Ariston 47-116-17 User Manual

Installation Instructions Type C Boilers
G.C.N: 41-116-03
47-116-17
LEAVE THESE INSTRUCTIONS WITH THE END-USER
Country of destination: GB
2752275
This manual is an integral and essential part of the product. It should be kept with the appliance so that it can be consulted by the user and our authorised personnel.
Please carefully read the instructions and notices about the unit contained in this manual, as they provide important information regarding the safe installation, use and maintenance of the product.
For operating instructions please consult the separate User’s Manual.
1. GENERAL INFORMATIONTABLE OF CONTENTS
1. GENERAL INFORMATION
1.1. GENERAL INFORMATION
1.3. OVERALL V
IEW
2. INSTALLATION
2.1. REFERENCE S
TANDARDS
2.2. SITING THE APPLIANCE
2.3. OVERALL DIMENSIONS
2.4. MINIMUM CLEARANCES
2.5. MOUNTING THE APPLIANCE
2.6. E
LECTRICAL CONNECTION
2.7. G
AS CONNECTION
2.8. W
ATER CONNECTIONS
2.9. FLUE CONNECTIONS
2.10. A
CCESSORY CONNECTION
2.10.1. R
OOM THERMOSTAT CONNECTION
2.10.2. REMOTE CONTROL CONNECTION
2.10.3. ACCESSORY CONNECTION TERMINAL BLOCK
2.10.4. CYLINDER TEMPERATURE PROBE CONNECTION
2.10.5. REMOTE CONTROL TERMINAL BLOCK AND CYLINDER PROBE
2.11. E
LECTRICAL DIAGRAM
2.12. WATER CIRCUIT DIAGRAMS
3. COMMISSIONING
3.1. INITIAL PROCEDURES
3.2. REMOVING THE CASING
3.3. C
ONTROL PANEL
3.4. INITIAL START-UP
3.5. DISPLAY:MESSAGES SHOWN DURING N
ORMAL OPERATION
3.6. OPERATING PARAMETERS
3.6.1. CONTROL MODES
3.6.2. O
UTDOOR SENSOR
3.6.3. S
ETTINGS D
ISPLAY
3.7. REGULATIONS
3.7.1. POTENTIOMETER
3.7.2. SETTING THE TEMPERATURE FIELD
3.7.3. COMFORT KEY/HEATING ONLY
3.7.4. POST-CIRCULATION OF THE PUMP
3.7.5. TEST MODE
3.7.6. R
EGULATION MENU TABLE
3.8. BOILER SAFETY SYSTEMS
3.9. COMBUSTION ANALYSIS
3.10. D
RAINING
4. GAS ADJUSTMENTS
4.1. O
VERALL VIEW
4.2. PRELIMINARIES
4.3. GAS REGULATION
4.3.1. T
EST OF THE CONNECTION PRESSURE
4.3.2. REGULATION OF THE THERMAL POWER
4.4. CHANGING THE TYPE OF GAS
4.5. O
PERATING TESTS
5. ZONE V ALVES
6. MAINTENANCE
6.1. GENERAL REMARKS
6.2. C
LEANING THE PRIMARY EXCHANGER
6.3. CLEANING THE CONDENSATE TRAP
6.4. OPERATIONAL TEST
7. TECHNICAL INFORMATION
1.1. G
ENERAL I
NFORMATION
Read the instructions and recommendations in these Installation Instructions carefully to ensure proper installation, use and maintenance of the appliance.
Keep this manual in a safe place. You may need it for your own reference while our Servicing Centre technicians or your installer may need to consult it in the future.
This is a combined appliance for the production of central heating (C.H.) and domestic hot water (D.H.W.).
This appliance must be used only for the purpose for which it is designed. The manufacturer declines all liability for damage caused by improper or negligent use.
No asbestos or other hazardous materials have been used in the fabrication of this product.
Before connecting the appliance, check that the information shown on the data plate and the table on pages 4-5 comply with the electric, water and gas mains of the property. You will find the data plate on the reverse of the control panel. The gas with which this appliance operates is also shown on the label at the bottom of the boiler.
Do not install this appliance in a damp environment or close to equipment which spray water or other liquids.
Do not place objects on the appliance. Do not allow children or inexperienced persons to use the appliance
without supervision. If you smell gas in the room, do not turn on light switches, use the
telephone or any other object which might cause sparks. Open doors and windows immediately to ventilate the room. Shut the gas mains tap (on the gas meter) or the valve of the gas cylinder and call your Gas Supplier immediately. If you are going away for a long period of time, remember to shut the mains gas tap or the gas cylinder valve.
Always disconnect the appliance either by unplugging it from the mains or turning off the mains switch before cleaning the appliance or carrying out maintenance.
In the case of faults or failure, switch off the appliance and turn off the gas tap.Do not tamper with the appliance. For repairs, call your local Authorised Servicing Centre and request the use of original spare parts. For in-guarantee repairs contact MTS (GB) Limited
The technical information and instructions provided herein below are intended for the installer so that the unit may be installed correctly and safely.
The installation and initial start-up of the boiler must be by a CORGI Approved Installer in compliance with the installation standards currently in effect, as well as with any and all local health and safety standards i.e.CORGI.
This appliance must be installed by a competent installer in accordance with the current Gas Safety (installation & use) Regulations.
