: To measure speci cation of DHW performance.
By-pass & Safety valve
Maintenance Interval: Annually How: Visual inspection / Clean as necessary
Central heating  lter
Maintenance Interval: Annually How: Visual inspection / Clean as necessary
Flow switch operation
Maintenance Interval: Annually How: Visual inspection / Clean as necessary / Check  ow rate
Expansion vessel
Maintenance Interval: Annually How: Check air pressure is at 1 bar (System drained)
Ignition & detection electrodes
Maintenance Interval: Annually How: Visual inspection / Clean as necessary / Distance from the burner / Ionisation current more than 1 A
Burner
Maintenance Interval: Annually How: Visual inspection / Clean as necessary
Fan
Maintenance Interval: Annually How : Visual inspection / Clean as necessary
Page 67
67
MAINTENANCE GUIDE
Primary Heat exchanger
Maintenance Interval: Annually How : Visual inspection / Clean as necessary
Condensate trap
Maintenance Interval: Annually
or after cleaning primary heat exchanger
How : Visual inspection / Clean as necessary /
Add water before replacing
Pump
Maintenance Interval: At the  rst ignition and annually
How: Check that the AAV is open /
Visual inspection / Clean as necessary
Page 68
Page 69
Failure to install and commission according to the manufacturer’s instructions and complete this Benchmark Commissioning Checklist will invalidate the warranty. This does not affect the customer’s statutory rights.
If yes, and if required by the manufacturer, has a water scale reducer been fitted?
CONDENSING BOILERS ONLY
The condensate drain has been installed in accordance with the manufacturer’s instructions and/or BS5546/BS6798 Yes
If the condensate pipe terminates externally has the pipe diameter been increased and weatherproof insulation fitted? Yes
Page 70
Service Record
It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed.
Service Provider
Before completing the appropriate Service Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
Always use the manufacturer’s specified spare part when replacing controls.
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Operative ID No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Gas Safe Register No.
Comments:
Signature:
Service 1 Service 2
Service 3 Service 4
Service 5 Service 6
Service 7 Service 8
Service 9 Service 10
Page 71
Page 72
420010439400
Ariston Thermo UK Ltd
Hughenden Avenue High Wycombe Bucks HP13 5FT Telephone: (01494) 755600 Fax: (01494) 459775 Internet: www.ariston.co.uk
Technical Advice: 0333 240 7777 Customer Service: 0333 240 8777
Loading...