Ariston CLAS HE 24, CLAS HE 30, CLAS HE 38 Installation and Servicing Instructions

Installation and Servicing Instructions
CLAS HE
Gas red condensing wall hung combination boilers
G.C.N : 47-116-51 (24 kW) G.C.N : 47-116-52 (30 kW) G.C.N : 47-116-53 (38 kW)
Country of destination GB, IE
CLAS HE 24
CLAS HE 30
CLAS HE 38
overview
INDEX
Overview
General Information ................................................................................................. 3
Advice for the Installer .............................................................................................4
CE Labelling .................................................................................................................4
Data Plate Symbols ...................................................................................................4
Safety Regulations ....................................................................................................5
Product description
Control Panel...............................................................................................................6
Display ...........................................................................................................................6
Overall View .................................................................................................................7
Overall Dimension ....................................................................................................7
Minimum Clearances ...............................................................................................7
Technical Information ..............................................................................................8
Installation
Reference Standards ................................................................................................9
Installing the Boiler ................................................................................................ 12
Gas Connection ....................................................................................................... 13
Water Connection .................................................................................................. 13
Instructions for Opening the Casing and Performing an
Internal Inspection ................................................................................................. 13
Connecting the Flue .............................................................................................. 15
Fitting the Coaxial Flue (Ø 60/100 Horizontal) .............................................16
Fitting the 5” Flue (Ø 80/125 Horizontal / Vertical) ..................................... 17
Fitting the Coaxial Flue (Ø 60/100 Vertical) ................................................... 18
Fitting the Twin Pipe (Ø 80/80) .......................................................................... 19
Electrical Connections .......................................................................................... 23
Peripheral Unit Connection ................................................................................ 23
Room Thermostat Connection .......................................................................... 24
Outdoor Sensor Connection ..............................................................................24
Electrical Diagram .................................................................................................. 25
Commissioning
Initial Preparation ................................................................................................... 26
Electricity Supply .................................................................................................... 26
Filling the Heating System .................................................................................. 26
Filling of the DHW System ...................................................................................26
Gas Supply ................................................................................................................26
Water Treatment ..................................................................................................... 26
First Igniton Operation ......................................................................................... 27
Ignition procedure ................................................................................................. 28
Test Function and Combustion Analysis ........................................................ 30
AUTO Function ........................................................................................................31
Boiler Protection Devices
Boiler Protection Devices ....................................................................................32
Anti-Frost Device .................................................................................................... 32
Table summarising error codes ......................................................................... 32
Settings - Adjustment - Problem Identication Menus
Accessing the Menus ............................................................................................33
Maintenance
General Comments ................................................................................................ 41
General Access ........................................................................................................42
Electrical Unit ........................................................................................................... 43
Hydraulic Unit .......................................................................................................... 45
Main Heat Exchanger ............................................................................................ 53
Burner Unit ............................................................................................................... 54
Fan Unit ...................................................................................................................... 57
Gas Valve ....................................................................................................................58
Annual Maintenance ............................................................................................. 59
Spare Parts Short List ............................................................................................60
Benchmark Commissioning Checklist ............................................................ 61
Benchmark Service Interval Record ................................................................. 62
2
overview
These instructions are suitable for CLAS HE boilers : Do not forget the Log Book! MTS supports Benchmark, the heating industry code to ensure the correct installation, commissioning and servicing of domestic central heating systems.
To The Householder Make sure you have a completed Log Book for your boiler. This provides a record of the commissioning of your boiler. It contains important information about your particular installation that may be required by service engineers. The Log Book will also provide contact details for the installer should you need guidance in the use of this appliance or if there are any problems. As with your car, your boiler will work more reliably and eciently if regularly serviced. We recommend an annual service check. The service history of the appliance will be recorded on the Log Book. In the unlikely event of any problems with your boiler or system you should rst contact your installer. If your installer cannot resolve the problem he should telephone our national service helpline. A charge may be made if MTS Service is called out to resolve a non-product related fault. Your statutory rights are not aected.
To The Installer
As part of the commissioning of this appliance it is vital that the Log Book is completed and given to the Householder. Please ensure that your customer is aware of the importance of keeping the Log Book safe as a record of the installation and the appliance service history.
Please ensure that your customer is aware of the correct operation of the system, boiler and controls.
MTS recommend the use of protective clothing, when installing and working on the appliance i.e. gloves.
CUSTOMER CARE
MTS, as a leading manufacturer of domestic and commercial water heating appliances is committed to providing high quality products and a high quality after sales service. Advice on installation or servicing can also be obtained by contacting the MTS Technical and Customer Service Departments at High Wycombe. TECHNIC Tel: 0870 241 8180 Tel: 0870 600 9888 Fax: 01494 459775 Fax: 01494 459775
GUARANTEE
T accordance with the recommendations made herein or in a manner not approved by the manufacturer. To assist us in providing you with an ecient after sales service, please return the guarantee registration card enclosed with the boiler without delay.
CAUTION
In the United Kingdom, installation, start-up, adjustments and maintenance, must be performed by a competent person only, in accordance with the current Gas Safety (Installation & Use) Regulations and the instructions provided.
In the Republic of Ireland, the installation and initial start up of the appliance must be carried out by a Competent Person in accordance with the current edition of I.S.813 “Domestic Gas Installations”, the current Buidling Regulations, reference should also be made to the current ETCI rules for electrical installation.
AL DEPARTMENT CUSTOMER SERVICE DEPARTMENT
he manufacturer’s guarantee is for 2 years from the date of purchase. The guarantee is invalidated if the appliance is not installed in
All CORGI registered installers carry a CORGI ID card, and have a registration number. Both should be recorded in your boiler Log Book. You can check your installer is CORGI registered by calling CORGI direct on:- (01256) 372300.