The installation of this appliance must be in accordance with the relevant requirements of the current Gas Safety (installation & use) Regulations, the Local Building Regulations, the current I.E.E.Wiring Regulations, the byelaws of the local water authority, and in Scotland, in accordance with the Building Standards (Scotland) Regulation and Health and Safety document No.635 “Electricity at work regs. 1989”. Installation should also comply with the following British Standard Codes of Practice:
2. INSTALLATION
2.1. R
EFERENCE STANDARDS
Low pressure pipes BS 6891 1988
Boilers of rated input not exceeding 60 kW BS 6798 1987
Forced circulation hot water system BS 5449 1990
Installation of gas hot water supplies for domestic purposes ( 2
nd
family gases) BS 5546 1990
Flues BS 5440-1 1990 Air supply BS 5440-2 1989
3
275
24 MFFI
LEGEND:
1. Flue connector
2. Heating flow temperature probe
3. Mixer
4. Condensate collector
5. Expansion vessel
6. Condensate trap (tube)
7. Condensate trap
8. Diverter valve
9. Main circuit flow switch
10. Domestic hot water temperature probe
11. Control panel
12. Gas valve
13. Domestic hot water flow switch
14. Drain valve
15. Safety valve (3 bar)
16. Secondary heat exchanger
17. Circulation pump with automatic air release valve
18. Heating return temperature probe
19. Sealed combustion chamber
20. Combustion chamber inspection hatch
21. Fan
22. Ignition and detection electrode
23. Main heat exchanger (aluminium)
24. Automatic by-pass
25. Silencer
F
IG. 1.1
1.3. OVERALL VIEW
24 RFFI SYSTEM
2.3. OVERALL DIMENSIONS
FIG. 2.1
24 MFFI
24 RFFI SYSTEM
4
275
The appliance may be installed in any room or indoor area, although particular attention is drawn to the requirements of the current I.E.E. Wiring Regulations, and in Scotland, the electrical provisions of the Building Regulations applicable in Scotland, with respect to the installation of the combined appliance in a room containing a bath or shower.
Where a room-sealed appliance is installed in a room containing a bath or shower the boiler and any electrical switch or appliance control, utilising mains electricity should be situated so that it cannot be touched by a person using the bath or shower.
The location must permit adequate space for servicing and air circulation around the appliance as indicated in paragraph 2.4. The location must permit the provision of an adequate flue and termination. For unusual locations special procedures may be necessary. BS 6798-1987 gives detailed guidance on this aspect. A compartment used to enclose the appliance must be designed specifically for this purpose. No specific ventilation requirements are needed for an installation within a cupboard. This appliance is not suitable for outdoor installation.
The type C appliances (in which the combustion circuit, air vent intake and combustion chamber are air-tight with respect to the room in which the appliance is installed) can be installed in any type of room.
There are no limitations with respect to ventilation and the volume of the room itself. The boiler must be installed on a solid, permanent wall to prevent access to the electrical parts (when live) through the aperture on the back frame.
2.2. SITING THE APPLIANCE
L
EGEND:
A = Central Heating Flow (3/4”) B = Domestic Hot Water Outlet (1/2”) C = Gas Inlet (3/4”) D = Domestic Cold Water Inlet (1/2”) E = Central Heating Return (3/4”) F = Cylinder Flow (3/4”) G = Cylinder Return (3/4”) H = Condensate discharge
20
=
67 67
65 65
155
181
100
(A-B-D-E)
208 (C)
=
Fasten the boiler in place using the template and anchors supplied with the unit. It is highly recommended that a spirit level be used to position the boiler so that it is perfectly level. For additional information, please consult the instructions contained in the connection kit and the flue kit.
2.5. MOUNTING THE APPLIANCE
2.6. ELECTRICAL CONNECTION
For safety purposes, have a competent person carefully check the electrical system in the property, as the manufacturer will not be held liable for damage caused by the failure to earth the appliance properly or by anomalies in the supply of power. Make sure that the residential electrical system is adequate for the maximum power absorbed by the unit, which is indicated on the rating plate. In addition, check that the section of cabling is appropriate for the power absorbed by the boiler.
The boiler operates with alternating current, as indicated in the technical data table (1.2), where the maximum absorbed power is also indicated. Make sure that the connections for the neutral and live wires correspond to the indications in the diagram. The appliance electrical connections are situated on the reverse of the control panel (see the servicing manual for further information)
FIG. 2.3
2.7. GAS CONNECTION
The local gas region contractor connects the gas meter to the service pipe. If the gas supply for the boiler serves other appliances ensure that an adequate supply is available both to the boiler and the other appliances when they are in use at the same time. Pipe work must be of an adequate size. Pipes of a smaller size than the boiler inlet connection should not be used.
5
275
In order to allow for access to the interior of the boiler for maintenance purposes, the boiler must be installed in compliance with the clearance requirements indicated in the diagram below.
2.4. MINIMUM CLEARANCES
FIG. 2.2
24 MFFI
24 MFFI SYSTEM
IMPORTANT!
In the event that the power supply cable must be changed, replace it with one with the same specifications. Make the connections to the terminal board located within the control panel, as follows:
- The yellow-green wire should be connected to the terminal marked with the earth symbol; make sure to re-use the ferrule mounted on the other supply cord;
- The blue wire should be connected to the terminal marked “N”;
- The brown wire should be connected to the terminal marked “L”. Note: The diagrams for the electrical system are indicated in section
2.11.
Warning,this appliance must be earthed.
External wiring to the appliance must be carried out by a qualified technician and be in accordance with the current I.E.E. Regulations and applicable local regulations. The Genus range of boilers are
supplied for connection to a 230 V~ 50 Hz supply.
The supply must be fused at 3 A.
The method of connection to the electricity supply must facilitate complete electrical isolation of the appliance, by the use of a fused double pole isolator having a contact separation of at least 3 mm in all poles or alternatively, by means of a 3 A fused three pin plug and unswitched shuttered socket outlet both complying with BS 1363. The point of connection to the Electricity supply must be readily accessible and adjacent to the appliance unless the appliance is installed in a bathroom when this must be sited outside the bathroom.
6
275
2.8. WATER CONNECTIONS
L
EGEND:
A = Central Heating Flow B = Domestic Hot Water Outlet C = Gas Inlet D = Domestic Cold Water Inlet) E = Central Heating Return F = Cylinder Flow G = Cylinder Return H = Condensate discharge I = Safety valve discharge
C
ENTRAL HEATING
Detailed recommendations are given in BS 6798:1987 and BS 5449­1:1990, the following notes are given for general guidance.
P
IPE WORK:
Copper tubing to BS EN 1057:1996 is recommended for water pipes. Jointing should be either with capillar y soldered or compression fittings. Where possible pipes should have a gradient to ensure air is carried naturally to air release points and water flows naturally to drain taps. The appliance has a built-in automatic air release valve, however it should be ensured as far as possible that the appliance heat exchanger is not a natural collecting point for air. Except where providing useful heat, pipes should be insulated to prevent heat loss and avoid freezing. Particular attention should be paid to pipes passing through ventilated spaces in roofs and under floors.
B
Y-PASS:
The appliance includes an automatic by-pass valve, which protects the main heat exchanger in case of reduced or interrupted water circulation through the heating system, due to the closing of thermostatic valves or cock-type valves within the system.
A
C
B
D E
I
A
C
G
D E
I
F
VIEW OF THE BOILER CONNECTIONS
FIG. 2.4
24 MFFI
24 MFFI SYSTEM
H
H
SYSTEM DESIGN:
This boiler is suitable only for sealed systems.
DRAIN COCKS:
These must be located in accessible positions to permit the draining of the whole system. The taps must be at least 15mm nominal size and manufactured in accordance with BS 2870:1980.
S
AFETY VALVE DISCHARGE:
The discharge should terminate facing downwards on the exterior of the building in a position where discharging (possibly boiling water & steam) will not create danger or nuisance, but in an easily visible position, and not cause damage to electrical components and wiring. The discharge must not be over an entrance or a window or any other type of public access.
C
ONDENSATE DISCHARGE:
The condensate discharge hose from the boiler must be inserted by at least 50 mm into a suitable acid resistant pipe - e.g. plastic waste or overflow pipe. The condensate discharge pipe must have a continuous fall and preferably be installed and terminated within the building to prevent freezing. The discharge pipe must be terminated in a suitable position:
i) Connecting in to an internal soil stack (at least 450 mm above
the invert of the stack).A trap giving a water seal of at least 75 mm must be incorporated into the pipe run , there also must be an air break upstream of the trap.
ii) Connecting into the waste system of the building such as a
washing machine or sink.The connection must be upstream of the washing machine/sink (If the connection is down stream of the waste trap then an additional trap giving a minimum water seal of 75 mm and an air break must be incorporated in the pipe run, as above.
iii) Terminating into a gully, below the grid level but above the
water level.
iv) Into a soakway.
N
OTE: If any condensate pipe work is to be installed externally,
then it should be kept to a minimum and be insulated with a waterproof insulation and have a continuous fall.
A
IR RELEASE POINTS:
These must be fitted at all high points where air naturally collects and must be sited to facilitate complete filling of the system. The appliance has an integral sealed expansion vessel to accommodate the increase of water value when the system is heated. It can accept up to 7 l (1.5 gal) of expansion water. If the heating circuit has an unusually high water content, calculate the total
FIG. 2.5
Fitting the connection kit to the ecoGENUS 24 RFFI SYSTEM only.
It will be noted that the kit has two connections not required for this boiler i.e. the domestic cold inlet “D” and the domestic hot water outlet “B” (see fig.
2.4). Although the cold water main supply must be connected to the isolation valve for the purpose of operating the filling-loop, the isolation valve is NOT connected to the boiler and should be left in the OFF position. The D.H.W. outlet is capped-off on the boiler, therefore not requiring the isolation valve to be used. The ecoGENUS 24 RFFI SYSTEM has 2 x 3/4" B.S.P. male threads for the cylinder flow and return. It is recommended that 2 x 22mm x 3/4" female iron fittings (not supplied) be used on these connections (using P.T.F.E. tape), before the boiler is mounted on the wall.
7
275
In F
IG. 2.11 below, several different types of flue systems are shown.
For additional information regarding the flue accessories, please consult the Flue Pipe Accessories manual.
Coaxial
Systems
Twin Pipe
Systems
Exhaust Type
C
13
B
33
outlet of fumes in
chimney or exhaust flue
C13, C33, C
43
C
53,C83
B
23
Maximum Extension
Exhaust/Air
(m)
4
4
31 (S1=S2)
55 (S1+S2)
54 (S2)
Diameter
of Pipes
(mm)
Ø 60/100
Ø 60/100
Ø 80/80
Ø 80/80
Ø 80
TERMINAL POSITION mm
A - Directly below an open window or other opening 300 B - Below gutters, solid pipes or drain pipes 75 C - Below eaves 200 D - Below balconies or car-port roof 200 E - From vertical drain pipes and soil pipes 75 F - From internal or external corners 300 G - Above ground or below balcony level 300 H - From a surface facing a terminal 600
I - From a terminal facing a terminal 1200
J - From an opening in the car port
(e.g.door, window) into dwelling 1200 K - Vertically from a terminal in the same wall 1500 L - Horizontally from a terminal in the same wall 300
FIG. 2.6
2.9. FLUE CONNECTIONS
FLUE SYSTEM
The provision for satisfactory flue termination must be made as described in BS 5440-1. The appliance must be installed so that the flue terminal is exposed to outdoor air . The terminal must not discharge into another room or space such as an outhouse or lean-to. It is important that the position of the terminal allows a free passage of air across it at all times. The terminal should be located with due regard for the damage or discolouration that might occur on buildings in the vicinity. In cold or humid weather water vapour may condense on leaving the flue terminal. The effect of such “steaming”must be considered. If the terminal is less than 2 metres above a balcony, above ground or above a flat roof to which people have access, then a suitable terminal guard must be fitted. When ordering a terminal guard, quote the appliance model number.
A suitable terminal guard is available from:
TOWER FLUE COMPONENTS Morley Road Tonbridge Kent TN9 1RA
R
ESIDUAL HEAD OF THE BOILER
expansion and add an additional sealed expansion vessel with adequate capacity.
MAINS WATER FEED - CENTRAL HEATING:
There must be no direct connection to the mains water supply even through a non-return valve, without the approval of the Local Water Authority.
F
ILLING:
A temporary method for initially filling the system and replacing lost water during servicing and initial filling (in accordance with Water Supply Byelaw 14), is provided as an integral part of the connection kit (see F
IG. 2.5). The flexible hose must be removed
once the system has been filled. The D.H.W. inlet valve on the connection kit has two positions, one for winter and one for the summer. This enables the flow-rate through the appliance to be adjusted so that a sensible D.H.W. temperature may be achieved throughout the year.