Improper installation may cause damage or injury to individuals, animals and personal property for which the manufacturer will not be held liable. To ensure ecient and safe operation it is recommended that the boiler is serviced annually by a competent person.
If it is known that a fault exists on the appliance, it must not be used until the fault has been corrected by a competent person.
This instruction booklet is especially designed for appliances installed in the UK and the Republic of Ireland
3
overview
MIN MAX
Advice for the installer The installation and rst ignition of the boiler must be performed by qualied personnel in compliance with current national regulations regarding installation, and in conformity with any requirements established by local authorities and public health organisations. After the boiler has been installed, the installer must ensure that the end user receives the declaration of conformity and the operating manual, and should provide all necessary information as to how the boiler and the safety devices should be handled.
This appliance is designed to produce hot water for domestic use. It should be connected to a heating system and a distribution network for domestic hot water, both of which must be compatible with its performance and power levels. The use of the appliance for purposes other than those specied is strictly forbidden. The manufacturer cannot be held responsible for any damage caused by improper, incorrect and unreasonable use of the appliance or by the failure to comply with the instructions given in this manual. Installation, maintenance and all other interventions must be carried out in full conformity with the governing legal regulations and the instructions provided by the manufacturer. Incorrect installation can harm persons, animals and possessions; the manufacturing company shall not be held responsible for any damage caused as a result. The boiler is delivered in a carton. Once you have removed all the packaging, make sure the appliance is intact and that no parts are missing. If this is not the case, please contact your supplier. Keep all packaging material (clips, plastic bags, polystyrene foam, etc.) out of reach of children as it may present a potential hazard. In the event of a fault and/or malfunction, turn the appliance o, turn o the gas cock and do not attempt to repair it yourself. Contact a qualied professional instead. Before any maintenance or repair work is performed on the boiler, make sure you have disconnected it from the electricity supply by switching the external bipolar switch to the “OFF” position and removing the fuse. All repairs, which should only be performed using original spare parts, should be carried out by a qualied professional. Failure to comply with the above instructions could compromise the safety of the appliance and invalidate all liability on the part of the manufacturer. In the event of any maintenance or other structural work in the immediate vicinity of the ducts or ue gas exhaust devices and their accessories, switch the appliance o by switching the external bipolar switch to the “OFF” position and shutting o the gas control valve. When the work has been completed, ask a qualied technician to check the eciency of the ducting and the
devices. Turn the boiler o and turn the external switch “OFF” to clean the
exterior parts of the appliance. Clean using a cloth dampened with soapy water. Do not use aggressive detergents, insecticides or toxic products. If the appliance is used in full compliance with current legislation, it will operate in a safe, environmentally-friendly and cost-ecient manner. If using kits or optional extras, make sure they are authentic.
CE labelling
The CE mark guarantees that the appliance conforms to the fol­lowing directives:
- 90/396/CEE relating to gas appliances
- 89/336/CEE relating to electromagnetic compatibility
- 92/42/CEE relating to energy eciency
- 73/23/CEE relating to electrical safety
Symbols used on the data plate
Key:
1. Brand
2. Manufacturer
3. Boiler model - code
4. Serial number - certication number
5. Destination country - gas category
6. Gas setting
7. Boiler type
8. Electrical data
9. Maximum domestic hot water pressure
10. Maximum heating pressure
11. NOx class
12. Eciency
13. Max - min heat input
14. Max - min heat output
15. Max/min operating room temperature
16. Max. central heating temperature
17. Gases which may be used
4
overview
Safety regulations
Key to symbols:
Failure to comply with this warning implies the risk of personal injury, in some circumstances even fatal Failure to comply with this warning implies the risk of damage, in some circumstances even serious, to property, plants or animals.
Install the appliance on a solid wall which is not subject to vibration.
Noisiness during operation.
When drilling holes in the wall for installation purposes, take care not to damage any electrical wiring or existing piping.
Electrocution caused by contact with live wires. Explosions, res or intoxication caused by gas leaking from damaged piping. Damage to existing installations. Flooding caused by water leaking from damaged piping.
Perform all electrical connections using wires which have a suitable section.
Fire caused by overheating due to electrical current passing through undersized cables.
Protect all connection pipes and wires in order to prevent them from being damaged.
Electrocution caused by contact with live wires. Explosions, res or intoxication caused by gas leaking from damaged piping. Flooding caused by water leaking from damaged piping.
Make sure the installation site and any systems to which the appliance must be connected comply with the applicable norms in force.
Electrocution caused by contact with live wires which have been installed incorrectly. Damage to the appliance caused by improper operating conditions.
Use suitable manual tools and equipment (make sure in particular that the tool is not worn out and that its handle is xed properly); use them correctly and make sure they do not fall from a height. Replace them once you have nished using them.
Personal injury from the falling splinters or fragments, inhalation of dust, shocks, cuts, pricks and abrasions. Damage to the appliance or surrounding objects caused by falling splinters, knocks and incisions.
Use electrical equipment suitable for its intended use (in particular, make sure that the power supply cable and plug are intact and that the parts featuring rotary or reciprocating motions are fastened correctly); use this equipment correctly; do not obstruct passageways with the power supply cable, make sure no equipment could fall from a height. Disconnect it and replace it safely after use.
Personal injury caused by falling splinters or fragments, inhalation of dust, knocks, cuts, puncture wounds, abrasions, noise and vibration. Damage to the appliance or surrounding objects caused by falling splinters, knocks and incisions.
Make sure any portable ladders are positioned securely, that they are suitably strong and that the steps are intact and not slippery and do not wobble when someone climbs them. Ensure someone provides supervision at all times.
Personal injury caused by falling from a height or cuts (stepladders shutting accidentally).
Make sure any rolling ladders are positioned securely, that they are suitably strong, that the steps are intact
and not slippery and that the ladders are tted with handrails on either side of the ladder and parapets on the landing.