D
OMESTIC W
ATER
The domestic water must be in accordance with the relevant
recommendation of BS 5546:1990. Copper tubing to BS EN 1057:1996 is recommended for water carrying pipe work and must be used for pipe work carrying drinking water.
The minimum acceptable spacing from the terminal to obstructions and ventilation openings are specified in Fig.2.6
8
275
FIG
. 2.11
2.10. ACCESSORY CONNECTION
To carry out the connection for the roomstat or the outdoor sensor, proceed as follows:
1. Unscrew the screws “A” and rotate the control panel forwards;
2. Insert the connection cable for the thermostat or the outdoor
sensor into the cable gland “B” and open the lid of the control panel after having first unscrewed fastening screws “C”.
3. Insert the connecting cable into the cable clamp “D” shown in the figure and fasten it.
4. Remove the grommet “E” shown in the figure, make a hole in it and pass the connecting cable for the roomstat or the outdoor sensor through it.
5a. In order to connect up the roomstat, remove the link that is
located in the “F” terminal (marked with the initials “TA”) and connect the cables.
5b. To connect up the outdoor sensor, insert the cables into the “G”
clamp (marked with the initials “SE”).
6. Return the grommet “E” to its initial position, then close back the lid and lastly return the control panel to its place.
7 If a remote time clock is to be fitted, disconnect the integral time
clock plug from the P.C.B.
8 Using a volt-free switching time clock, connect the switching
wires from the time clock following points 1-6 above.
9 If using a time clock and room thermostat, these must be
connected in series as per points 1-8 above.
Note: Only a two-wire type room thermostat can be used.
For details on fitting the D.H.W. probe (ecoGENUS 27 RFFI only), please consult the separate instruction sheet supplied with the probe. An anti-frost device is built-in to the appliance’s electronic regulation system.
1
2.10.1. ROOM THERMOSTAT CONNECTION
2
3
4
B
D
A
C
E
F
G
E
9
275
Refer to the illustrations in section 2.10.1.
1. Unscrew the screws “A” and rotate the control panel forwards.
2. Insert the connecting cable of the under floor heating sensor into
the cable gland “B” and open the lid of the instrument panel after having unscrewed the fastening screws “C”.
3. Remove a blind grommet, make a hole in it and insert the connecting cable of the under floor heating sensor through it.
4. Remove the jumper located in the flying clamp
5. Connect the cables of the under floor heating sensor to the flying
clamp connected to position C6 on the P.C.B. (in place of the position previously occupied by the jumper).
6. Bring the grommet back to its initial position, close the lid and lastly the control panel.
2.10.4. UNDER FLOOR HEATING CONNECTION
2.10.5. REMOTE CONTROL TERMINAL BLOCK,
CYLINDER PROBE AND SECONDARY OUTLET
C5 (1-2) (red)
C6 (3-11) (grey)
C7 (1-9) (violet)
CONNECTIONS TO THE P.CB.
JUMPER: UNDER FLOOR HEATING SENSOR
REMOTE CONTROL
SECONDAR Y OUTLET (LPG valve, secondary pump)
2.10.3. ACCESSORY CONNECTION TERMINAL BLOCK
2.10.2. REMOTE
CONTROL CONNECTION
Refer to the illustrations in section 2.10.1.
1. Unscrew the screws “A” and rotate the control panel forwards.
2. Insert the connecting cables of the remote control into the cable
gland “B” and open the lid of the control panel after having unscrewed the fastening screws “C”.
3. Remove a blind grommet, make a hole in it and pass the connecting cable of the remote control through it.
4. Connect the cables of the remote control to the flying lead (see section 2.11.) connected to position C5 on the P.C.B. (positions with no closed jumper).
5. Bring the grommet back to its initial position, then close the lid and lastly the control panel.
N
OTE
: The wir ing of the RC must be done by using 2 x 0.5 mm
2
cable this guarantees a maximum length of 500 m. The “BUS” cable of the RC must be wired separately from the 230 VAC cable.
NOTE: The wiring of the Outdoor Sensor (SE) must be done by using
2 x 0.5 mm
2
cable this guarantees a maximum length of 50 m. The sensor must be positioned at least 2 - 2.5 m above the ground and where possible facing north.The sensor must not be exposed to direct sunlight.
LEGEND
:
A: JUMPER
When needed, the P.C.B. allows the different options to be selected by means of a wire link. The boiler has the following basic arrangement:
1 OPEN 2 CLOSED (jumper) 3 OPEN 4 OPEN 5 OPEN 6 OPEN 7 CLOSED 8 OPEN (MFFI); CLOSED (SYSTEM)
N
OTE
: under absolutely no circumstances must jumpers 2, 7 and 8
be removed. The opening of such contacts will lead to boiler malfunction.
This is the factory configuration. It is recommended that this set-up not be changed, unless under the following particular circumstances: JUMPER 3: if the contact is closed, the Secondary Output (flying
clamp connected to connection C7; positions 1-9) controls an LPG valve (optional).
JUMPER 4: if the contact is closed, the continuous operation of
the pump is selected. If the contact remains open, it has no effect and there is no change in the operation of the boiler.
JUMPER 5: if the contact is closed, the signal transmitted by the
connection of the secondary output clasp (connected to C7; positions 1-9) relates to a secondary pump (optional). If the contact remains open, the output signal controls a zone valve
(optional). JUMPER 6: not used JUMPER 7/8:
I = inserted (contact closed) N.I = not inserted (contact open)
N
OTE: it is essential that the operations involving setting of the
jumpers be carried out only with the device turned off.