Personal injury caused by falling from a height.
During all work carried out at a certain height (generally with a dierence in height of more than two metres), make sure that parapets are used to surround the work area or that individual harnesses are used to prevent falls. The space where any accidental fall may occur should be free from dangerous obstacles, and any impact upon falling should be cushioned by semi-rigid or deformable surfaces.
Personal injury caused by falling from a height.
Make sure the workplace has suitable hygiene and sanitary conditions in terms of lighting, ventilation and solidity of the structures.
Personal injury caused by knocks, stumbling etc.
Protect the appliance and all areas in the vicinity of the work place using suitable material.
Damage to the appliance or surrounding objects caused by falling splinters, knocks and incisions.
Handle the appliance with suitable protection and with care.
Damage to the appliance or surrounding objects from shocks, knocks, incisions and squashing.
During all work procedures, wear individual protective clothing and equipment.
Personal injury caused by electrocution, falling splinters or fragments, inhalation of dust, shocks, cuts, puncture wounds, abrasions, noise and vibration.
Place all debris and equipment in such a way as to make movement easy and safe, avoiding the formation of any piles which could yield or collapse.
Damage to the appliance or surrounding objects from shocks, knocks, incisions and squashing.
All operations inside the appliance must be performed with the necessary caution in order to avoid abrupt contact with sharp parts.
Personal injury caused by cuts, puncture wounds and abrasions.
Reset all the safety and control functions aected by any work performed on the appliance and make sure they operate correctly before restarting the appliance.
Explosions, res or intoxication caused by gas leaks or an incorrect ue gas exhaust. Damage or shutdown of the appliance caused by out-of-control operation.
Before handling, empty all components that may contain hot water, carrying out any bleeding if necessary.
Personal injury caused by burns.
Descale the components, in accordance with the instructions provided on the safety data sheet of the product used, airing the room, wearing protective clothing, avoid mixing dierent products, and protect the appliance and surrounding objects.
Personal injury caused by acidic substances coming into contact with skin or eyes; inhaling or swallowing harmful chemical agents. Damage to the appliance or surrounding objects due to corrosion caused by acidic substances.
If you detect a smell of burning or smoke, keep clear of the appliance, disconnect it from the electricity supply, open all windows and contact the technician.
Personal injury caused by burns, smoke inhalation, intoxication.
5
product description
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
9
6
12
I
1
2
3
4
5 6
7 8
17
16
15
13
14
11
12
10
9
Control panel
Legend :
1. Display
2. R
ESET button
3. Red indicator locking light
4.
Orange indicator C
OMFORT fonction
5. Pressure gauge
6.
Heating temperature regulation knob
7. button
8.
M
9. E
10. button +
_
ENU/OK button (Programming key)
SC button
11.
Domestic Hot Water adjustment knob
12. Time clock
13. ON/OFF button
14. Blue indicator burner ON
15.
Yellow indicator A
16. A
UTO button
17. C
OMFORT button
UTO fonction
(To active Thermoregulation)
6
28
770
200
150
120 120
200
180
65 6567 67
25770
Overall view
450
003
003
50 50
1
2
3
4
5
6
7
8
9
10
11
12
13
25
24
23
22
21
20
18
19
17
15
16
product description
1. ue connector
2. air pressure switch
3.
burner
4. detection Electrode
5.
overheat thermostat
6.
C.H. Return temperature probe
7.
C.H. Flow temperature probe
8.
gas valve
9.
secondary heat exchanger
10.
D.H.W. temperature probe
11.
siphon
12. C.H. pressure relief valve
13. electrical box
15.
C.H. circuit lter
D.H.W. Flow switch
16.
17.
circulation Pump with air release valve
18.
diverter valve
19.
switch On-O
20. silencer
21. modulating Fan
22. ignition electrodes
23. ignitor
24. thermal fuse
25.
combustion Analysis Test Point
Overall Dimensions
24/30/38
A. Central Heating Flow B. Domestic Hot Water Outlet C. Gas Inlet D. Domestic Cold Water Inlet E. Central Heating Return
Minimum clearances
In order to allow easy access to the boiler for maintenance operations, The boiler must be installed in accordance with the clearances stated below.