10
275
The P.C.B. is fitted with 2 fuses, on the live and the neutral. The fuse holder contains:
- 5 x 20mm “3.15A Slow”glass fuses
2.11. ELECTRICAL DIAGRAM
B: Control microprocessor C: Flame detection jumper (under no circumstances should this
jumper be moved from the 1-2 position) D: Anti-cycling device (RA) E: Maximum heating output regulation (PR) F: Soft-light regulation (RLA) G: Operating mode selector knob H: Heating temperature adjustment I: Domestic hot water temperature adjustment J: Remote control module K: Main microprocessor L: Relay M: Fuses (2 x 0.54 A SLOW) N: Transformer (PRI: 230V-50Hz; SEK: 10V-0,8VA; SEK:10V-3,5VA;
SEK:10V-3,5VA;) O: Fuses (2 x 3.15 A SLOW) P: Earth Q: Spark generator R: Connection to the main P.C.B. S: Comfort light T: Programming keys U: Comfort key V: Alpha-numeric display X: Set and reset key W: Connection to PC
C1 = FAN
1: “Hall” sensor power supply 12V (red) 2: “Hall” sensor ground (blue) 3: Not used 4: Start of coil (black) 5: “Hall” sensor input (white) 6: End of coil (brown)
C2 = POWER SUPPLY
1: Earth (yellow/green) 2: Earth (yellow/green) 3: Not connected 4: Neutral (blue) 5: Not connected 6: Live (brown)
7
N.I.
I.
N.I.
I.
8
N.I. N.I.
I. I.
CONFIGURATION
Central heating only MFFI Not used RFFI System
11
275
2.12. WATER CIRCUIT DIAGRAMS
LEGEND:
1- Fan 2 - Main Heat exchanger 3 - Ignition/detection electrode 4 - Burner 5 - Gas valve 6 - Heating return temperature probe 7 - Heating flow temperature probe 8 - Silencer 9 - Motorised valve 10 - Automatic by-pass 11 - Main circuit flow switch 12 - Domestic hot water temperature probe 13 - Secondary heat exchanger 14 - Domestic hot water inlet filter 16 - Drain valve 17 - Safety valve 18 - Pressure gauge 19 - Circulation pump with automatic air release valve 20 - Expansion vessel 21 - Condensate trap inspection cap 22 - Condensate trap 23 - Condensate discharge tube 24 - Condensate trap inlet 25 - Injector 26 - Domestic hot water flow switch
24 MFFI
C3 = CONNECTION TO ROOMSTAT
1: Input - 1 2: Input - 2
C4 = TIMER
1: 3 V output 2: Timer ground 3: Timer output 4: Not connected
C5 = REMOTE CONTROL (Bus+/Bus-)
1: Input/output-1 2: Input/output-2
C6 = SENSOR CONNECTOR
1: Domestic hot water flow switch (grey) 2: Main circuit flow switch (grey) 3: Under floor heating thermostat (grey) 4: Heating flow sensor (grey) 5: Heating return sensor (grey) 6: Domestic hot water sensor (grey) 7: Not used: jumper 8: Outdoor sensor (grey) 9: Domestic hot water flow switch (grey) 10: Main circuit flow switch (grey) 11: Under floor heating thermostat (grey) 12: Flow sensor (grey) 13: Heating sensor (grey) 14: Domestic hot water sensor (grey) 15: Not used: under floor heating 16: Outdoor sensor (grey)
C7 = EQUIPMENT CONNECTIONS
1: Secondary output (optional) 2: Gas valve (white) 3: 3-way valve neutral (white) 4: Pump (white) 5: Ionisation (black) 6: Not connected 7: Ground 8: Pump earth (yellow/green) 9: Secondary output (optional) 10: Gas valve (brown) 11: 3-way valve (domestic hot water) (brown) 12: 3-way valve (heating) (brown) 13: Pump (brown) 14: Not connected 15: Earth 16: Gas valve earth (yellow/green)
12
275
3. COMMISSIONING
3.1. INITIAL PREP ARATION
MTS (GB) Limited support the initiative. Within the information pack you will find a copy of the logbook. It is important that this is completed in the presence of your customer, they are shown how to us it, and it is signed by them.Please instruct your customer that they must have their logbook with them whenever they contact a service engineer or us.Preliminary electrical system checks to ensure electrical safety must be carried out by a competent person i.e. polarity, earth continuity, resistance to earth and short circuit.
F
ILLING THE HEATING SYSTEM:
Remove the panels of the case and lower the control panel (see section 3.2. for further information). Open the central heating flow and return cocks supplied with the connection kit. Unscrew the cap on the automatic air release valve one full turn and leave open permanently. Close all air release valves on the central heating system. Gradually open valve(s) at the filling point (filling-loop) connection to the central heating system until water is heard to flow, do not open fully. Open each air release tap starting with the lower point and close it only when clear water, free of air, is visible.
Purge the air from the pump by unscrewing the pump plug and also manually rotate the pump shaft in the direction indicated by the pump label to ensure the pump is free.
Close the pump plug. Continue filling the system until at least 1 bar registers on the pressure gauge. Inspect the system for water soundness and remedy any leaks discovered.
F
ILLING OF THE D.H.W. SYSTEM:
Close all hot water draw-off taps. Open the cold water inlet cock supplied with the connection kit. Open slowly each draw-off tap and close it only when clear water, free of bubbles, is visible
G
AS SUPPLY:
Inspect the entire installation including the gas meter, test for soundness and purge, all as described in BS 6891:1988. Open the gas cock (supplied with the connection kit) to the appliance and check the gas connector on the appliance for leaks.
When the installation and filling are completed turn on the central heating system (sect. 3.4) and r un it until the temperature has reached the boiler operating temperature. The system must then be immediately flushed through. The flushing procedure must be in line with BS 7593:1992 Code of practice for treatment of water in domestic hot water central heating systems. During this operation, we highly recommend the use of a central heating flushing detergent (Fernox Superfloc or equivalent), whose function is to dissolve any foreign matter that may be in the system.
Substances different from these could create serious problems to the pump or other components.
The use of an inhibitor in the system such as Fernox MB-1 or equivalent is strongly recommended to prevent corrosion (sludge) damaging the boiler and system.
Failure to carry out this procedure may invalidate the appliance warranty.