5
5
7
product description
GENERAL NOTE
Model
24 kW
30 kW
38 kW
CE Certication (pin)
0085BR0347
Boiler type
B23-C13-C33-C43-C53-C83
POWER SPECIFICATIONS
Max/min nominal caloric ow rate (Pci) Qn
KW
22,0/5,5
28,0/6,5
31,0/7,5
Max/min nominal caloric ow rate (Pcs) Qn
KW
24,4/6,1
31,1/7,2
34,4/8,3
Domestic hot water max/min nominal caloric ow rate (Pci) Qn
KW
25,0/5,5
30,0/6,5
38,0/7,5
Domestic hot water max/min nominal caloric ow rate (Pcs) Qn
KW
27,8/6,1
33,3/7,2
42,2/8,3
Max/min power output (80°C-60°C) Pn
KW
21,6/5,2
27,4/6,2
30,3/7,3
Max/min power output (50°C-30°C) Pn
KW
23,5/6,0
30,0/6,9
33,1/8,0
Domestic hot water max/min power output Pn
KW
25,0/5,0
30,0/6,0
38,9/7,1
Combustion eciency (of ue gas)
%
97,9
97,9
98,0
Nominal caloric ow rate eciency (60/80°C) Hi/Hs
%
98,0/88,2
98,0/88,2
97,6/87,9
Nominal caloric ow rate eciency (30/50°C) (condensation) Hi/Hs
%
107,0/96,4
107,0/96,4
106,7/96,1
Eciency at 30% at 30°C (condensation) Hi/Hs
%
108,0/97,3
108,0/97,3
109,1/98,2
Eciency at 30% at 47°C Hi/Hs
%
101,0/90,9
98,2/88,4
103,1/92,8
Minimum caloric ow rate eciency (60/80°C) Hi/Hs
%
95,0/85,5
95,6/86,1
96,8/87,2
Eciency rating (dir. 92/42/EEC)
stars
****
****
****
Sedbuk class
class
A / 90,3
A / 90,3
A / 90,1
Loss when stopped (∆T = 50°C)
%
0,2
0,1
0,1
Loss of burner gas when operating
%
2,1
2,1
2,0
EMISSIONS
Available air pressure
Pa
137
141
132
NoX class
class55
5
Flue gas temperature (G20) (80°C-60°C)
°C6363
63
CO2 content (G20) (80°C-60°C)
%
9,0
9,0
9,6
CO content (0%O2) (80°C-60°C)
ppm
< 100
< 100
< 125
O2 content (G20) (80°C-60°C)
%
4,5
4,5
3,5
Maximum ue gas ow (G20) (80°C-60°C)
Kg/h
41,2
49,4
59,2
Excess air (80°C-60°C)
%2727
20
HEATING CIRCUIT
Expansion chamber ination pressure
bar11
1
Maximum heating pressure
bar33
3
Expansion chamber capacity
L
6,5
6,5
6,5
Maximum water capacity with in the appliance (75°C-35°C)
L
100/300
100/300
100/300
Min/max heating temperature (high temperature range)
°C
35/82
35/82
35/82
Min/max heating temperature (low temperature range)
°C
20/45
20/45
20/45
DOMESTIC HOT WATER
CIRCUIT
Domestic hot water max/min temperature
°C
36/60
36/60
36/60
Specic ow rate of domestic hot water (∆T=30°C)
l/mn
12,0
15,0
18,2
Quantity of hot water ∆T=25°C
l/mn
14,4
18,0
21,8
Quantity of hot water ∆T=35°C
l/mn
10,3
12,9
15,6
Hot water comfort rating (EN13203)
stars
***
***
***
Hot water minimum ow rate
l/mn
< 2
< 2
< 2
Domestic hot water max/min pressure
bar
7/0,3
7/0,3
7/0,3
ELECTRICAL
Power supply frequency/voltage
V/Hz
230/50
230/50
230/50
Total electrical power absorbed
W
114
115
150
Minimum ambient temperature for use
°C+5+5
+5
Protection level for the electrical appliance
PI
X5D
X5D
X5D
Weightkg323535,5
Dimension (L x H x D)
mm
440/820/385
440/820/455
440/820/455
Technical Data
8
Reference Standards
In the United Kingdom, the installation and initial start-up of the boiler must be by a CORGI registered installer in accordance with the installation standards currently in eect, as well as with any and all local health and safety standards i.e. CORGI.
In the Republic of Ireland the installation and initial start-up of the appliance must be carried out by a Competent Person in accordance with the current edition of I.S.813 “Domestic Gas Installations” and the current Building Regulations, reference should also be made to the current ETCI rules for electrical installation.
The installation of this appliance must be in accordance with the relevant requirements of the Local Building Regulations, the current I.E.E. Wiring Regulations, the by-laws of the local authority, in Scotland, in accordance with the Building Standards (Scotland) Regulation and Health and Safety document No. 635, “Electricity at Work Regulations 1989” and in the Republic of Ireland with the current edition of I.S. 813 and the Local Building Regulations (IE).
C.O.S.H.H.
Materials used in the manufacture of this appliance are non­hazardous and no special precautions are required when servicing.
Codes of Practive
Installation should also comply with the following British Standards Code of Practice:
BS 7593:1992
Treatment of water in domestic hot water central heating systems BS 5546:1990 Installation of hot water supplies for domestic purposes BS 5440-1:2000 Flues BS 5440-2:2000 Air supply BS 5449:1990 Forced cicrulation hot water systems BS 6798:2000 Installation of gas red hot water boilers of rated input not exceeding 70kW BS 6891:1989 Installation of low pressure gas pipes up to 28mm BS 7671:2001 IEE Wiring Regulations BS 4814:1990 Specication for expansion vessels BS 5482:1994 Installation of L.P.G.
and in the Republic of Ireland in accordancce with the following codes of practice:
I.S. 813 Domestic Gas Installations
Avoid installing the boiler where the air inlet can be polluted by checmical products such as chlorine (swimming pool area), or ammonia (hair dresser), or alkalin products (launderette).
Flue
Detailed information on ue assembly can be found in the “Connecting the Flue” section. The boiler must be installed so that the ue terminal is exposed to the free passage of external air at all times and must not be installed in a place likely to cause nuisance. It must not be allowed to discharge into another room or space such as an outhouse or closed lean-to.
Condensing boilers have a tendency to form a plume of water vapour from the ue terminal due to the low temperature of the ue gasses. The terminal should therefore be located with due regard for the damage or discolouration that may occur to
installation
building within the vicinity and consideration must also be given to adjacent boundaries, openable windows should also be taken into consideration when siting the ue.
The minimum acceptable clearances are shown below:
- A Dir
ectly below an opening, window, etc 300 mm
- B Horizontally to an opening, window, etc 300 mm
- C Below gutters, soils pipes or drain pipes 75 mm
- D Below eaves 200 mm
- E From vertical drain pipe or soil pipe 75 mm
- F From internal or external corner 300 mm
- G Above ground, roof or balcony level 300 mm
- H From a surface facing the terminal 2500 mm
- I From a terminal facing a terminal 2500 mm
- J Vertically from a terminal on the same wall 1500 mm
- K Horizontally from an terminal on the same wall 300 mm
- L Fixed by vertical ue terminal
N
OTE: THE FLUE MUST NOT BE INSTALLED IN A PLACE LIKELY TO CAUSE A NUISANCE AND POSITIONED TO ENSURE THAT PRODUCTS OF COMBUSTION DO NOT DISCHARGE ACROSS A BOUNDARY
It may be necessary to protect the terminal with a guard, if this is the case it will be necessary to purchase a stainless steel terminal guard. Reference should be made to the Building Regulations for guidance.
Ventilation
The room in which the boiler is installed does not require specic ventilation. If the boiler is installed in a cupboard or compartment ventillation is not required for cooling purposes.
Gas Supply
The gas installation and tightness testing must be in accordance with the requirements of BS6891. Ensure that the pipe size is adequate for demand including other gas appliances on the same supply.
Electrical Supply
T
he appliance requires an earthed 230V - 50 Hz supply and must be in accordance with current I.E.E. regulations. It must also be possible to be able to completely isolate the appliance electrically. Connection should be via a 3 amp douple pole fused isolating switch with contact separation of at least 3mm on both poles. Alternatively, a fused 3 Amp, 3 pin plug and unswitched socket may be used, provided it is not used in a room containing a bath or shower, it. It shoild only supply the appliance.
9
installation
Water Supply
The boiler is suitable for sealed systems only. The maximum working pressure for the appliance is 6 bar. All ttings and pipework for the appliance should be of the same standard. If there is a possibility of the incoming mains pressure exceeding 6 bar, particularly at night, then a suitable pressure limiting valve must be tted. The boiler is designed to provide hot water on demand to multiple outlets within the property. If there is a requirement for greater demands, for example if the boiler has several bathrooms and cloakrooms, a vented or unvented hot water storage system may be used.
Showers
Any shower valves used with the appliance should be of a thermostatic or pressure balanced type. Refer to the shower manufacturer for performance guidance and suitability.
Flushing and Water Treatment
The boiler is equipped with a stainless steel heat exchanger.
The detailed recommendations for water treatment are given in BS 7593:199 heating systems); the following notes are givent for general guidance;
If the boiler is installed on an existing system, any unsuitable additives must be removed.
Under no circumstances should the boiler be red before the system has been thoroughly ushed; the ushing procedure must be in line with BS 7593:199
We highly recommend the use of a ushing detergent appropriate for the metals used in the circuit. These include cleansers produced by Fernox BetzDearbon, whose function is to disolve any foreign matter that may be in the system;
In hard water areas or where large quantities of water are in the system the treatment of water to prevent premature scaling of the main exchanger is necessary.
The formation of scale strongly compromises the eciency of the thermic exchanger because small areas of scale cause a high increase of the temperature of the metallic walls and therefore add to the thermal stress of the heat exchanger.
Demineralised water is more aggressive so in this situation it is necessary to treat the water with an appropriate corrosion inhibitor.
2 (Treatment of water in domestic hot water central
2.
Preiodically check the pH balance of the water/anti-freeze mixture of the boiler circuit and replace it when the amount measured is out of the range stipulated by the manufacturer (7 < pH < 8). DO NOT MIX DIFFERENT TYPES OF ANTI-FREEZE
In under-oor systems, the use of plastic pipes without protection against penetration of oxygen through the walls can cause corrosion of the systems metal parts (metal piping, boiler etc), through the formation of oxides and bacterial agents.
To prevent this problem it is necessary to use pipes with an “oxygen proof barrier”, in accordance with standards DIN 47
26/4729. If pipes of this kind are not used, keep the system
separate by installing heat exchangers of those with a specic system water treatment.
IMPORTANT Failire to carry out the water treatment procedure will invalidate the appliance guarantee.
System Controls
The boiler is electrically controlled and is suitable for most modern electronic time and temperature controls. The addition of such external controls can be benecial to the ecient operation of the system. The boiler connections for external c
ontols are 12V DC and so only controls of 12V DC that have voltage free contacts should be used. (page 24). MTS supply a range of wired and wireless system controls. Contact your supplier for more details.
Location
The boiler can be installed on any suitable internal wall (suitable sound proong may be required when installing onto a stud partition wall). Provision must be made to allow for the correct routing of the ue and siting of the terminal to allow the safe and ecient removal of the ue products. A compartment or cupbaord may be used provided that it has been built or modied for this purpose. It is not necessary to provide permanent ventillation for cooling purposes. Detailed r
ecommendations are given in BS 5440 Part 2. If it is proposed that it is to be installed in a timber framed building then r
eference should be made to British Gas Document DM2, IGE/ UP/7 or advice sought from CORGI.
Where a room sealed appliance is installed in a room containing a bath or shower, the appliance and any electrical switch or appliance control, utilising mains electricity should be situated specically in accordance with current IEE Wiring Regulations.
Any treatment of water by additives in the system for frost protection or for corrosion inhibition has to be absolutely suitable for all metals used in the circuit.
The use of a corrosion inhibitor in the sysem such as Fernox MB-1, BetzDearborn Sentinel X100 or Fernox System Inhibitor is recommended to prevent corrosion (sludge) damaging the boiler and system;
If anti-freeze substances are to be used in the system, check carefully that they are compatible with the metals used in the circuit.
MTS suggests the use of suitable anti-freeze products such as Fernox ALPHI 11, which will prevent rust and incrustation taking place.
10
For unusual locations, special procedures may be necessary. BS
6798:2000 gives detailed guidance on this aspect.