24 RFFI SYSTEM
LEGEND
:
1- Fan 2 - Main Heat exchanger 3 - Ignition/detection electrode 4 - Burner 5 - Gas valve 6 - Heating return temperature probe 7 - Heating flow temperature probe 8 - Silencer 9 - Motorised valve 10 - Automatic by-pass 11 - Main circuit flow switch 12 - Non-return valve (integral to Jig Kit) 13 - Filling loop (integral to Jig Kit) 14 - Indirect cylinder expansion vessel 15 - Expansion relief valve 16 - Drain valve 17 - Safety valve (3 bar) 18 - Pressure gauge 19 - Circulation pump with automatic air release valve 20 - Expansion vessel 21 - Condensate trap inspection cap 22 - Condensate trap 23 - Condensate discharge tube 24 - Condensate trap inlet 25 - Injector
3.3. CONTROL PANEL
A. Selector Knob for Summer/Winter/Flue Test Modes B. Domestic Hot Water Temperature Adjustment Knob C. Central Heating Temperature Adjustment Knob D. On/Off L.E.D. E. On/Off Knob F. “COMFORT” Function Push-button/heating only (RFFI SYSTEM) G. “COMFORT” Function L.E.D./heating only (RFFI SYSTEM) H. Reset Button I. Multifunction Display J. Heating System Pressure Gauge K. Time Clock L. Programming “+”key M. Programming “-” key
When necessary configure the main P.C.B.according to the following diagram (please refer to the legend on page 17)
I = inserted (contact closed) N.I = not inserted (contact open)
SECONDARY OUTLET = conntection C7 (position 1-9 page 17)
1. Make sure that:
- the cap of the automatic air release valve is loosened;
- the system pressure is at least 1 bar on the pressure gauge;
3.4. INITIAL START-UP
3.2. REMOVING THE CASING
To disassemble the front casing panel, follow these steps:
1. Unscrew the screws “A” (1/4 turn only) and rotate the control panel forwards;
2. Unscrew the screws “B”;
3. Unhook the front panel of the casing by lifting it.
To disassemble the side panels, follow these steps:
4. Unscrew the screws “C” (at bottom) fastening the side panels;
5. Lift and unhook the panels.
13
275
A
1
B
2
3
C
4 5
POSITION
3
4
5
INSERTED
Secondary outlet (connection C7; positions 1-9) controls a LPG valve (optional).
Continuous pump operation.
Secondary output relates to a secondary pump (optional).
NOT INSERTED
The secondary outlet controls what is selected by Jumper 5.
No change in pump operation.
Secondary output controls a zone valve (optional)
7
N.I.
I.
N.I.
I.
8
N.I. N.I.
I. I.
CONFIGURATION
Central heating only MFFI Not used RFFI System
14
275
3.5. DISPLAY:MESSAGES SHOWN DURING
N
ORMAL OPERATION
3.6. OPERATING PARAMETERS
3.6.1. CONTROL
MODES
During operation of the boiler, while it is carrying out its normal operations, the left-hand display shows a series of characters that refer to the operations indicated below:
--
Diagnostics phase (precedes the other operations)
00
No request for heat
CC
Heating, burner off
CC..
Heating, burner on
cc
Pump overrun for heating
dd
Domestic hot water, burner off
dd..
Domestic hot water, burner on
hh
Pump overrun for domestic hot water
bb
Storage cylinder, burner off (SYSTEM version)
bb..
Storage cylinder, burner on (SYSTEM version)
N
OTE: the flashing dot on the left-hand display always indicates
“burner off”; if the still dot indicates “burner on”. The right-hand display (two-digit) shows:
- in HEATING mode: temperature of the heating system flow;
- in DOMESTIC HOT WA TER mode:temperature of domestic hot water.
The boiler has been designed to allow easy intervention with regard to the operating parameters.
The generation of the set-point and the request for heat are clarified in the following diagram, with regard to the heating mode.
* See section 3.6.2. The remote control and the timer are available as an accessory Kit: in the preceding diagram, it is clear that in the event that a device of this type is not installed, the calculation of the set-point depends on an outdoor sensor (if installed) and is carried out by the P.C.B.
N
OTE
: a configuration is also possible which allows for the
simultaneous presence of a remote control and an outdoor sensor.In this case, the flow temperature is calculated as a function of the external temperature and the room temperature. In this manner, it is possible to carry out a particularly efficient modulation, which allows considerable comfort to be obtained, combined with savings in fuel. The influence of the roomstat and the timer are shown in the following diagram, taking into consideration the fact that:
- ON/OFF Room ther mostat installed: contact open or closed, controlled by the room thermostat temperature sensor.
- ON/OFF Room thermostat not installed: contact closed (jumper).
- Timer installed: contact open or closed, controlled by the timer settings entered by the user.
- Timer not installed: contact open.
LEFT RIGHT
- the gas cock is closed;
- the electrical connection has been carr ied out in the correct manner. To allow the air to escape from the system, proceed as follows:
- turn on the On/off knob “D” and position the selector knob “A” in the “winter” position. The boiler pump will start up and three consecutive attempts will be made to ignite the burner. After the third attempt, the electronic system will shutdown the boiler, because the supply of gas has been cut off. The message “A01” will appear on the display;
- let the pump operate until all the air has escaped from the system;
- repeat the procedure for bleeding the radiators of air;
- draw hot water for a short while;
- check the system pressure and, if it has gone down, fill it with water until it returns to 1 bar.
2. Check the flue system for products of combustion.
3. Check that any required local ventilation inlets are open.
4. Fill the boiler condensate trap with water. N.B. In the event of prolonged period of system shutdown, the condensate trap should be filled before any renewed use. A shortage of water in the trap is dangerous because it could possibly lead to a leakage of fumes into the air.
5. Turn on the gas cock and check the seals on the connections,
including the one for the burner, making sure that the meter does not signal the passage of gas. Check the connections with a soap solution and eliminate any leaks.
6. Press the reset button “H” for the lighting system; the spark will light the main burner. If the burner does not light the first time, repeat the procedure.
The boiler is configured in the factory for the gas type in question. It is not necessary to regulate the gas type on installation. N
OTE: the reference values of the CO
2
are contained in the
T
ECHNICAL INFORMATION
section on page 4.
Schematic representation of the influence exerted by the roomstat and by the timer on the request for heat and on the calculation of the set-point (flow temperature of the primary circuit) by means of the external temperature values:
The type of curve is entered by means of the controls of the display P.C.B located under the lid of the P.C.B. itself. To access the programming buttons (+ / -), raise the lid with a screwdriver as shown in the illustration.
In the event of the chosen curve not being the most suitable for the type of system, it may be changed (selecting a more appropriate one) or moved until the desired thermal behaviour is obtained for the boiler and the system.
15
275
3.6.2. OUTDOOR SENSOR
In the case of the use of an outdoor sensor, the microprocessor­controlled P.C.B. calculates the most suitable flow temperature, taking into account the external temperature and the type of system. The microprocessor is capable of doing this because it is possible to establish a link between the external temperature and the flow temperature of the heating system water. This link translates into a "thermal curve". The type of curve should be chosen in correspondence with the planned temperature of the system and the nature of the heat loss present in the building. The flow temperature directly influences the room temperature, therefore making reference to the room temperature is equivalent to indicating variations in the temperature of the building.
-
+
PROCEDURES AND PRACTICAL EXAMPLES
: If the building is always cold, under all external temperature conditions (and therefore in all seasons), the steps to take are as follows: The curve must be translated parallel to itself, i.e. raising the flow temperature (and thereby the room temperature) in parity with the external temperature.
It is possible to carry out this operation by heating temperature knob. The konb in vertical position set a temperature oh 20°C.Turning the knob on the right it’s possible to set a higher room temperature.
In this manner, temperatures for the water coming out of the boiler are set successively higher, which then influence the room temperature increasing it to the desired settings.
While turning the knob the display shows “d.xx” for few seconds, “xx” is the room temperature set. Alternatively, it is possible to lower the output temperature of the boiler if the room temperature is too hot. It is possible obtain this turning the knob on the left translating lower the curve.
NB: The last effect achieved by adjusting the thermal curves is to change
the behaviour of the system in relation to the room temperature. If the curve used has been selected underestimating the thermal needs of the building, i.e.it is too “low”, it is possible that the building will not heat up sufficiently (the boiler will arrive to the set-point before the building reaches the desired temperature); the result is that the building will feel cold.
100
60
789
6
5
4
3
2
1
20
+20
-20
16
275
The general conditions to follow upon installation are the following: Warning (see 3.7.2) * The curves 1,2,3,4,5,6 could be set in the lower temperature; * The curves 5,6,7,8,9 could be set in the upper temperature;
CURVE 1: under floor heating (radiant panels at ultra-low
temperature).Planned temperature 30/20°C.
CURVE 2-3: under floor heating (radiant panels, low temperature
radiant plate systems).Planned temperature 40/30°C.
If the room temperature is too cold during the winter (while in spring the temperature is adequate), it is necessary to enter a steeper curve. To do this, press the reset button for 5 seconds and then press it repeatedly until the
letter “FF” appears (using the “+” and “-” keys). In this manner, the curves may be selected from 1 to 5.
Alternatively, if the building is too warm in the winter, while the room temperature is adequate in warmer seasons, it is necessary to choose a less steep curve, adjusting it in the same manner as above.
For buildings with standard insulation, materials and exposure, it is recommended initially that the straight line not be moved parallel to itself. If a timer is installed, it is possible to set different temperatures for daytime and night-time. It is therefore possible to lower the temperature that the P.C.B. calculates in relation to the values provided by the outdoor sensor by a quantity decided by the user for night-time operation.To do
this, it is necessary to select the night function “uu”, in the following manner:
- press the reset key for 5 seconds;
- press the same key again once to make the “nn” character appear;
- using the programming keys “+” and “-”, select a value from 0 to 12 depending on the amount of night-time lowering of the temperature desired.
CURVE 4-5: conventional low temperature boilers (cast iron and
aluminum radiators, radiant plate systems). Planned temperature 60/45°C.
CURVE 6-7: conventional low temperature boilers (cast iron and
aluminum radiators, radiant plate systems). Planned temperature 75/60°C.
CURVE 8-9: boilers with higher temperatures (radiators, convectors,
fan coils).Planned temperature 90/75°C.
In the opposite situation (in which the building is too hot in spring and adequately heated in winter), a higher curve (“dd” and “+”) must first be chosen and then “moved”turning the heating temperature knob.
If the following situation occurs: with low external temperatures (e.g: winter, -20°C) the building is adequately heated, but with favourable climatic conditions (e.g: spring, +20°C) it is not sufficiently heated, it is
necessary first to choose a lower curve (“FF” on the display and then “-”) and then turning the heating temperature knob.
17
275
3.7.2. SETTING THE TEMPERATURE FIELD
Remove the protection of the display using a screwdriver as a lever. Press the reset button for over 5 seconds. The display will show
AA0033
. On pressing the reset button again the display will change to
RR0000
(R indicates the setting of the field of regulation of the flow temperature). Using the button “E”, the setting may be changed. It is possible to choose two fields of regulation of the flow temperature.
0000
signifies that the flow temperature (which may be set by means of the knob on the front control panel) may be regulated from 30 to 75°C.
0011
signifies that the flow temperature (which also may be set by means of the knob on the front control panel) may be regulated from 42 to 82 °C.The factory setting is
0000
.
The boiler allows the convenience level to be increased in the output of domestic hot water by means of the “COMFORT” function. This function keeps the secondary exchanger warm during the periods in which the boiler is inactive, thereby allowing the initial water drawn to be at a higher temperature. The function may be activated by pressing the “H” key on the control panel (see section 3.3.). When the function is active, a green light comes on, again located on the control panel.
N
OTE: During the overrun period of the pump, the “COMFORT”
function, if selected, is temporarily deactivated. The L.E.D. light remains on to indicate that the boiler will return to the “COMFORT” mode once the pump overrun is terminated.