Codensate Discharge
The condensate discharge hose from the boiler must have a c
ontinuous fall of 2.5 into a suitable acid resistant pipe - e.g. plastic waste or overow pipe. The condensate discharge pipe must have a minimum diamet
er of 22mm, must have a continuous fall and preferably be installed and terminated to prevent freezing. The discharge pipe must be terminated in a suitable position:
i)
Connecting into an internal soil stack (at least 450mm above the invert of the stack). A trap giving a water seal of at least 75mm must be inc must be an air beak upstr
o
and must be inserted by at least 50mm
orporated into the pipe run, there also
eam of the trap.
installation
ii) Connecting into the waste system of the building such as a washing maching or sink trap. The connection must be upstr
eam of the washing machine/sink. If the connection is down stream of if the waste trap then an additional trap giving a minimum water seal of 75mm and an air break must be incorporated in the pipe run, as above.
iii)
Terminating into a gully, below the grid level but above the
w
ater level
iv) Into a soakaway
Note: If any condensate pipework is to be installed externally then it should be kept to a minimum and be insulated with a waterproof insulation and have a continuous fall. The total length of external pipe used should not exceed 3 metres.
Some examples of the type of condensate terminations can be found below.
1. Internal termination of codensate drainage pipe to internal stack.
3. External termination of condensate drainage pipe via internal discharge branch (e.g. sink waste - proprietary tting).
4. External termination of condensate drainage pipe via condensate siphon
2
. External terminaton of condensate drainage pipe via internal
discharge branch (e.g. sink waste) and condensate siphon.
11
installation
Note: Connections viewed from behind boiler
A
A
Installing the Boiler
Please check that you are familiar with the installation requirement before commencing work (pages 7 - 11).
The installation accessories described in the following list are included in the boiler packaging:
-
Hanging bracket
- A paper template (showing the dimensions of the boiler with 5 mm side clear
- Connection valves (Compression)
- Screws and washers
- Filling loop
- Installation, Servicing and Operating Instructions
- Flue gasket
Method of positioning the boiler on the wall
The paper template can be used to ensure the correct positioning of kitchen cabinets etc.
The paper template has to be xed to the wall and used to locate the position of the hanging bracket and the centre for the ue hole. Drill and plug the wall and secure the hanging bracket using the screws provided. Remove the boiler from it’s packaging and remove the front casing panel. Place the boiler on the hanging bracket.
ances)
N
OTE: THE APPLIANCE MUST NOT BE FITTED ON A COMBUSTIBLE WALL SURFACE.
Connecting the Boiler to the System
-
Remove the boiler casing as described on page 13;
- Remove the caps and connect the valves to the boiler using the w
ashers provided;
- 4 x bre washers for the CH ow and return, cold water inlet and hot w
ater outlet connections;
Safety Valve Discharge and Condense Outlet
The pressure relief valve tube is made of copper. It should terminate below the boiler safely outside the premises. Care should be taken that it does not terminate over an entrance or window or where a discharge of heated water could endanger occupants or passers by.
Fill the central heating and DHW system and bleed air from the system as described in the Commissioning instructions (page 2
6).
The system should be carefully checked for leaks, as frequent relling could cause premature system corrosion or unnecessary scaling of the heat exchanger. The pipe from the trap should be connected to a drain as described in the relevant regulations.
Pay special attention not to bend the condensate silicone drain pipe is such a way as to interrupt the ow. Please only use drain pipe material compatible with condensate products (refer to BS 6798:
2000).
The condensate ow can reach 2 litres/hour because of the acidity of the condensate products (Ph close to 2), take care before operation.
See page 11 for condensate discharge possibiities.
12
- remove the 2 screws A from the transport bar
- dispose of the transport bar and reassemble the xing screws.
installation
A
B
C
D
E
I
H
F
Gas connection
Make sure, using the labels on the packaging and the data plate on the appliance itself, that the boiler is in the correct country and that the gas category for which the boiler was designed corresponds to one of the categories available in the country where it will be used. The gas supply piping must be created and measured out in compliance with specic legal requirements and in accordance with the maximum power of the boiler; you should also make sure that the shut-o valve is the right size and that it is connected correctly. Check that the supplied gas corresponds to the type of gas for which the boiler was designed (see the data plate located on the appliance itself). It is also important to check that the pressure of the gas (methane or LPG) you will be using to feed the boiler is suitable, because if it is insucient the power may be reduced, causing inconvenience for the user.
Instructions for opening the casing and performing an internal inspection
Before performing any work on the boiler, rst disconnect it from the electrical power supply using the external bipolar switch removing the fuse and shutting o the gas valve. To access the inside of the boiler, the following is necessary:
1. Remove the casing by unhooking it from the control panel (a)
2. Loosen the two screws on the front casing (b), pull it forwards and unhook it from the upper pins (c)
3. Lower the control panel (d)
4. Unhook the two clips on the combustion chamber panel and lift o (e).
(a)
(b)
Water connection
The illustration shows the connections for the water and gas attachments of the boiler. See valves conguration on page 13. Check that the maximum water mains pressure does not exceed 6 bar; if it does, a pressure reducing valve must be installed. For the measuring of the pipes and of the heating bodies in the heating system, the residual head value should be calculated as a function of the requested ow rate, in accordance with the values shown in the circulation pump graph.
(c)
(d)
(e)
A. Central heating Flow E. Central Heating Return B
. Domestic Hot Water Outlet F. Safety Valve Discharge
C.
Gas Inlet H. Drain Valve
D
. Domestic Cold Water Inlet I. Drain condensate
13
installation
0
50
100
150
200
250
300
350
400
450
500
0 100 200 300 400 500 600 700 800 900 1000 1100 1200
mbar
l/h
24 kW
30-35 kW
A
B
C
D
E
I
G
H
F
2
1
4
3
11
8
10
9
12
13
14
15
16
17
18
19
20
21
22
7
6
5
A B C D E
To calculate the size of the heating installation, refer to the "Available pressure" graph below.
Graph representing the available circulation pump pressure
o
T20
C
30-38 kW
Before the rst time the equipment is used, the trap must
be lled with water. To do this, add approximately 1/4 litre of water via the ue outlet before tting the ue system, or unscrew the cap on the trap positioned under­neath the boiler, ll it with water and ret it
Warning! insucient water in the trap can temporarily cause the ue gas to be expelled into the surrounding ambient air
Water circuit diagram
Underoor heating
For appliances with underoor heating, t a safety thermostat onto the underoor heating outlet. For the electrical connec­tion of the thermostat see the section on “Electrical connections
- page
24”.
If the outlet temperature is too high, the boiler will stop both do­mestic hot water and the heating production and the error code 1 16 “oor thermostat contact open” will appear on the display. The boiler will restart when the thermostat is closed during automatic resetting.
If the thermostat cannot be installed, the underoor heating equi­pment must be protected by a thermostatic valve, or by a by-pass to prevent the oor from reaching too high a temperature.
14
1. Manual air vent
2. Overheat thermostat
3.
Burner
4.
Detection electrode
5.
C.H. ow temperature
probe
6.
C.H. return temperature
probe
7.
Secondary heat ex-
changer
8.
C.H. pressure relief valve
1
2. Condensate trap
14. C.H. circuit lter
15.
D.H.W. Flow switch
16.
diverter valve
17.
water pressure sensor
18.
circulation Pump
19.
expansion vessel
20. modulating Fan
21. ignition electrodes
22. thermal fuse
9. D.H.W. temperature probe
10.
By-pass
11. Drain valve
Connecting the Flue
118 mm
See table
118 mm
4
Flue System The provision for satisfactory ue termination must be made as described in BS 5440-1. The appliance must be installed so that the ue terminal is expo­sed to outdoor air. The terminal must not discharge into another room or space such as an outhouse or lean-to. It is important that the position of the terminal allows a free passage of air across it at all times. The terminal should be located with due regard for the damage or discolouration that might occur on buildings in the vicinity, it must also be located in a place not likely to cause nuisance. In cold or humid weather water vapour may condense on leaving the ue terminal. The eect of such “steaming” must be considered. If the terminal is less than 2 metres above a balcony, above ground or above a at roof to which people have access, then a suitable stainless steel terminal guard must be tted.
The minimum acceptable spacing from the terminal to obstruc­tions and ventilation openings are specied in Fig. 1.
installation
Fig. 1
- A Directly below an opening, window, etc 300 mm
- B Horizontally to an opening, window, etc 300 mm
- C Below gutters, soils pipes or drain pipes 75 mm
- D Below eaves 200 mm
- E From vertical drain pipe or soil pipe 75 mm
- F From internal or external corner 300 mm
- G Above ground, roof or balcony level 300 mm
- H From a surface facing the terminal 2500 mm
- I From a terminal facing a terminal 2500 mm
- J Vertically from a terminal on the same wall 1500 mm
- K Horizontally from an terminal on the same wall 300 mm
- L Fixed by vertical ue terminal
See table on page 21
Fig. 2
180
15
installation
150 mm
118
* pente 5 mm par mètre
150 mm
* pente
Warning
The exhaust gas ducts must not be in contact with or close to inammable material and must not pass through building struc­tures or walls made of inammable material. When replacing an old appliance, the ue system must be chan­ged.
Important
Ensure that the ue is not blocked. Ensure that the ue is supported and assembled in accordance with these instructions.
Installation without extension
Installation with extension
slope
Fitting the Coaxial Flue (Ø 60 / 100 Horizontal)
Contents: 1x Silicone O-Ring (60mm) 1x Elbow (90°) 2x Wall Seals (Internal & External) 1x Flue Pipe including Terminal (1 metre - 60/100) 2x Flue Clamps 4x Screws 2x Seals
Once the boiler has been positioned on the wall, t the rubber ue seal into the internal ue turret (see diagram opposite),
insert the elbow into the socket and rotate to the required po­sition. note: It is possible to rotate the elbow 360° on its vertical axis.
Level
Fig. 3
Level
slope 5 mm per metre
e.g. X = 555mm 753-555 = 198mm (Length to be cut from the plain end of the ue).
Once cut to the required length, ensure that the ue is free from burrs and reassemble the ue. If tting the ue from inside of the building attach the grey outer wall seal to the ue terminal and push the ue through the hole, once the wall seal has passed through the hole, pull the ue back until the seal is ush with the wall. Alternatively, the ue can be installed from outside of the building, the grey outer seal being tted last.
Should the ue require extending, the ue connections are push t, however, one ue bracket should be used to secure each metre of ue.
Note: See table for maximum and minimum ue runs.
Using the ue clamp, seals and screws supplied (Fig 4) secure the elbow to the boiler.
The 1 metre horizontal ue kit (3318073) supplied is suitable for an exact X dimension of 753mm.
Measure the distance from the face of the external wall to the face of the ue elbow (X - Fig 2), this gure must now be su­btracted from 753mm, you now have the total amount to be cut from the plain end of the ue.
Draw a circle around the outer ue and cut the ue to the requi­red length taking care not to cut the inner ue, next cut the inner ue ensuring that the length between the inner and outer ue is maintained. (Fig 4).
16
Clamp
180 mm
installation
Screws
Seal
Fig. 4
Fitting the 5” Flue (Ø 80 / 125 Horizontal/vertical)
Fig. 5
Once the boiler has been positioned on the wall, it is necessary to insert the Ø80/125 adaptor (Fig. 5) for both horizontal and vertical ue runs into the boiler ue socket (not supplied with ue kit - Part No 3318095).
Push the adaptor onto the boilers ue connection, grease the seals then add extensions or elbows as required, secure the adaptor, using the clamp and screws provided.
To t extensions or elbows it is rst necessary to ensure that the lip seal is tted correctly into the inner ue, once veried, it is simply necessary to push them together, no clamps are neces­sary to secure the ue components.