This function may be activated by pressing the “H” key on the control panel (see section 3.3.). When the function is active, a green light comes on, again located on the control panel.This indicates that the external indirect cylinder is not maintained at the set temperature, only the anti-frost protection of the indirect cylinder is active. When the temperature goes below 5°C, the boiler turns itself on and heats up the indirect cylinder until the temperature goes over 10°C.
H
EATING ONLY KEY:
24 RFFI
3.7. REGULATIONS
To access the areas reserved for the regulation and control, open the control panel, after having first unscrewed the plastic fastening screws, and raise the rubber protection stopper for the potentiometers, as shown in the illustration.
This allows access to the three regulation potentiometers:
1. RA - Ignition delay (anti-cycling device) potentiometer
It is possible to set the ignition delay by adjusting the potentiometer with a screwdriver. The values that may be selected range from 0 to 15 min. The delay has been set at 15 minutes in the factory. The value
D
ISPLAY MESSAGE REFERENCE
3.7.1. P
OTENTIOMETERS
The boiler is designed to monitor some operating variables and settings by means of the display on the front control panel. Keeping the reset key pressed for over 10 seconds allows access to the “readout” function of the main system variables. By pressing the button repeatedly after that, it is possible to read the following information in sequence:
Indication on the left-hand display
UU//11
UU//22
UU//55
UU//FF
UU//tt
PP//AA
PP//--
PP//LL
bb
ll
Value read on right-hand display
Flow temperature of the heating circuit (C°) Return temperature of the heating circuit (C°) Domestic hot water output temperature (C°) Ionisation current (expressed in bT) Main circuit flow switch Heating ignition delay (see section 3.6.4. ­expressed in min.x10) Maximum thermal power for heating (expressed in a percentage of the difference between the maximum power allowed by the boiler and the minimum) Soft light power (expressed in a percentage of the difference between the maximum power allowed by the boiler and the minimum) Last safety shut-off (see section 3.7.) Last shutdown (see section 3.7.)
3.6.3. SETTINGS DISPLAY
To return to the normal display, press the “H” reset key repeatedly until all the sequence of “readout” functions have scrolled through the display and until one of the “display of normal operations” has appeared (the message that appears will depend on the current operating mode of the boiler).
* N
OTE 1: U/1 means that “
uu
”and “11” blink alternately on the display
N
OTE 2: the value 100% appears as “
0000
” on the display
entered may be viewed in the manner described in section 3.6.3. (the display shows the value with steps of 10).
2. PR - Maximum heating circuit power potentiometer, variable
between the maximum allowed by the boiler and the minimum (see “T
ECHNICAL INFORMATION” table). The boiler is calibrated in
the factory at 70%.
3. RLA - Soft-light potentiometer, variable between the
maximum power (shown on the display as “
0000
”, i.e. 100%) and
minimum power (shown on the display as “
0011
”, i.e.1%).The boiler is calibrated in the factory at a value which is suitable for ignition with any type of gas (approx.70%). The display shows the value between 100% (“
0000
” on the display)
and 1% (“
0011
”) of this interval. The indications on the display with
regard to the power are shown in the graph:
3.7.3. COMFORT KEY:
24 MFFI
The pump overrun may be varied (after the burner has been tur ned off). To access this function, it is necessary to press the reset button for over 5 seconds and then press it repeatedly until the character
“AAappears on the left-hand display. The following modes are available:
0011
1 minute of pump overrun
0033
3 minutes of pump overrun
0066
6 minutes of pump overrun
0099
9 minutes of pump overrun
1122
12 minutes of pump overrun
1155
15 minutes of pump overrun
CCOO
24 hours of pump overrun
It is also possible to set a continuous pump operation by closing the contact of jumper 4 (see section 2.12.).
Safety shutdown:In the event that a safety shutdown occurs, it is necessary to contact an Authorised Service Centre.
DISPLAY
AA0011
AA0022
AA0033
AA0077
AA1199
AA2200
AA2211
AA2222
AA3333
AA9999
CAUSE
Too many attempts to ignite on starting up After three attempts at ignition, no increase in DT was detected The heating flow temperature exceeds 100°C during operation Too many failures to flame in one period during operation The flame was detected after the gas valve had closed The flame was detected before the gas valve opened The flow switch does not close The flow switch does not open Problem with the fan Problem with the electronic monitoring
NOTE: When there is no ignition, check that the gas cock is open.
18
275
3.7.4. PUMP OVERRUN
3.8. BOILER SAFETY SYSTEMS
3.7.6. R
EGULATION MENU TABLE
3.7.5. TEST MODE
Summary of the functions accessed when the RESET button is pushed for 5 seconds.
The boiler is protected from malfunctioning by means of internal checks by the P.C.B., which brings the boiler to a stop if necessary. In the event of the boiler being shut off in this manner, a code appears on the display which refers to the type of shut-off and the reason behind it. There are two types of shut-off:
- SAFETY SHUTDOWN :these group of errors (characterised on the display by the letter “EE”) this situation is automatically removed as soon as the cause behind it is resolved.
As soon as the origin of the shutdown disappears, the boiler starts up again and returns to its normal operation.
- SHUTDOWN: (characterised on the display by the letter “AA”), it is not removed unless a manual intervention is made. The boiler may return to operation only if reset by means of pressing the button “H” (see illustration on page 18) located at the centre of the display.
There follows a list of the shutdown modes and the respective codes shown on the display.
Shutdown (“AA” type): if such a situation occurs, it is necessary to reset the boiler using the appropriate key. If this shutdown occurs again, an Authorised Service Centre should be contacted.
The P.C.B. allows the boiler to be forced to the maximum or minimum power. To make the boiler operate at maximum power (100%: 24kW), it is necessary to turn the selector knob “A” (section 3.3.) and, using a light pressure, bring it to the < > position.To return the boiler to its normal function, turn the selector “A” to the summer or winter position.
N
OTE: To force the boiler to its maximum output it is necessary to
completely rotate the potentiometer for maximum heating output regulation (PR).
Loading...
+ 41 hidden pages