Before proceeding to t the ue, ensure that the maximum ue length has not been exceeded (See the tables) and that all elbows and bends have been taken into consideration, the ma­ximum ue length is 10 metres, for each additional 90° elbow 1 metre must be subtracted from the total ue length, and for each 45° 0.5 metres must be subtracted from the total ue length (the height of the vertical adaptor and a 45° bend can be seen in Fig.6 and a 90° bend in Fig. 7).
Note: DO NOT cut the vertical ue kit.
Fig. 6 Fig. 7
17
installation
180 mm
Fitting the Coaxial Flue (Ø 60 / 100 Vertical)
Note: See table for maximum and minimum ue runs.
Contents: 1x Silicone O-Ring (60mm) 1x Conical Adaptor (60/100mm) 1x Vertical Flue Kit (80/125mm) 3x Screws
The vertical ue kit is supplied with a specially designed weather proof terminal tted, it can be used either with a at roof or a pitched roof.
The Vertical ue kits useable lengths with the pitched roof ashings are indicated in Fig. 7.
Before proceeding to t the ue, ensure that the maximum ue length has not been exceeded (See the tables) and that all elbows and bends have been taken into consideration, the maximum ue length is see table, for each additional 90° elbow 1 metre must be subtracted from the total ue length, and for each 45° 0.5 metres must be subtracted from the total ue length (the height of the vertical adaptor and a 45° bend can be seen in Fig. 8).
Mark the position of the ue hole in the ceiling and/or roof (see Fig. 7 for distance from wall to the centre of the ue).
Fig. 7
Cut a 130mm diameter hole through the ceiling and/or roof and t the ashing plate to the roof.
DO NOT cut the vertical ue kit.
To connect the vertical ue kit directly to the boiler, place the vertical starter kit (Part No. 3318079) (see Fig. 7) onto the exhaust manifold and secure with the clamp, t the vertical adaptor onto the vertical starter kit (note: there is no need to use a clamp to secure this as it is a push t connection), the vertical ue kit must then be inserted through the roof ashing, this will ensure that the correct clearance above the roof is provided as the terminal is a xed height.
Should extensions be required, they are available in 1 metre (Part No. 3318077), 500mm (Part No. 3318078) and 160mm lengths, they must be connected directly to the vertical starter kit before connecting the adaptor to allow the vertical ue kit to be tted. In the event that extension pieces need to be shortened, they must only be cut at the male end and it must be ensured that the inner and outer ue remain ush.
When utilising the vertical ue system, action must be taken to ensure that the ue is supported adequately to prevent the wei­ght being transferred to the appliance ue connection by using 1 ue bracket per extension.
18
Fig. 8
When the ue passes through a ceiling or wooden oor, there must be an air gap of 25mm between any part of the ue system and any combustible material. The use of a ceiling plate will faci­litate this. Also when the ue passes from one room to another a re stop must be tted to prevent the passage of smoke or re, irrespective of the structural material through which the ue passes.
installation
Fitting the Twin Pipe (Ø80 / 80)
When siting the twin ue pipe, the air intake and exhaust terminals must terminate on the same wall, the centres of the t
erminals must be a minimum of 280 mm apart and the air intake must not be sited above the exhaust terminal (refer to Fig. 10). The air intake pipe can be run horizontally, however, the terminal and the nal 1 metre of ue must be installed either horizontally or with a slight fall away from the boiler to avoid rain ingress.
It is also strongly recommended that the air intake pipe run be constructed of insulated pipe to prevent condense forming on the outside of the tube.
The maximum permissible ue length for twin ue is dependent on the type of run used (see table on page 21).
For further information relating to ue runs not illustrated, please contact the Technical Department on 0870 241 8180.
Note: See table for maximum and minimum ue runs.
Where it is not possible to terminate the ue within the distance permitted for coaxial ues, the twin ue pipe can be used by tting a special adaptor to the ue connector and using the aper­ture for the air intake located on top of the combustion chamber.
Always ensure that the ue is adequately supported, using one ue bracket per extension and avoiding low points. (MTS supply suitable clamps as Part No. 705778). To utilise the air intake it is necessary to:
1) Take the air intake cover o the top of the appliance ) Assemble the ange on the header supplied with the boiler
2
3) Insert the header on the tube or the elbow up until the lower
stop (you do not have to use the washer).
4) Insert the elbow/header in the boiler air intake hole and fasten
it with screws.
The twin ue pipes can be tted with or without additional elbows and need no clamps, simply ensure that the red o-ring is inserted in the female end of the ue pipe and push the exten­sion piece fully into the previous section of ue pipe or elbow, check that the o-ring is not dislodged when assembling the ue (greasing the seal will aid assembly).
Twin pipe can also be converted back to Coaxial ue to enable vertical termination with a coaxial kit by using the pipe bridge (Twin - Coaxial Adaptor - Part No. 3318089). When running the twin ue pipe vertically.
It is not possible to terminate concentrically horizontally. Termi­nation is only possible with separate air and exhaust terminals.
19
installation
EXHAUST
AIR INTAKE
AIR INTAKE
AIR INTAKE MUST NOT BE
FITTED ABOVE THE EXHAUST
195
105
120
180
Fig. 9
For coaxial systems, the maximum development value, mentio­ned in the table below also takes into account an elbow. For twin ue systems the maximum development value, mentio­ned in the table includes the exhaust gas/air intake terminal.
Type 5 outlets should respect the following instructions: 1- Use the same ø 80 mm ue pipes for the air intakes and
exhaust gas ducts.
2- If you need to insert elbows in the air intake and exhaust gas
ducts, you should consider for each one the equivalent length
to be included in the calculation of developed length. 3- The exhaust gas duct should jut above the roof by at least 0.5 m. 4- The intake and exhaust gas ducts in Type C13 + C53 must be
installed on the same wall, or where the exhaust is vertical and
the air intake horizontal, the terminals must be on the same
side of the building.
Fig. 10
20
Loading...
+ 44 hidden pages